Manuel d'utilisation / d'entretien du produit 40106 Rev. H 05/05 du fabricant Pentair
Aller à la page of 36
Model 5600 & 5600 Econominder ® Service Manual IMPORTA NT: Fill in p ertinent info rmation on page 3 for future reference..
2 Model 5600 & 5600 Econominder ® Table of Contents Job Specification Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Residential Installation Check List .
Model 5600 & 5600 Econominder ® 3 Job Specification Sheet Job Number _______________ _________________ ___ Model Number __ __________________ ____________ W ater T est _____________ _________________ ______ Capacity of Unit __________ ______________ Max.
4 Model 5600 & 5600 Econominder ® General Residential Installation Check List W at er Pressur e A minimum of 25 lbs of water pressure is r equ ired for regeneration valve to operate effectively . Electrical Facilities An uninterrupted alternating current (A/C) suppl y is required.
Model 5600 & 5600 Econominder ® 5 Valve Installation and Start-up Procedures 1. Place the softener ta nk where you want to install the unit. NOTE: Be sure the tank is level and on a firm base. 2. During cold weather it is recommended th at the installer warm the valve to room temperature before operatin g.
6 Model 5600 & 5600 Econominder ® Model 5600 Installation and Start-up Procedures NOTE: Install the water softener with th e inlet, outlet and drain connections made according to manufacturer’ s recommendations and to m eet applicable plumbing cod es.
Model 5600 & 5600 Econominder ® 7 Model 5600 Backwash Filter Installation and Start-up Procedures NOTE: Install the water softener with the inlet, outlet and drain connections made according to manufacturer’ s recommendations and to meet applicable pl umbing codes.
8 Model 5600 & 5600 Econominder ® Model 5600 Backwash Filter Installation and Start-up Procedures (Cont’d.) Cycle Times and Flow Diagrams 1. In Service position. See Figure 4, page 10 . 2. Preliminary Rinse position. — Same as Figure 4, page 10 with standard piston (white end plug) or filter piston (black end plug).
Model 5600 & 5600 Econominder ® 9 Model 5600 Econominder Installation and Start-up Procedures NOTE: Install the water softener with the inlet, outlet and drain connections made according to manufacturer’ s recommendations and to meet applicable pl umbing codes.
10 Model 5600 & 5600 Econominder ® Water Conditioner Flow Diagrams Service Position Pr eliminary Rinse Position Figur e 4 : Service Position Figur e 5 : Preliminary Rinse Position.
Model 5600 & 5600 Econominder ® 11 Water Conditioner Flow Diagrams (Cont’d.) Backwash Position Brine Position Figur e 6 : Backwash Position Figur e 7 : Brine Position.
12 Model 5600 & 5600 Econominder ® Water Conditioner Flow Diagrams (Cont’d.) Slow Rinse Position Second Backwash Position Figur e 8 : Slow Rinse Position Figur e 9 : Second Ba ckwash Position.
Model 5600 & 5600 Econominder ® 13 Water Conditioner Flow Diagrams (Cont’d.) Settling Rinse Position Brine T ank Fill Position Figure 10 : Settling Rinse Position Figur e 1 1 : Brine T ank Fill.
14 Model 5600 & 5600 Econominder ® Model 5600 Control Valve Drive Assembly Figur e 12 : Model 5600 Control V alve Drive Assembl y 1 29 27 20 16 15 19 22 5 1A 1A 13 14 37 39 12 38 34 21 7 8 6 9 2 .
Model 5600 & 5600 Econominder ® 15 Model 5600 Control Valve Drive Assembly ▲ Not used when a filter valve Item Number No. Req’d Part Number Description 1 1 14448-010 housing, with pin 1 14448.
16 Model 5600 & 5600 Econominder ® Model 5600 and 5600 Econominder Control Valve Drive Assembly Figure 13 : Model 5600 and 5600 Econominder Control V alve Drive Assembly 48 47 10 49 50 12 11 9 8 .
Model 5600 & 5600 Econominder ® 17 Model 5600 and 5600 Econominder Control Valve Drive Assembly * not used wi th meter controls ▲ used in backwash fi lter Item Number No. Req’d Part Number Description 1 2-4 13255 adapter clip (c lock or meter) 2 5 13242 seal 5 17772 silicone s eal 3 1 61400-12 valve body asse mbly , 1 ″ dist.
18 Model 5600 & 5600 Econominder ® Model 5600 Econominder Control Valve Drive Assembly Figur e 14 : Model 5600 Econominder Control V alve Drive Assembly 29 1 27 19 20 18 21 1A 13 12 42 14 44 43 3.
Model 5600 & 5600 Econominder ® 19 Model 5600 Econominder Control Valve Drive Assembly Item Number No. Req’d Part Number Description 11 14448-000 housing, with roll pin 1 14488-001 housing, wit.
20 Model 5600 & 5600 Econominder ® Bypass Valve Assembly, Plastic Figur e 15 : Bypass V alve Assembly , Plastic Item Number No. Req’d Part Number Description 9 2 13305 o-ring, 1 19 10 2 13255 c.
Model 5600 & 5600 Econominder ® 21 Bypass Valve Assembly, Brass Figur e 16 : Bypass V alve A ssembly , Brass Item Number No. Req’d Part Number Description 1 1 17290 bypass valve body , 3/4".
22 Model 5600 & 5600 Econominder ® Model 5600 Econominder Meter Assembly Figure 17 : Model 5600 Eco nominder Meter Assembly Item Number No. Req’d Part Number Description 1 4 12473 screw , meter.
Model 5600 & 5600 Econominder ® 23 Service Instructions Replace Time Brine V alve, Injectors and Scr een 1. Unplug electrical cord from outlet. 2.
24 Model 5600 & 5600 Econominder ® Service Instructions (Cont’d.) Replace Timer 1. Unplug electrical cord from outlet. 2. Turn off water supply t o conditioner: — If the conditioner i nstallation has a “three valve” bypass system, fi rst open the valve in the bypass l ine, then close the valves at the conditioner inlet and ou tlet.
Model 5600 & 5600 Econominder ® 25 Service Instructions (Cont’d.) Replace Piston Assembly 1. Unplug electrical cord from outlet. 2. Turn off water supply to conditioner: — If the conditioner .
26 Model 5600 & 5600 Econominder ® Service Instructions (Cont’d.) Replace Seals and Spacers 1. Unplug electrical cord from outlet. 2. Turn off water supply t o conditioner: — If the condition.
Model 5600 & 5600 Econominder ® 27 Service Instructions (Cont’d.) Replace Meter 1. Unplug electrical cord from outlet. 2. Turn off water supply to conditioner: — If the conditioner installation h as a “three valve” bypass sy st em, first open the valve in the bypass line, then close the valves at the conditioner inl et and outlet.
28 Model 5600 & 5600 Econominder ® Service Instructions (Cont’d.) Replace Meter Cover and/or Impeller 1. Unplug electrical cord from outlet. 2. Turn off water supply to conditioner: — If the .
Model 5600 & 5600 Econominder ® 29 Model 5600 and 5600 Econominder Troubleshooting PROBLEM CAUSE CORRECTION 1. Softener fails to regenerate. A. Electrical service to un it has been interrupted. A. Assure permanent electrical service (check fuse, plug, pull chain or switch).
30 Model 5600 & 5600 Econominder ® Model 5600 and 5600 Econominder Troubleshooting (Cont’d.) General Service Hints for Meter Contr ol PROBLEM CAUSE CORRECTION 9. Softener fails to draw brine. A. Draw line flow control is plugged. A. Clean drain line flow control.
Model 5600 & 5600 Econominder ® 31 Model 5600SF Troubleshooting PROBLEM CAUSE CORRECTION 1. Filter fails to backwash. A. Electrical service to unit has been interrupted. A. Assure permanent electrical service (check fuse, plug, pull chain or switch).
32 Model 5600 & 5600 Econominder ® Service Assemblies Part Number Description 60102-00 piston, softener 60102-10 piston, filter 60102-20 piston, low water 60125 seal kit 60084-XX injector 60032 b.
Model 5600 & 5600 Econominder ® 33 Notes:.
34 Model 5600 & 5600 Econominder ® Notes:.
.
P/N 40106 Rev . H 05/05.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Pentair 40106 Rev. H 05/05 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Pentair 40106 Rev. H 05/05 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Pentair 40106 Rev. H 05/05, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Pentair 40106 Rev. H 05/05 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Pentair 40106 Rev. H 05/05, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Pentair 40106 Rev. H 05/05.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Pentair 40106 Rev. H 05/05. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Pentair 40106 Rev. H 05/05 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.