Operator’s Manual

This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-4 (motors and generators).

Thank you for purchasing this quality-built Briggs & Stratton generator. We’re pleased that you’ve placed your confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this manual, your generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with standby generators and how to avoid them. Because we do not necessarily know all the applications this equipment could be used for, it is important that you read and understand these instructions thoroughly before attempting to start or operate this equipment. This product is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. Save these original instructions for future reference.
This generator requires professional installation before use. Refer to the separate installation manual for full information. Your installer should follow the instructions completely.
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow Pages. There are thousands of Briggs & Stratton authorized service dealers worldwide who provide quality service. You can also contact Technical Service by phone at 800 732-2989, or click on Find a Dealer at BRIGGSandSTRATTON.COM, which provides a list of authorized dealers.
Generator and engine model and serial numbers should be recorded in the installation manual.
Briggs & Stratton Power Products Group, LLC P.O. Box 702 Milwaukee, WI 53201-0702
Copyright © 2013. All rights reserved. No part of this material may be reproduced or transmitted in any form without the express written permission of Briggs & Stratton Power Products Group, LLC.



SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
Hot Surface Rotating Parts
Chemical Burn Auto Start
Exploding Battery Rotating Belt/Pulley
Lift Hazard Read Manual
The safety alert symbol indicates a potential personal injury hazard. A signal word (DANGER, WARNING, or CAUTION) is used with the alert symbol to designate a degree or level of hazard seriousness. A safety symbol may be used to represent the type of hazard. The signal word NOTICE is used to address practices not related to personal injury.
CAUTION indicates a hazard which, if not avoided, could result in minor or moderate injury. NOTICE addresses practices not related to personal injury. The manufacturer cannot possibly anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and the tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique that the manufacturer does not specifically recommend, you must satisfy yourself that it is safe for you and others. You must also make sure that the procedure, work method or operating technique that you choose does not render the generator system unsafe.


injury.
engine to start at any time without warning resulting in minor or moderate injury.

For the Owner: To help you make informed choices and communicate effectively with your installation contractor(s), read and understand Owner Orientation in this manual before contracting or starting your generator installation. To arrange for proper installation, contact the store at which you purchased your generator, your dealer, a licensed electrician or your utility power provider. The generator warranty is VOID unless the system is installed by licensed electrical and plumbing professionals. Every effort has been made to ensure that information in this manual is accurate and current. However, we reserve the right to change, alter, or otherwise improve the product and this document at any time without prior notice. The Emission Control System for this generator is warranted for standards set by the U.S. Environmental Protection Agency and by the California Air Resources Board (CARB).
We sincerely appreciate your patronage. For this reason, we have made every effort to provide for a safe, streamlined and cost-effective installation. Because each installation is unique, it is impossible to know of and advise the trade of all conceivable procedures and methods by which installation might be achieved. Neither could we know of possible hazards and/or the results of each method or procedure. For these reasons, only current licensed electrical and plumbing professionals should attempt generator system installations. Installations must strictly comply with all applicable codes, industry standards and regulations. Your generator is supplied with this “Operator’s Manual” and a separate “Installation Manual”. These are important documents and should be retained by the owner after the installation has been completed.
This product is only for use as an optional generator system which provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and communication systems that, when stopped during any power outage, could cause discomfort or inconvenience.
For the Installing Dealer/Contractor: For most applications, the Installation manual contains all the information required to properly install and start the generator. This operator’s manual describes routine operation and owner maintenance procedures. If you need more information in this matter, please call 800 732-2989, between 8:00 AM and 5:00 PM CT.
Owner Orientation This section provides generator owners with the information necessary to achieve the most satisfactory and cost effective installation possible. The illustrations are for typical circumstances and are meant to familiarize you with the installation options available with your generator. A thorough understanding of these options will provide fundamental control over the cost of your installation, as well as ensure your final satisfaction and security. Federal and local codes, appearance, noise levels, fuel types, and distances are the factors that must be considered when negotiating with an installation professional. Remember that as the distance from the existing electrical service and gaseous fuel supply increases, and the number of 90 degree bends in the fuel supply increases, compensations in piping and wiring materials must be made. This is necessary to comply with local codes and overcome electrical voltage drops and gaseous fuel pressure drops. The factors mentioned above will have a direct affect on the overall price of your generator installation. In some areas you may need to acquire electrical permits for installing the generator, building permits for installing gas lines, and permits for noise allowances. Your installer should check your local codes AND obtain the permits before installing the system.
Every effort has been made to ensure that information in this manual is accurate and current. However, we reserve the right to change, alter, or otherwise improve the product and this document at any time without prior notice.
Only current licensed electrical and plumbing professionals should attempt generator system installations. Installations must strictly comply with all applicable codes, industry standards, laws and regulations.

Delivery Inspection Carefully inspect the generator for any damage that may have occurred during shipment. If loss or damage is noted at time of delivery, have the person(s) making delivery note all damage on the freight bill and affix his signature under the consignor’s memo of loss or damage. If loss or damage is noted after delivery, separate the damaged materials and contact the carrier and your installer for claim procedures. Missing or damaged parts are not warranted.
Power Decrease at High Altitude or High Temperature Air density is less at high altitudes, resulting in less available engine power. Specifically, engine power will decrease 3% for each 1,000 feet (300 meters) above sea level and 1% for each 10° F (5.6°C) above 77°F (25°C). Make sure you and your installer consider these factors when determining total generator load.

Generator Location The actual physical location of your generator has a direct affect on: 1. The amount of plumbing required to fuel your generator. 2. The amount of wiring required to control and connect

Read this operator’s manual and Important Safety Instructions before operating your generator.
Compare the illustrations of this model with your generator to familiarize yourself with the locations of various controls and adjustments. Save this manual for future reference.

Generator is pictured with access doors removed for clarity and screen guard open for clarity.
A - Exhaust Port — High-performance muffler lowers engine
J - Coolant Recovery Bottle — Located on inside of screen
sound level to comply with most residential codes.
guard. Provides visual indicator of engine coolant level.
B - Coolant Fill Door — Provides access for servicing engine
K - Oil Filter — Filters engine oil to prolong system life.
with coolant.
L - Fuel Inlet — Fuel supply is connected here.
C - Air Cleaner — Protects engine by filtering dust and
M - Oil Drain Hose — Provided to facilitate oil changing.
debris out of intake air.
N - ID Label (located on base) — Identifies unit by
D - Battery Door opening — Provides access to starting
serial number.
battery and air cleaner.
P - Circuit Breaker Enclosure — Equipped with removable
E - Engine Label — Identifies engine model and type.
bottom to assist with conduit connection.
F - Oil Dip Stick — Used to check the engine oil level.
R - Control Panel Door opening — Provides access to
G - Oil Fill Cap — Remove to service the engine with
control panel, oil filter, etc.
recommended oil.
S - Control Panel — Used for various test, operation and
H - Screen Guard — Prevents fingers from touching radiator
maintenance functions. See System Control Panel.
fan and houses the coolant recovery bottle. Must stay closed while generator is in use.

Each generator is supplied with a set of identical keys. These keys fit the locks that secure the access doors.
The system control panel is a printed circuit board that is integrated with the control panel of the generator. It contains all the logic circuits, operator controls, and system displays necessary to operate, program, and protect the generator. The system control panel interprets and monitors electrical inputs from related circuits throughout the unit.
one quarter turn counterclockwise. 2. Grasp door’s handle and turn one quarter turn
counterclockwise to open. Remove key. 3. Coolant Fill door is unlocked in the same manner. It can
Please refer to the supplied Control Panel Application Guide for detailed information about the control panel.
be used for adding coolant or oil.
Access Ports The generator is equipped with an enclosure that has several access doors. The doors are named for a significant component located behind them, as follows:: A - Fuel Inlet port (shown for reference) B - Control Panel door C - Exhaust opening (shown for reference) D - Coolant Fill door E - Battery door F - Muffler door
turn clockwise. 2. Insert key into lock of door handle and turn key one
quarter turn clockwise. Remove key.
The enclosure also includes muffler and radiator access panels, used for cleaning those components. Those panels should remain closed at all other times to assure proper cooling, reduce noise, and for added safety.
resulting in serious injury.




E F

The generator’s control board constantly monitors utility voltage. Should utility voltage drop below a preset level, the control board will signal the engine to crank and start.
When utility voltage is restored above a preset voltage level, the engine is signaled to shut down.
The actual system operation is not adjustable and is sequenced by sensors and timers on the control board, as follows:
Utility Voltage Dropout Sensor
This engine is shipped from the factory pre-run and filled with non-synthetic oil (API SL 10W-30W). This allows for system operation in a wide range of temperature and climate conditions. Before starting the engine, check oil level and ensure that engine is serviced as described in the Maintenance section.
Coolant System This engine is shipped from the factory filled with a 50-50 mix of automotive (ethylene glycol) anti-freeze and water. This will provide optimum year round protection against freezing, boiling and corrosion. Battery The installer must supply a valve-regulated, rechargeable 12 volt DC starting battery. See Battery in Final Installation Considerations in the installation manual.
Utility Voltage Pickup Sensor
This sensor monitors utility voltage. When utility voltage is restored above 80 percent of the nominal source voltage, a time delay starts timing and the engine will go to engine cool- down.
When utility power is sensed and the load transfers back to the utility source, the engine will go into a cool down period as described below:
15 Amp Fuse The generator’s 15 Amp fuse is critical to correct system operation. The 15 Amp fuse was removed at the factory to prevent the unit from starting during shipping. Your installer will ensure the fuse is properly installed upon completion of the installation.
Engine Oil · Engine Cool-down Timer

Shutdown Alarm Detection System
It is recommended to have the generator go through an excercise cycle once every seven days. During this exercise period, the unit runs for approximately 20 minutes and then shuts down.
The generator may have to run for long periods of time with no operator present. For that reason, the system is equipped with sensors that automatically shut down the generator in the event of potentially damaging conditions, such as low oil pressure, high temperature, over speed, and other conditions.
Refer to the Control Panel Application Guide supplied with this generator for more detailed information on the exercise timer.
The generator’s control board shows possible shutdown alarms descriptions on the digital display.
OR, refer to the Automatic Transfer Switch Application Guide for more detailed information on the exercise timer.
The possible shutdown alarms are listed below:
The generator warranty does not cover items that have been subjected to operator abuse or neglect. To receive full value from the warranty, the operator must maintain the system as instructed in the Maintenance section.
Before performing any generator maintenance, always perform the following steps:
The operator must reset the shutdown alarm detection system each time it activates.
Refer to the Control Panel Application Guide supplied with this generator for more detailed information on resetting the Shutdown Alarm Detection System. Overspeed
This shutdown alarm is indicated by Overspeed showing on the digital display. This condition occurs if the engine speed in greater than 115% of nominal engine RPM, which is derived from generator frequency. To remedy the problem, contact your installer or an authorized dealer. Underspeed
This shutdown alarm is indicated by Underspeed showing on the digital display. This condition occurs if the engine speed drops under the nominal engine RPM. To remedy the problem, contact your installer or an authorized dealer.

Low Oil Pressure This shutdown alarm is indicated by Low Oil Pressure on the digital display. The unit is equipped with an oil pressure switch that uses normally closed contacts held open by engine oil pressure during operation. Should oil pressure drop below the 8 psi range, switch contacts close and the engine will shut down. To remedy the low oil pressure condition, add the recommended oil to the FULL mark on the dipstick or contact your installer or an authorized dealer. High Coolant Temperature This shutdown alarm is indicated by High Coolant Temperature on the digital display. This condition occurs when the temperature of the coolant exceeds the shutdown threshold. To remedy the problem, contact your installer or an authorized dealer.
Generator CCW Rotation This shutdown alarm is indicated by Generator CCW on the digital display. This condition occurs when the generator phase is out of sequence. To remedy the problem, contact your installer or an authorized dealer.
Start Fail This shutdown alarm is indicated by Start Fail on the digital display. This condition occurs when the generator does not start. To remedy the problem, contact your installer or an authorized dealer.
Stop Fail This shutdown alarm is indicated by Stop Fail on the digital display. This condition occurs when the generator fails to stop. To remedy the problem, contact your installer or an authorized dealer.
External Shutdown 1,2 or 3 This shutdown alarm is indicated by External Shutdown on the digital display. To remedy the problem, contact your installer or an authorized dealer.
Battery Flat This shutdown alarm is indicated by Battery Flat on the digital display. This condition occurs if the controller loses power during starting sequence due to a bad battery condition. It will not try to start again until the battery is functioning properly. To remedy the problem, contact your installer or an authorized dealer.
Generator Circuit Breaker (GCB) Fail This shutdown alarm is indicated by GCB Fail on the digital display. This condition occurs when the generator circuit breaker trips or becomes non-functional. To remedy the problem, contact your installer or an authorized dealer.
Voltage Autodetect This shutdown alarm is indicated by Voltage Autodetect on the digital display. This condition occurs if the controller loses power during starting sequence due to a bad battery condition. It will not try to start again until the battery is functioning properly. To remedy the problem, contact your installer or an authorized dealer.
Generator Overvoltage This shutdown alarm is indicated by Generator Overvoltage on the digital display. This condition occurs when the output voltage exceeds the preset threshold. To remedy the problem, contact your installer or an authorized dealer.
Generator Undervoltage This shutdown alarm is indicated by Generator Undervoltage on the digital display. This condition occurs when the output voltage drops below the preset threshold. To remedy the problem, contact your installer or an authorized dealer.
Generator Overfrequency This shutdown alarm is indicated by Generator Overfrequency on the digital display. This condition occurs when the generator frequency is out of limits given by setpoints. To remedy the problem, contact your installer or an authorized dealer.
Generator Underfrequency This shutdown alarm is indicated by Generator Underfrequency on the digital display. This condition occurs when the generator frequency is out of limits given by setpoints. To remedy the problem, contact your installer or an authorized dealer.

Generator Maintenance Generator maintenance consists of keeping the unit clean. Operate the unit in an environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air louvers on the enclosure must not become clogged with snow, leaves, or any other foreign material. To prevent generator damage caused by overheating, keep the enclosure cooling inlets and outlets clean and unobstructed at all times. Check the cleanliness of the unit frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior/interior surface. Inspect the air inlet and outlet openings inside and outside the enclosure to ensure air flow is not blocked. DO NOT use direct spray from a garden hose to clean generator. Water can enter the engine and generator and cause problems.
Engine Maintenance The maintenance of an engine and related components are critical to its operating performance and lifespan. Industrial engines operate in an environment that often include hot and cold temperatures and extreme dust. The recommended maintenance schedule is listed in this section, however, environmental operating conditions and additional installed equipment may require more frequent inspection and servicing. The owner and/or authorized service technician should review the operating conditions of the equipment to determine the inspection and maintenance intervals. Proper engine cooling and lubrication are very important, so pay particular attention to these matters.
Engine Oil The engine is shipped from the factory pre-run and filled with non-synthetic oil (API SL 10W-30). This allows for system operation in a wide range of temperature and climate conditions.
FOR THE BEST FUEL ECONOMY AND COLD STARTING, SELECT THE LOWEST
SAE VISCOSITY GRADE OIL FOR THE EXPECTED TEMPERATURE RANGE
IF NEITHER SAE 10W-30 NOR SAE 15W-40 GRADE OILS ARE AVAILABLE, SAE 30 GRADE MAY BE USED AT TEMPERATURES ABOVE 4
DEGREES C (40F), SAE 40
DEGREES C (80F).
DO NOT USE SAE 10W-40 GRADE OIL OR ANY OTHER GRADE NOT RECOMMENDED
COLD WEATHER
Select and engine oil viscosity that will best match the prevailing daytime temperature. The oil must meet GM specification 9986231. Motor oils meeting this spec receive the API (American Petroleum Institure) starburst symbol:
It is noted that the GF-4 oils are also “backward compatible” and are equal or better than previous grades of oil in all aspects.
Synthetic Oils Synthetic Oils have been available for use in industrial engines for a relatively long period of time and may offer advantages in cold and hot temperatures. However, it is not known if synthetic oils provided operational or economic benefits over conventional petroleum-based oils in industrial engines. Use of synthetic oils does not permit the extension of oil change intervals.
Cleaning the Generator

Checking Engine Oil Level NOTICE: It is important to be careful when checking engine oil level. Oil must be maintained between the “ADD” and the “FULL” mark on the dipstick. To ensure that you are not getting a false reading, make sure the following steps are taken before checking the oil level. 1. Stop engine. 2. Turn the generator off. 3. Remove 15 Amp fuse from control panel. 4. Allow approximately five minutes for the oil to drain
POLLUTE. CONSERVE RESOURCES. RETURN USED OIL TO COLLECTION CENTERS.
Change oil while the engine is still warm from running. 1. Turn the generator off. 2. Remove 15 Amp fuse from control panel. 3. Place oil drain hose (B) into an approved container. 4. Open valve (A) located on bottom of oil pan. 5. When oil has drained, replace brass fitting on hose. 6. Remove oil filter and dispose of properly. 7. Before installing a new oil filter, lightly lubricate the oil
back into the oil pan. 5. Remove the dipstick. Wipe with a clean cloth or paper
towel and reinstall. Push the dipstick all the way into the dipstick tube. 6. Remove the dipstick and note the amount of oil on the
filter gasket with fresh, clean oil. 8. Install the oil filter by hand until the gasket contacts the
oil filter adapter, then tighten the oil filter ½ to ¾ turn. 9. Add the required amount of oil to bring the level up to,
dipstick. The oil level must be between the “ADD” and “FULL” marks. 7. If the oil level is below the “ADD” mark, reinstall the
but not over the “FULL” mark on the dipstick. Reinstall the oil filler cap to valve rocker arm cover and wipe any excess oil clean. 10. If all engine servicing is complete, replace 15 Amp fuse
dipstick and proceed to step 6. 8. Remove the oil filler cap from the valve cover. 9. Add the required amount of oil to bring the level up to,
in control panel and and turn the generator on and place in AUTO mode. To make the task of adding oil more convenient, we recommend use of a funnel attached to a length of tubing long enough to reach from the Coolant Fill door to the oil fill opening on the engine valve cover.
but not over, the “FULL” mark on the dipstick. Reinstall the oil filler cap to the valve rocker arm cover and wipe any excess oil clean.
Changing Engine Oil

Engine Coolant System It is important that the cooling system of the engine be maintained properly to ensure proper performance and longevity.
Engine Air Cleaner Once each year service the air cleaner, as follows. If operating in a dusty environment, service more often. 1. Turn the generator off. 2. Remove 15 Amp fuse from control panel. 3. Remove filter cartridge - Remove the service cover by
injury.
disengaging three clips and detaching cover, starting with the bottom two clips and the top clip last. Gently move the end of the filter back and forth, then rotate while pulling straight out. 4. Clean outlet tube and check Vacuator™
valve - Use a clean cloth to wipe the filter sealing surface and the outlet tube surfaces. Make sure that all contaminant is removed before the new filter is inserted. Be careful to not damage the sealing area on the tube.
Visually check and physically squeeze Vacuator valve
attached to service cover to make sure it is flexible and not inverted, damaged or plugged. 5. Clean filter - Use a soft bristle brush to loosen dirt
and a vacuum cleaner to remove dirt and debris. Low pressure air (not to exceed 25 psi) may also be used to blow away dirt. Replace filter cartridge if any holes are detected in filter media. 6. Install clean filter properly - Insert the filter carefully.
Seat the filter by hand, making certain it is completely into the air cleaner housing before securing the cover in place. To complete a tight seal, apply pressure by hand at the outer rim of the filter, not the flexible center. (Avoid pushing on the center of the urethane end cap.) No cover pressure is required to hold the seal. NEVER use the service cover to push the filter into
With the engine cold, check the coolant level in the coolant recovery bottle (see Controls). Specifications for the coolant system can be found in the Maintenance chart of this manual. Coolant Specification - ethylene glycol 50-50 mixture w/ distilled water.
place! Using the cover to push the filter in could cause damage to the housing, cover, or fasteners and will void the warranty. If the service cover hits the filter before it is fully in place, remove the cover and push the filter (by hand) further into the air cleaner and try again. The cover should go on with no extra force. 7. Reinstall service cover - Once the filter is in place,
reinstall the service cover, positioning the cover with the arrow and the word TOP to the top. Fasten the top clip first, the bottom two clips last. Make sure that all mounting bands, clamps, bolts, and connections in the entire air cleaner system are tight and verify absence of holes in piping - repair if needed. 8. Replace 15 Amp fuse in control panel. 9. Turn the generator on.

(indicated by NEGATIVE, NEG, or (-)). 6. Ensure hardware on both positive and negative battery
terminals is secure. 7. Reinstall 15 Amp fuse in control panel. 8. Turn the generator on. 9. Reset exercise timer. See Setting Exercise Timer.
DON’T POLLUTE. CONSERVE RESOURCES, RETURN USED BATTERY TO RECYCLING COLLECTION CENTER.
Charging the Battery If it is necessary to charge the battery, proceed as follows: 1. Turn the generator on. 2. Remove 15 Amp fuse from control panel. 3. Disconnect negative battery cable from negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
battery holds 12 Volts. DO NOT exceed 13.7 volts when charging battery. 5. Connect negative battery cable to negative battery
Battery Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
terminal (indicated by NEGATIVE, NEG, or (-)). 6. Ensure hardware on both positive and negative battery
terminals is secure. 7. Reinstall 15 Amp fuse in control panel. 8. Turn the generator off. 9. Reset exercise timer. See Setting Exercise Timer.
Servicing the Battery If it is necessary to service the battery, proceed as follows: 1. Turn the generator off. 2. Remove 15 Amp fuse from control panel. 3. Service or replace battery as required. See Battery
in Final Installation Considerations in the installation manual for specific battery needed. 4. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).

Natural Gas/Propane Fuel System The fuel system installed on this industrial engine has been designed to various standards to ensure performance and reliability. To ensure compliance to these standards, follow the recommended maintenance schedule contained in this section.
Pressure Regulator Maintenance and Inspection NOTICE: The pressure regulator components have been specifically designed and calibrated to meet the fuel system requirements of the engine.
Engine Exterior Periodically inspect the engine exterior for contamination and potential damage from dirt, leaves, rodents, spider webs, insects, etc. and remove.
Venturi/Throttle Control Device Maintenance and Inspection NOTICE: The venturi and throttle body components have been specifically designed and calibrated to met the fuel system requirements of the engine.
When Calling for Assistance You must have the following information at hand if it is necessary to contact a local service center regarding service or repair of this unit: 1. Obtain the unit Model Number and Serial Number from
the unit ID label. See Controls for location of the label or refer to the information recorded on the inside front cover of the installation manual. 2. Obtain the engine identification numbers from the
engine label. See the Installation manual for location of this information.
Storage The generator system is designed for long term service as a backup generator. There is no need to take any storage precautions. However, if it becomes necessary to take the system out of service for an extended period, call Technical Services at 800 743‑4115, between 8:00 AM and 5:00 PM CT for specific recommendations.

Maintenance Chart This maintenance schedule represents the manufacturer’s recommended maintenance intervals to maintain proper engine/ equipment function. Federal, State, or Local regulations may require additional or more frequent inspection or maintenance intervals than those specified above. Check with the authority having jurisdiction for details. Perform the following maintenance on the engine at the hours indicated and at equivalent hour intervals thereafter.

1000 1500 2000 2500 3000 3500 4000 4500 5000
Change engine oil and oil filter Every 100 hours or Annually
Check fuel system for leaks Before and after any service or maintenance activity
Inspect accessory drive belts X
Clean debris from radiator core Every 100 hours or 60 days of operation
Change coolant - ethylene glycol 50-50 mixture w/ distilled water X
Every 2,000 Hours or two years, whichever occurs first
Inspect battery case for leaks/damage X
Inspect all electrical connector retainer locks X
Inspect crank sensor timing wheel Every 100 hours or annually
Clean secondary ignition coil tower x
Inspect air cleaner Every 200 hours (or every 100 hours in severe environments) and Annually
Replace inline LPG filter x

Engine is running, but no AC output is available.
Engine runs good at no-load but “bogs down” when loads are connected.
Engine will not start; or starts and runs rough.
Engine shuts down during operation.
Loss of power on circuits. 1. Generator circuit breaker is open. 2. Transfer switch problems.

U.S. EPA, and Briggs & Stratton Corporation Emissions Control Warranty Statement for Emergency Standby Engines
Your Warranty Rights And Obligations September 2010
General Information The U.S. EPA, and Briggs & Stratton (B&S) are pleased to explain the emissions control system warranty on your Model Year 2010 and later engine / equipment. In the U.S., new Emergency Standby Engines greater than 25HP must be designed, built, and equipped to meet stringent emission standards. B&S must warrant the emissions control system on your engine / equipment. See Definition of appropriate use of Emergency Standby below. The emission-related warranty covers all components whose failure would increase an engine’s non-evaporative emissions of any regulated pollutant referenced below.
Manufacturer’s Warranty Coverage: Briggs & Stratton warrants that the engine is free from defects in material and workmanship, and is also designed, built, and equipped to conform to applicable regulations under Section 213 of the Clean Air Act, from the time the engine is sold, until the expiration of its warranty period. This warranty applies to all emission related engine components whose failure would cause engine exhaust emissions to be out of EPA compliance. Further, this warranty also applies to other engine components damaged due to the failure of any of these emissions related components. If a warrantable emissions related component on your engine is defective, the part will be repaired or replaced by B&S at no cost to you including diagnosis, parts, and labor. Warranty coverage period is two years from date of original purchase, and is offered to the original purchaser and each subsequent purchaser so long as Owner’s Warranty Responsibilities are adhered to.
IMPCO is the Manufacturer of Record for all Environmental Protection Agency (EPA) compliance issues related to the manufature and use of the engine. Please refer to Emissions Warranty for further information.
Emergency Stationary Engine Definition
An Emergency Stationary Engine is defined as any stationary internal combustion engine whose operation is limited to emergency situations and required testing and maintenance. Examples include stationary engines used to produce power for critical networks or equipment (including power supplied to portions of a facility) when electric power from the local utility (or the normal power source, if the facility runs on its own power production) is interrupted, or stationary engines used to pump water in the case of fire or flood, etc. Stationary engines used for peak shaving are not considered emergency stationary engines. Stationary engines used to supply power to an electric grid or that supply power as part of a financial arrangement with another entity are not considered to be emergency engines. Emergency stationary ICE may be operated for the purpose of maintenance checks and readiness testing, provided that the tests are recommended by Federal, State or local government, the manufacturer, the vendor, or the insurance company associated with the engine. Maintenance checks and readiness testing of such units is limited to 100 hours per year. There is no time limit on the use of emergency stationary engines in emergency situations. The owner or operator may petition the Administrator for approval of additional hours to be used for maintenance checks and readiness testing, but a petition is not required if the owner or operator maintains records indicating that Federal, State, or local standards require maintenance and testing of emergency ICE beyond 100 hours per year. Emergency stationary ICE may operate up to 50 hours per year in non-emergency situations, but those 50 hours are counted towards the 100 hours per year provided for maintenance and testing. The 50 hours per year for non-emergency situations cannot be used for peak shaving or to generate income for a facility to supply power to an electric grid or otherwise supply power as part of a financial arrangement with another entity. For owners and operators of emergency engines, any operation other than emergency operation, maintenance and testing, and operation in non-emergency situations for 50 hours per year, as permitted above is prohibited.
Form NO. 313540 Rev.-

STANDBY GENERATOR OWNER WARRANTY POLICY
Effective September 1, 2010 - replaces all undated Warranties and Warranties dated before September, 2010.
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or workmanship or both. Travel expenses are reimbursed as specified under the Briggs & Stratton Warranty Guidelines document to authorized Briggs & Stratton dealers for performing applicable warranty repair work. This warranty is effective for the time periods and subject to the conditions stated below. For all warranty service, find the nearest Authorized Service Dealer in our dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED WARRANTIES ARE EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you specific legal rights and you may also have other rights which vary from state to state or country to country.
The warranty period begins on the date of purchase by the first retail consumer and continues for the period of time stated above.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
If you have any questions regarding your warranty rights and responsibilities, you should contact B&S at 1-800-233-3723 or BRIGGSandSTRATTON.COM.
IMPCO is the Manufacturer of Record for all Environmental Protection Agency (EPA) compliance issues related to the use and performance of the engine. Please refer to Emissions Warranty for further information.
We welcome warranty repair and apologize to you for being inconvenienced. Any authorized service dealer may perform warranty repairs. Most warranty repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if equipment damage occurred because of misuse, lack of routine maintenance, and shipping, handling, warehousing or improper installation. Similarly, the warranty is void if the manufacturing date or serial number(s) on the equipment has been removed or the equipment has been altered or modified. During the warranty period, the authorized service dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use and service. This warranty will not cover the following repairs and equipment:
Warranty terms continue on next page.
Generator 4 years · Engine 2 years

Exclusions: 1. Wear items such as engine oil, oil gauges, o-rings, filters, fuses, spark plugs, anti-freeze, starting batteries, etc., or damage or malfunctions resulting from accidents, freezing, abuse, modifications, alterations, or improper servicing or chemical deterioration. 2. Any costs for adjustments, loose or leaking clamps or connections, installation or start-up operations fuel system cleaning and obstruction (due to chemical, dirt, carbon, lime, and so forth) and any failures caused by contaminated fuels, anti-freeze or oil, etc. 3. Units sold for primary power applications as defined by the U.S. & Canadian National Electric Codes, whether utility power exists or where utility power does not normally exist. * For purposes of this warranty, Prime Power is defined where the generator is a source of power where no electrical power is available from the UTILITY POWER GRID. If no UTILITY power is available, the generator is considered the prime power source. 4. Used, reconditioned, and demonstration equipment, equipment used in mobile or rental applications, and equipment used in life support applications. “Rental use” means any use of this product in a temporary or semi-permanently installed rental application. Once equipment has experienced rental use, it shall thereafter be considered rental use for purposes of this warranty. 5. Bodily injuries including death which results from product’s malfunction. 6. Enclosure is warranted against surface rust and corrosion for the first year of the warranty period. Surface rust and corrosion is defined as any rust or corrosion that has penetrated the paint but has not penetrated through the metal substructure. Enclosure is warranted against rust-through for the first three years of the warranty period. Rust-through is defined as rust or corrosion that has penetrated completely through the paint and metal substructure. Enclosure is not warranted for surface rust or corrosion or complete rust-through that may result due to improper installation, damage to painted surfaces that compromise the paint’s corrosion prevention properties, or if the unit is installed in environments that expose the generator to high levels of corrosive agents. 7. Accessory parts. 8. Any loss of revenue that is a direct or indirect result of the malfunction of this unit. 9. Malfunctions caused by any force majeure event or external force beyond the manufacturer’s control or Act of God such as, but not limited to freezing, theft, fire, collision, wars or riots, vandalism, lightning, earth quake wind storm, hail, volcanic eruption, water or flood damage, tornados, hurricanes, terrorist acts or nuclear holocaust. 10. Any incidental, consequential or indirect damages caused by defects in materials or workmanship or any delay in repair of replacement of the defective part(s). 11. Malfunction due to misapplication or misrepresentation. 12. Any mode of transportation deemed as abnormal in our judgment, such as planes, ferries, railroad, buses, helicopters, snowmobiles, snow-cats, off-road vehicles, etc. 13. Any and all expenses incurred investigating performance complaints unless defective Briggs & Stratton materials and/or workmanship were the direct cause of the malfunction.
MILWAUKEE, WI, USA
Generator Specifications
60kW
Series 60000* Voltage Rated Amps
Rated Maximum Load Current (at 40°C/104°F, LP or NG):
3 Phase Wye 120/208 215
at 240 Volts** 146 Amps at 1.0pf**
3 Phase Wye 139/240 186
Rated AC Voltage 120/240 Volts**
3 Phase Delta 120/240 186
3 Phase Wye 240/416 108
Rated Frequency 60 Hertz
3 Phase Wye 277/480 93
Normal Operating Range -20°F (-28.8°C) to 104°F
3 Phase Wye 346/600 73
Output Sound Level 65 dB(A) at 23 ft. (7 m) at normal load
Shipping Weight 2120 lb (962 kg)
* Natural gas rating will depend on specific fuel but typical derates are between 10 to 20% off the LP gas rating. ** Determine Voltage and Rated Amps using the chart to the right.
This generator is rated in accordance with UL (Underwriters Laboratories) 2200 (stationary engine generator assemblies) and CSA (Canadian Standards Association) standard C22.2 No. 100-4 (motors and generators).
Phase Three phase

Manual del operario
Sistema generador e nfriado por líquido
Este generador está clasificado conforme a la norma UL (Underwriters Laboratories) 2200 (grupos generadores de motor fijo) y a la norma C22.2 No. 100-04 (motores y generadores) de la CSA (Canadian Standards Association [Asociación canadiense de normalización]).
Pages mentionnées dans ce manuel — fabricant, assistance et téléchargements.
Problèmes fréquents, causes probables et solutions.
| Problème | Cause possible | Solution | |
|---|---|---|---|
| Engine is running, but no AC output is available. | 1. Circuit breaker open or defective. 2. Fault in generator control panel. 3. Poor wiring connections or defective transfer switch. | 1. Reset or replace circuit breaker. 2. Contact local service facility. 3. Check and repair. | p.21 |
| Engine runs good at no-load but “bogs down” when loads are connected. | 1. Short circuit in a connected load. 2. Generator is overloaded. 3. Shorted generator circuit. 4. Fuel pressure or mixture is incorrect. 5. Kinked fuel line. | 1. Disconnect shorted electrical load. 2. Turn off one or more loads. 3. Contact local service facility. 4. See Gaseous Fuel System in the Installation Manual. 5. Remove kink. Replace if necessary. | p.21 |
| Engine will not start; or starts and runs rough. | 1. 15 Amp fuse missing or blown. 2. Fuel supply turned off or depleted. 3. Failed battery. 4. Fuel pressure is incorrect | 1. Install (new) 15 Amp fuse. See System Control Panel. 2. Open fuel valve(s); check propane tank. 3. Replace battery. N 4. See Gaseous Fuel System in the Installation Manual. | p.21 |
| Engine shuts down during operation. | 1. Fuel supply turned off or depleted. 2. Fault indicator blinking. | O 1. Check fuel valves, fill propane tank. I T 2. Count blinks and refer to Fault Detection System. | p.21 |
| Loss of power on circuits. | C U 1. Generator circuit breaker is open. 2. Transfer switch problems. | 1. Reset circuit breaker. 2. See the transfer switch manual. | p.21 |