DRA-DCC-8 DIGIT AL TO 8 CURRENT LOOP CONVERTER User’s Guide http://www .omega.com e-mail: info@omega.com.
USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGASM Customer Service: 1-800-622-2378 / 1-800-622-BESTSM Engineering Service: 1-800-872-9436 / 1-800-USA-WHENS M TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA Mexico and Latin America: T el: (95) 800-TC-OMEGASM F AX: (95) 203-359-7807 En Espanol: (95) 203 359-7803 e-mail: espanol@omega.
C o n t e n t s 1. MOUNTING INSTRUCTIONS 2. REPLACING FUSES 3. ASSEMBL Y 4. SUPPL Y VOL T AGE 5. MODES OF OPERA TION 5.1 0-20 or 4-20mA output current selection 5.2 Switch Settings 6. P ARALLEL CONTROL MODE 6.1 PLC Inter face 6.2 The "E" (ENABLE) T erminal 7.
1. MOUNTING INSTRUCTIONS 2 The DRA-DCC-8 is designed for standard DIN rail mounting. Place the unit on the upper par t of the mounting rail with the fastening tab facing down. Using a suitable flat screwdriver loosen the tab slightly and attach the unit to the rail.
3 The DRA-DCC-8 is powered by a DC power supply at a range of 15-32Vdc. In order to determine the minimum supply voltage, use the following equation: Vmin = 8 + Rload( Ω ) * 0.02 where: Vmin is the minimum required supply voltage. Rload( Ω ) is the maximum output load including the leads resistance.
4 Figure 2. SW5 MSB Self T est Mode * according to para #5.2 6. P ARALLEL CONTROL MODE * according to para #5.2 In the parallel control mode, the DRA-DCC-8 unit is controlled via a 15 bit bus. Three Address bits (A0-A3) select the proper current output channel and 12 Data bits (D0-D11) determine its value (A0 and D0 are MSB).
5 6.2 THE "E" (ENABLE) TERMINAL For E="1" the unit is enabled, which means that all input vectors are received and the output is updated. When E="0" the unit ignores any new input vector . The E terminal is recommended to be used as a strobe for parallel data which has a long setup time.
6 7.4.1 BAUD RA TE SELECT SW1 and SW2 select one out of four available baud rates. 300 BPS 4800 BPS 9600 BPS 19200 BPS OFF SW1 SW2 OFF ON OFF OFF ON ON ON 7.4.2 ID CODE Up to eight DRA-DCC-8s can be connected in a multidrop configuration. Switches SW3, SW4, and SW5 (MSB) set the ID code.
7 Note: If the value is omitted it will be treated as zero. Separators such as blanks or commas are not allowed. Example: Channel 4 in DRA-DCC-8 no. 7 has to receive the value of 981.
8 8.1 SELF TEST #1 (Communication Por ts T est) In order to test the serial communication por ts, this test mode converts the unit to a transponder for ASCII characters. Any transmitted character will be echoed to the host terminal. The host parameters should be set to: Baud rate : 4800, W ord length: 8 bits, Parity: even, Stop bit: 1 8.
9 11. DRA-DCC-8 CALIBRA TION Generally there is no need to calibrate the DRA-DCC-8 unit. However if calibration is required, the following steps should be carried out: T wo potentiometer trimmers, one for "Zero" and the other for "Span" are located on printed card 7040.
10 INPUTS: P ARALLEL INPUTS LOGIC LEVELS: DA T A HOLD TIME: MAXIMUM P ARALLEL INPUT RA TE: SERIAL COMMUNICA TION BAUD RA TES: P ARITY : STOP BIT : ST A TUS REPORT : MUL TIDROP CAP ABILITY : OUTPUTS: O.
RETURN REQUESTS / INQUIRIES Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBT AIN AN AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SER VICE DEP ARTMENT (IN ORDER TO A VOID PROCESSING DELA YS).
Where Do I Find Ever ything I Need for Pr ocess Measurement and Control? OMEGA…Of Course! TEMPERA TURE ⻬ Thermocouple, R TD & Thermistor Probes, Connectors, Panels & Assemblies ⻬ W ire: .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Omega DRA-DCC-8 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Omega DRA-DCC-8 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Omega DRA-DCC-8, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Omega DRA-DCC-8 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Omega DRA-DCC-8, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Omega DRA-DCC-8.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Omega DRA-DCC-8. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Omega DRA-DCC-8 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.