Model information can be found on the name plate behind the front cover.
Please complete and mail the owner registration card furnished with this product, or register online at www.friedrich.com (USA only). For your future con ve nience, record the model information here.



Make sure the wiring is adequate for your unit. If you have fuses, they should be of the time delay type. Before you install or re lo cate this unit, be sure that the amperage rating of the circuit breaker or time delay fuse does not exceed the amp rating listed in Figure 1.
DO NOT use an extension cord. The cord provided will carry the proper amount of electrical power to the
unit; an ex ten sion cord will not.
Make sure that the receptacle is compatible with the air conditioner cord plug provided. This insures proper grounding. If you have a two prong receptacle you
will need to have it replaced with a grounded receptacle by a certifi ed electrician. The grounded receptacle should meet all national and local codes and ordinances. Under no circumstances should you remove the ground prong from the plug. You must use the three prong plug furnished with the air conditioner.
All Friedrich room air conditioners are shipped from the factory with a Leakage Current Detection Interrupter (LCDI) equipped power cord. The LCDI device meets the UL and NEC requirements for cord connected air conditioners effective August 2004.
To test your power supply cord:
RESET
WHEN GREEN LIGHT IS ON IT IS WORKING PROPERLY
Once plugged in the unit will operate normally without the need to reset the LCDI device.
If the device fails to trip when tested or if the power supply cord is damaged it must be replaced with a new supply cord from the manufac- turer. We recommend you contact our Technical Assistance Line at (800) 541-6645 ext. 845. To expedite service, please have your model and serial number available.
Insulation Good insulation will be a big help in maintaining desirable comfort levels. Doors should have weather stripping. Be sure to caulk around doors and windows.
Make sure that your air conditioner is always in top performing condition by cleaning the filter regularly. In struc tions for removing and cleaning the filter can be found on page 7.
Proper installation of seal gasket
Make sure the airflow to and from the unit is clear. Your air conditioner puts the conditioned air out at the top of the unit, and takes in unconditioned air at the bottom. Airflow is critical to good operation. It is just as important on the outside of the build ing that the airflow around the unit exterior is not blocked.
Make sure the seal gasket has been installed properly to minimize noise and improve effi ciency. If the seal gasket has not been installed, please refer to Step 14 (page 13) of the installation instructions.
Also, if you switch from Cool mode to Fan Only, and switch back to COOL mode, there is a three minute delay before the compressor comes back on.
Unit placement If your air conditioner can be placed in a window or wall that is shaded by a tree or an oth er building, the unit will operate even more efficiently. Using drapes or blinds on the sunny side of the dwelling will also add to your unit’s efficiency.
920-198-00

How to operate your Friedrich room air con di tion er (QuietMaster Programmable)
1 If your air conditioner is installed and plugged into a proper re-

cep ta cle, it is ready to go. Touch Power button once. The unit will automatically be in Cool mode with the temperature set at 75°F (24°C) and the fan speed at F1, the sleep setting. There is a 3- minute delay before the compressor will turn on. (See "Automatic Component Protection" on this page). 2 Should the Check Filter light turn on when you fi rst turn on the unit,
touch Check Filter to turn off the light. Check Filter light will come on af ter 250 hours of use. (See page 7 for fi lter clean ing in struc tions.) Touch Check Filter to reset. To set mode of operation
3 When you fi rst turn on the unit, it will be in the Cool mode (light on),
with constant fan. 4 Touch MoneySaver® (light on) to activate the MoneySaver® feature.
This cycles the fan with the compressor so that the fan does not run all the time. This saves energy and improves de hu mid i fi ca tion. (MoneySaver® will also run the fan to sample the return air tempera- ture if the off cycle is too long). Or you may prefer constant fan for more air movement. To return to constant fan, touch Cool. 5 Touch Fan Only (light on) if you want only the fan to run. You may want
to use this feature in conjunction with the Fresh Air / Exhaust lever to bring outside air into a room, or to exhaust stale air. (See page 7, "Fresh Air and Exhaust Control" for more information.)
6 COOLER – Touch and hold until the display shows the desired
room temperature. 7 WARMER – Touch and hold until the display shows the desired room temperature. 8 FAHRENHEIT / CELSIUS – Touch ºF / ºC to show the temperature in Celsius, touch again to show Fahrenheit.
You can set the A/C Start and A/C Stop timer a min i mum of one hour apart and a maximum of 23 hours apart.
9 Touch 1-4 Speed to see current setting. Touch again to change
13 TIMER STOP - Press the A/C Stop button and continue pressing until the hour you want the unit to shut off appears in the display (A.M. or P.M.). The stop time for cooling will then be set.
speed. F1 is the lowest set ting (SLEEP SETTING), F2 is low speed (LOW), F3 is medium speed (MED), F4 is high speed (HIGH).
14 START TIME - Press A/C Start to view the current start time for cooling. Continue pressing until the hour you want the unit to start appears in the display (A.M. or P.M.). The start time for cooling will then be set.
10 Touch Smart Fan (light on). Smart Fan will adjust the fan speed au to mat i cal ly to maintain the desired comfort level. For example, if the outside doors in your home are open for an extended pe ri od of time, or more people enter a room, Smart Fan may adjust to a higher fan speed to compensate for the increased heat load. This keeps you from having to adjust the fan speed on your own. Smart Fan cannot be activated in the Fan Only mode.
15 Press the Timer On/ Off button once to activate (light on) the timer function. Touch Timer On/ Off again (light off) to cancel the timer function if you so de sire. Once the on and off times have been se- lected, they will remain in memory, and cycle daily until changed.
11 Touch 1-4 Speed, and select your desired fan speed.
Automatic component protection Your unit is equipped with Automatic Com po nent Protection.
12 Press Set Hour once to see the current clock setting. Continue pressing the button until the hour closest to the actual time appears in the display.
To protect the compressor of the unit, there is a three minute time delay if you turn the unit off or if power is interrupted. The fan will not be affected.
MAKE SURE YOU SET A.M. AND P.M. PROPERLY. A light will appear in the upper left corner of the display when the hour is P.M.
920-198-00

To set the timer
1 POWER - Press the Power button once. The unit will automatically
turn on in the mode and fan speed it was last left on.
9 TIMER START - Press Start to view the current start time for cool-
2 COOL - Press the Cool button to automatically switch the operating
ing. Continue pressing the Start button until you arrive at the start time you desire. The start time for cooling will then be set.
mode to COOL.
3 FAN ONLY - Press the Fan Only button if you want to run the fan only.
10 TIMER STOP - Press the Stop button. Continue pressing the Stop button until you arrive at the stop time you desire. The stop time for cooling will then be set.
You may want to use this feature in conjunction with the Fresh Air/ Exhaust if you want to bring outside air into the room, or exhaust stale air. (The FRESH AIR/ EXHAUST feature is located on the front of the air conditioner near the top. See Figure 9 on page 7.)
11 TIMER ON/OFF - Press the On/off button once to activate (light on) or deactivate (light off) the timer. Once the Start and Stop times have been selected, they will remain in memory, and cycle daily until changed.
4 MoneySaver® - Press the MoneySaver® button to activate the
MoneySaver® feature. This cycles the fan with the compressor so that the fan does not run all the time.
5 COOLER - Press the Cooler button to raise the temperature setting.
6 WARMER - Press the Warmer button to lower the temperature setting.
7 FAN SPEED - Press the Fan Speed button to see the current set-
ting. Press again to change the fan speed. F1 is the lowest setting (SLEEP SETTING), F2 is low speed (LOW), F3 is medium (MED), and F4 is high (HIGH).
8 SET HOUR CLOCK - Press Set Hour once to see the current clock set-
Only Speed Saver®
ting. Continue pressing the button until you arrive at the current time.
Set Hr. Stop Start
MAKE SURE YOU SET THE A.M. AND P.M. PROPERLY. (NOTE: MINUTES ARE NOT SHOWN ON THE DISPLAY.) A light will appear in the upper left corner of the display when the hour is P.M.
* A Friedrich RC1 wireless remote control can be used to operate all QuietMaster® Programmable models.

How to operate your Friedrich room air con di tion er (QuietMaster 'K' & Heavy Duty models / Twintemp models)
If your air conditioner is installed and plugged into a properly grounded re cep ta cle, it is ready to op er ate.

Mode control (QuietMaster ‘K’ and Heavy Duty) The upper dial (Figure 5) allows you to select cooling at four different
speeds, as well as Fan Only (Models SL28 and SL36 only have three cooling speeds.).
Off - to turn the unit off. High Cool - for quick cooling. Medium Cool - to maintain a de sired temperature. Low Cool - when cooling demand is low. Sleep Setting - for nighttime use, or when cooling demand is low. Fan Only - to circulate air in the room without the compressor coming on.
The Fan Only setting can also be used with the Exhaust air set ting to remove
stale air or smoke from the room; or it can be used with the Fresh Air setting to bring outside air into the room. This is especially useful in the spring and fall when cooling may not be nec es sary. The Fresh Air and Exhaust controls are in the upper air discharge area. The center po si tion of this control is the normal, or closed position, which recirculates air for maximum performance in the cool ing mode (See Figure 9).
Money Saver® Yes No

Mode control (Twintemp) This dial allows you to select cooling or heat ing at three different speeds,
as well as Fan Only (Figure 6).
Off - to turn the unit off. High Cool or High Heat - for quick re sponse. Medium Cool or Medium Heat - to main tain a de sired temperature. Low Cool or Low Heat - for nighttime use, or when demand is low. Fan Only - to circulate air in the room without the compressor coming on.
Allow 3 min. between restarts

The Fan Only set ting can also be used with the Exhaust air set ting to
re move stale air or smoke from the room, or it can be used with the Fresh Air setting to bring outside air into the room, es pe cial ly in the spring and
fall when cool ing isn’t nec es sary.
The Fresh Air and Exhaust con trols are in the up per air discharge area
(see Figure 9, page 7). The cen ter position of this control is the normal, or closed po si tion, which re cir cu lates air for max i mum per for mance in the cool ing mode.
Temperature control The bottom dial on the control panel is the thermostat. Turn it clock wise
for cooler temperature and counterclockwise for warmer.
Money Saver® switch This rocker switch can be depressed to either Yes or No. In the Yes position
you will get the most eco nom i cal operation. Both the fan and com pres sor will cy cle on and off to geth er, main tain ing the se lect ed tem per a ture at a more con stant lev el and re duc ing the hu mid i ty more ef fi cient ly in the cooling mode. This control will only op er ate when the unit is in cooling or heating mode. In the No position, the fan will run con stant ly as long as the unit is in the cooling or heat ing mode.
Allow 3 min. between restarts

To remove, wash and replace filter and return air grille Open the return air (RA) grille by grasping it at the top outside edges and pulling towards you (See Figure 7). The RA grille will stay open until it is detached or closed (it is easier to completely detach the grille before closing it). To remove the RA grille, grasp it at the bottom and pull towards you.

The fi lter is held in place by two spring clips (See Figure 7). Push down on the clips, grasp the fi lter and pull towards you to remove it for cleaning. Clean with warm water and a mild detergent, rinse, dry completely and replace. Use caution when removing the fi lter. The coil surface can be sharp.
If the RA grille has been removed, pick up the grille by supporting it from both sides near the bottom (See Figure 8, Note 1). Lift return air grille and insert the grille's tabs into the bottom slots of the discharge air plenum (See Figure 8, Note 2). Snap the grille into place by pushing the grille up and onto the unit's latches at the bottom (See Figure 8, Notes 3 and 4).
Fresh air and exhaust control Your air con di tion er has the ability to bring fresh air into the room or ex haust stale air out of the room. The con trol le ver is found on the upper part of the unit (See Fig ure 9).
TO BRING IN FRESH AIR - Move the lever to the Fresh Air position which allows outside air to enter the room. This is useful in fall and spring as a means of bringing in fresh outside air when using Fan Only. It can also be used in the summer with the com pres sor in the Cool ing Mode if you wish. Normally, for most effi cient operation, cooling is ac com plished with this control in the middle or closed position.

TO EXHAUST INDOOR AIR - Move the lever to the Exhaust position. This will allow stale air to be expelled to the outside of the dwelling. This is es pe - cial ly handy in the spring or fall when indoor air tends to get stale, or after a social gathering involving smokers, or to re move odors after cooking.

920-198-00

Refer to the electrical data plate located on the air conditioner chassis to determine the cor rect fuse or circuit breaker amperage for your model (See Figure E on Page 16 for electrical receptacle location).
Your air conditioner must be connected to a power supply with the same A.C. voltage and hertz as marked on the data plate located on the chassis. Only alternating current (A.C.), can be used. Direct Current (D.C.) cannot be used. Refer to page 3 for the correct type of receptacle for your model.
The power cord has a plug with a grounding prong of approved type and
a matching receptacle is required.
CIRCUIT PROTECTION - USE ON SINGLE OUTLET CIRCUIT ONLY. An over load ed circuit will in vari ably cause mal func tion or fail ure of an air con di tion er, there fore, it is nec es sary that the electrical pro tec tion is ad e - quate. Due to mo men tary high cur rent de mand when your air con di tion er is start ed, use a "TIME DELAY" fuse or a HACR type circuit breaker. Consult your dealer or power company if in doubt.
The following instructions are for standard chassis model groups distin-
guished by the fi rst two letters of the model designations and cabinet sizes listed below.
920-198-00

Thru-the-wall Installation Hardware
ITEM #3
ITEM #7
ITEM #10 ITEM #8



ITEM #11

ITEM #14
ITEM #12
ITEM #6
ITEM #1
ITEM #5
NOT TO SCALE
920-198-00

STEP 1 Remove decorative plastic return air grille to a safe area away from unit. The return air grille can be removed by pulling at the sides on either the top or bottom.
STEP 5 Anchor the side angles (Item #6) by engaging the tabs at each end of the sill plate (see Figure B) with the bottom loops of the side angle. Engage the tabs at each end of the top angle (Item #5) with the top loops of the side angle (see Figure B). Install two (2) screws (Item #7) to secure the top angle tabs and the side angle to the cabinet (see Figure B).
STEP 2 Also remove the installation hardware to a safe area away from the unit.
STEP 3 Remove the chassis retainer by re mov ing the far right screw in the basepan (see Figure A); save this screw to reattach the chassis retainer after installation (Step 15). Also, remove and discard the two retainer screws and black plastic washers located at the rear of the unit.
STEP 6 Check the window sill and frame to be sure they are in good condition and fi rmly anchored to the wall. Repair if necessary.
STEP 7 CABINET MOUNTING – Raise the lower sash window ¼" more than the height of the cabinet. Carefully slide the cabinet through the open window until the sill plate channel rests behind the window sill and the top support rests against the window (see Figure C.) Center side to side and drill three (3) 5⁄ 32" dia. pilot holes into the window sill using the holes in the cabinet sill plate as a guide. Install three (3) #12A x 2" long screws (Item #4, Figure C).
STEP 4 While an assistant holds the cabinet sta tion ary, use the hand pull at the front of the base pan, together with the pull strap (see Figure A) to pull the chassis out of the cabinet. REMOVE THE LARGE WHITE FOAM BLOCKS USED TO RESTRAIN THE COM PRES SOR DURING SHIPMENT. Inspect basepan for dislodged white blocks, and remove. Do not remove any other foam parts.
FAR RIGHT SCREW
CHASSIS RETAINER WIRE
PULL STRAP

8A x ⅜" LONG SCREW (ITEM #7) 2 REQUIRED
SIDE ANGLE (ITEM #6) 2 REQUIRED
DETAIL B-1
TAB
LOOP
SILL PLATE TAB
DETAIL B-2
920-198-00 · Figure A · Figure B

STEP 8 OUTSIDE SUPPORT MOUNTING – Assemble the support brackets (Item #1) to the bottom rails of the cab i net with four (4) 10-24 1" long screws (Item #2) and four (4) 10-24 fl at nuts (Item #3). Adjust the support brackets to bring the bottom pads in contact with the wall surface. (A 1" x 4" or 2" x 4" SPACER SHOULD BE USED BETWEEN THE WALL AND THE SUPPORT BRACKETS WHEN IN STALLED ON ALU MI NUM OR VINYL SIDING). Drill 5⁄32" dia. pilot holes and secure the brack ets to the wall with two (2) #12A x 2" long screws (Item #4). Adjust the support brackets to provide an ap prox i mate 3/8" down slope toward the out side for drainage. (See Figure D). Tighten all screws.

CENTER CABINET IN WINDOW SIDE
PULL WINDOW SASH DOWN BEHIND TOP SUPPORT ANGLE
TO SIDE.
AND INSTALL
2" LONG SCREWS (ITEM #4)
SIDE SUPPORT ANGLE
WINDOW
LOCATE SILL PLATE GUIDE CHAN NEL JUST BACK OF WIN DOW SILL
The following illustrations show a standard frame con struc tion installation as well as some suggested ways of adapt ing the support bracket to thick walls and large stone ledges.

SUPPORT BRACKET
SUPPORT BRACK ET (ITEM #1)
10 – 24 FLAT WELD NUT (ITEM #3)
#12A x 2" SCREW
1" x 4" OR 2" x 4" SPACER SHOULD BE USED BE TWEEN WALL AND BRACKET WHEN IN STALLED ON ALUMINUM, ASBESTOS OR VINYL SIDING

MEASURE DISTANCE "B" TO INSIDE OF THE CHANNEL ON EACH SIDE
CUT HERE AND DISCARD CENTER WASTE MATERIAL.
SUBTRACT ⅛" FROM DIMENSION "B" AND MEA SURE FROM THE EDGE OF THE WING- BOARD (ITEM # 8), MARK, SCORE AND CUT WITH APPROPPRIATE CUTTING TOOL NOTE: It is not necessary to cut the wingboard for vertical height; only horizontal WIDTH Dimension “B”.

Figure 1A TYPICAL MOUNTING SCHEME
Figure 2A MODIFIED MOUNTING SCHEME


SUPPLY AIR
CONDENSER AIR OUTLET
RETURN AIR
CUT HERE
DIMENSION "A"
CONDENSER AIR INLETS
#12A x 2" SHEET METAL SCREW
1" x 4" OR 2" x 4" SPACER BE TWEEN WALL AND BRACKET SHOULD BE USED ON ALUMINUM, ASBESTOS OR VINYL SIDING.
CUT TO FIT DIMENSION "A" AND BEND DOWN TO FORM A VER TI CAL LEG.
Figure 3A TYPICAL MOUNTING SCHEME Figure 4A REVERSE SUPPORT BRACKET SCHEME


STONE LEDGE
⅜" SLOPE
DOWN
STRAIGHTEN TAB TO LAY FLAT ALONG THE BOTTOM RAIL OF THE SHELL
#12 x 2" SHEET METAL SCREW
SECURE THE LONGEST SIDE OF THE BRACKET TO THE SHELL
2" x 4" SPACER
STEP 9 CUT WINGBOARD PANELS – Measure and cut the wingboard
panels from the Masonite sup plied (Item #8) to fi t the spaces be- tween the side window channels and the sides of the cab i net. (See Figure E).

GOING TO STEP 10.
CUT EDGE
STEP 10 ASSEMBLE THE CLIPS TO THE WINGBOARD PANELS-
Assemble the "J" type speed nuts (Item 9) and spring steel clips (Item 10) to the edges of the cut wingboard panels (See Figure F).
SLIDE CLIP OVER CUT EDGE OF WINGBOARD PANEL CENTER THE HOLE IN THE SPEED NUT OVER THE SLOT IN THE WINGBOARD PANEL

STEP 11 INSTALL THE SIDE WINGBOARD PANELS – Be sure the
STEP 13 When possible, caulk the outside of the installation with
cabinet has been secured to the win dow sill and that the out- side support brackets have been installed as shown in Figure D. Raise the window sash and install the right and left side wingboard panels. (See Figure G).
industrial type caulking to prevent weath er leaks.
STEP 14 INSTALL CHASSIS – After installing the shell, slide the chassis
into the shell stopping approximately 3" from full insertion. Stuff the chassis seal gasket one inch deep between the chassis and the shell (see Figure I). Begin at either bottom corner and go up the side, across the top, and down the opposite side. Then push the chassis all the way into the shell for the remaining distance so that the plastic front meets the front edge of the shell.
STEP 12 INSTALL THE WINDOW SEALING GASKETS – Measure
and cut the vinyl window seal gasket (grey color, Item # 12) to fi t the width of the window, and install as shown in Figure H. Pull the window sash down behind the gasket. Measure and cut the dark foam window seal gasket (Item #13) and install it between the upper glass panel and the top part of the lower sash. (See Figure H).
If chassis seal gasket is not installed, the operation of the unit
will be negatively affected. Operational noise and outside noise will also be amplifi ed.
CUSTOMER MUST PRO VIDE A MEANS OF PRE VENT ING THE WINDOW FROM OPENING.
STEP 15 Reattach the chassis retainer wire with the same screw as in
Step 3 (See Figure A).

GASKET OVER TOP ANGLE TO WINGBOARD (ITEM #12)
INSERT FOAM WINDOW SEAL GASKET (ITEM # 13)

SECURE THE SIDE WINGBOARD PANELS TO THE SIDE ANGLES WITH FOUR (4) #8 x ½" LONG SCREWS (ITEM #11), TWO ON EACH SIDE.
PLACE WINGBOARD PANEL IN WINDOW JAM TO COMPRESS THE SPRINGS INSIDE THE RUNNERS, AND SWING THE PANEL INTO PLACE INDICATED BY THE DOTTED LINE.
WINDOW JAM
VINYL WINDOW
TOP WINGBOARD ANGLE
GASKET
SECTION A - A
SECTION B - B
920-198-00 · Figure G · Figure H

STEP 17 Be sure the fi lter is in place before installing the return air grille
it exits the left side of the unit. At the consumer’s discretion, the supply cord can be made to exit the right side of the unit. To do this, remove the black rubber coated cord clamp from
(See Figure J), and that the electrical cord is properly routed so not to interfere with the installation. (See Step 16.)
under the far left screw (See Figure I). Replace this screw back into the far left screw hole. Route the supply cord over the top of the return air grille latches and reattach the clamp to the adjacent screw hole (Figures I & J). Detach the right side cord clamp, route the supply cord through it and reattach. The supply cord should be pulled taut so as not to rest on the
STEP 18 Pick up the grille by sup port ing it from both sides near the bottom
(See Figure K, Note 1.) Lift return air grille and insert the grille's tabs into the bottom slots of the discharge plenum (See Figure K, Note 2). Snap the grille into place by pushing the grille up and onto the unit's latches at the bottom (See Figure K, Notes 3 and 4).
STEP 19 Refer to the Operating Instructions beginning on page 3.
return air grille latches.


WHEN INSTALLING CHASSIS SEAL GASKET, BEGIN AT EITHER BOTTOM CORNER AND GO UP THE SIDE, ACROSS THE TOP, AND DOWN THE OPPOSITE SIDE.

920-198-00

The following instructions apply to wood, masonry, brick, concrete or cinder block wall con struc tion
STEP 1 Follow steps 1, 2, 3 and 4 of the "STANDARD SASH WINDOW INSTALLATION" instructions beginning on page 10.
STEP 3 WALL PREPARATION – The maximum wall thickness permis- sible without special construction is de ter mined by the model size to be installed. THE OUTSIDE CABINET CONDENSER-AIR- INTAKE-LOU VERS MUST NOT BE BLOCKED BY EXTENDING INSIDE THE WALL AREA. Observe the maximum wall thickness shown in the chart and di a gram in Figure B.
STEP 2 CABINET PREPARATION – Remove the sill plate from the cabinet by removing the two nuts and screws re tain ing the sill plate. Note that the chassis retainer is secured by a right side nut and screw (See Detail 1, Figure A.) Bend the tabs of the sill plate down into its channel at both ends of the plate or cut them off (See Detail 2, Figure A.) Turn the sill plate end to end, 180° and reinstall. Reverse the ori en ta tion of nuts and screws so that the head of screw is on bottom of cabinet facing up and nut is on top facing down (See Detail 3, Figure A.) Insure that the chassis retainer is reinstalled as shown in the detail.
SPECIAL INSTRUCTIONS FOR EXTRA THICK WALLS – For installation in walls exceeding the max i mum thickness shown in the chart, the following suggested construction may apply.

NUT (2 REQUIRED)
SILL PLATE
DETAIL 1
NOTE: HOLES MOVED TO BACK SIDE
TURN SILL PLATE END TO END
NUT (2 REQUIRED) RETAINER, CHASSIS THIS SIDE ONLY
DETAIL 3
SCREW (2 REQUIRED)
SCREW AND NUT ORIENTATION NOW
REVERSED
DETAIL 2
BEND TABS DOWN
Figure B EXTRA THICK WALL CON STRUC TION

MAXIMUM WALL THICKNESS
CONDENSER AIR INTAKE LOUVERS
2" MINIMUM BOTH SIDES
TOP VIEW SHOW ING BEVELED SIDES FOR AIR INTAKE. WALL BELOW UNIT MUST BE BEVELED ALSO.
MODEL A
SMALL CHASSIS 7 ⅜"
CONDENSER AIR OUTLET / REJECTED
LARGE CHASSIS 15 ⅛"
HEATED AIR
920-198-00 · Figure A

STEP 4 CHECKING WIRING AND PLUMBING: Check all wiring and plumbing inside and outside of the wall to be sure none will be broken where the hole is to be cut.
Figure D BRICK VENEER CONSTRUCTION
STEP 5 HOLE CONSTRUCTION: Depending upon size of unit to be installed, lay out the hole dimensions per the chart below. Cut and frame in hole to fi nished dimensions. Use 2" x 4" material for framing and follow the suggested typical installations in Figure C, D, or E.
SHIM VOID SPACES AT TOP AND SIDES WITH WOOD AS REQUIRED


FINISHED DIMENSION
SMALL CHASSIS
MEDIUM CHASSIS
LARGE CHASSIS
A 16 3⁄16" 18 3⁄16" 20 3⁄8"
B 26 3⁄16" 26 3⁄16" 28 1⁄4"
Figure E SOLID MASONRY CONSTRUCTION

Figure C FRAME WALL CONSTRUCTION

CABINET
CAULK ALL SIDES
CABINET
MOR TAR
ELECTRICAL RE CEP TA CLE
POINT "X"
ELECTRICAL RECEPTACLE (SEE FIG. E FOR LO CA TION NOTE)
SHIM THE VOID SPACE AT THE TOP AND SIDES WITH WOOD AS REQUIRED
920-198-00

Figure F TYPICAL INSTALLATION

TRIM MOULDING
⅜" SLOPE DOWN
SCREW #12A x 2"
CABINET
SILL PLATE GUIDE CHANNEL
SUPPORT BRACK ETS (AVAILABLE AS OP TION AL AC CES SO RY)
SCREW #12 x 2" LONG, USE ONE EACH BRACKET. DRILL 5⁄32 DIA. PILOT HOLES.
STEP 6 Slide the cabinet into the hole far enough to allow the guide-
STEP 8 Drill two (2) 5⁄32" dia. pilot holes each cabinet side at the locations
channel of the sill plate to con tact the inside wall surface (See Figure F).
shown (see Figure F) and install four (4) #12A x 2" screws (Item # 4, page 9). Provided that Step 5 (hole construction) provides a sturdy mount with solid vertical studs, no support brackets are required. The installation must support the weight of the unit plus an additional weight of 400 pounds on the rear of the cabinet.
STEP 7 Drill three (3) 5⁄32" dia. pilot holes through holes in sill-plate
into framing and install three (3) #12A x 2" long screws (See Figure F).
If support brackets are available, they can certainly be used for
through-the-wall installations as shown in Figure F.
If the reliability of the wall is in question, a window installation kit which
includes support brackets can be ordered (see Accessories).
STEP 9 If desired, trim around the cabinet on the room side with a suitable
frame moulding furnished by the installer (see Figure F).
STEP 10 Complete the installation by following steps 13 through 18 of SASH
WINDOW INSTALLATION IN STRUC TIONS, pages 13-14.
STEP 11 Refer to the OPERATION SECTION for instructions.
920-198-00

Power failure If you have a power failure, the unit's auto-restart feature will resume operation in the selected mode prior to the power failure.
Noises All air conditioners make some noise. Friedrich QuietMaster® units are designed to operate as quietly as possible. An air conditioner mounted in a wall is quieter than one mounted in a window. It is important to ensure that the chassis seal gasket is properly installed (refer to installation instructions).
If your air conditioner operates, but won’t cool; check to see if the controls are properly set. Check the filter and clean thoroughly if needed. Check to see if the vent door is closed. Check to see if the chassis seal gasket is installed (refer to installation instructions).
Cleaning your air conditioner The decorative front and the cabinet can be cleaned with warm water and
a mild liquid de ter gent. The indoor coil can be vacuumed with a dusting attachment if it appears to be dirty. The outdoor coil can be gently sprayed with a hose if you can get to it. If not, you might call your dealer for a more thorough cleaning when needed. The air fi lter should be inspected weekly and cleaned if needed by vacuuming with a dust attachment or by cleaning in the sink using warm water and a mild dishwashing detergent. Dry the fi lter thoroughly before reinstalling. Use caution– the coil surface can be sharp.
Make sure the power cord is plugged in completely. Check for a bad fuse, tripped breaker or tripped LCDI Device. Refer to page 3 for LCDI reset instructions and to confi rm proper fuse size.
the “Check Filter” button at the same time. The LED (small red light) for the Check Filter will begin blinking. Once this occurs, turn the unit off by pressing the On/Off button once and then unplug the unit. Finally, plug the unit back in and turn it on by pressing the On/Off button once. All settings revert back to the factory default settings.
If your unit is a "Y", or heat pump model, there are some things that you will want to be aware of.
This is a warm weather appliance Your air conditioner is designed to cool in warm weather when the outside
Some functions of a heat pump differ from your unit when it is used for heating:
temperature is above 60°F (16°C) and below 115°F (46°C), so it won't cool a room if it is already cool outside. If you want to cool a room in the spring or fall, touch Fan Only and set the Fresh Air/Exhaust control to Fresh Air. This will bring in a supply of cooler outside air.
Condensation is normal Air conditioners actually pump the heat and humidity from your room to the outside air. Humidity be comes water, and your air conditioner will use most of the water to keep the outside coil cool. If there is excessive humidity, there may be excess water that will drip outside. This is normal op er a tion.
Frosting This usually occurs because of insufficient airflow across the coils, a dirty
filter, cool damp weath er, or all of these. Set unit to Fan Only and the frost will disappear. Setting the thermostat a little warmer will probably prevent the frosting from recurring.
DC Drain Kit - Part No. 01900235 In some installations, excess condensate water caused by extremely humid con di tions, may result in an un de sir able water drip such as on a patio or over an entryway. MODEL DC-2 DRAIN KIT (Part No. 01900-235) can be installed to drain the excess condensate.
Window Installation Kits TwinTemp or Heat/Cool room air conditioners are shipped without window mount ing hard ware because they are seldom mount ed in the window. For those in stanc es when these units are being mounted in a window, there are window installation kits available. Depending upon the chassis size for which an in stal la tion kit is desired, order:
THESE ACCESSORIES CAN BE ORDERED FROM YOUR FRIEDRICH DEAL ER.
920-198-00

Friedrich Air Conditioning Company
P.O. Box 1540 San Antonio, TX 78295
210.357.4400 www.friedrich.com
LIMITED WARRANTY
ANY PART: If any part supplied by FRIEDRICH fails because of a defect in workmanship or material within twelve months from date of original purchase, FRIEDRICH will repair the product at no charge, provided room air conditioner is reasonably accessible for service. Any additional labor cost for removing inaccessible units and/or charges for mileage related to travel by a Service Agency that exceeds 25 miles one way will be the responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within twelve months from the date of the original purchase.
SEALED REFRIGERANT SYSTEM: If the Sealed Refrigeration System (defined for this purpose as the compressor, condenser coil, evaporator coil, reversing valve, check valve, capillary, filter drier, and all interconnecting tubing) supplied by FRIEDRICH in your Room Air Conditioner fails because of a defect in workmanship or material within sixty months from date of purchase, FRIEDRICH will pay a labor allowance and parts necessary to repair the Sealed Refrigeration System; PROVIDED FRIEDRICH will not pay the cost of diagnosis of the problem, removal, freight charges, and transportation of the air conditioner to and from the Service Agency, and the reinstallation charges associated with repair of the Sealed Refrigeration System. All such cost will be the sole responsibility of the owner. This remedy is expressly agreed to be the exclusive remedy within sixty months from the date of the original purchase.
APPLICABILITY AND LIMITATIONS: This warranty is applicable only to units retained within the Fifty States of the U.S.A., District of Columbia, and Canada. This warranty is not applicable to:
1. Air filters or fuses. 2. Products on which the model and serial numbers have been removed. 3. Products which have defects or damage which results from improper installation, wiring, electrical current characteristics, or maintenance; or caused by accident, misuse or abuse, fire, flood, alterations and/or misapplication of the product and/or units installed in a corrosive atmosphere, default or delay in performance caused by war, government restrictions or restraints, strikes, material shortages beyond the control of FRIEDRICH, or acts of God.
OBTAINING WARRANTY PERFORMANCE: Service will be provided by the FRIEDRICH Authorized Dealer or Service Organization in your area. They are listed in the Yellow Pages. If assistance is required in obtaining warranty performance, write to: Room Air Conditioner Service Manager, Friedrich Air Conditioning Co., P.O. Box 1540, San Antonio, TX 78295-1540.
LIMITATIONS: THIS WARRANTY IS GIVEN IN LIEU OF ALL OTHER WARRANTIES. Anything in the warranty notwithstanding, ANY IMPLIED WARRANTIES OF FITNESS FOR PARTICULAR PURPOSE AND/OR MERCHANTABILITY SHALL BE LIMITED TO THE DURATION OF THIS EXPRESS WARRANTY. MANUFACTURER EXPRESSLY DISCLAIMS AND EXCLUDES ANY LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGE FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.
OTHER: This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
PROOF OF PURCHASE: Owner must provide proof of purchase in order to receive any warranty related services.
All service calls for explaining the operation of this product will be the sole responsibility of the consumer.
All warranty service must be provided by an Authorized FRIEDRICH Service Agency, unless authorized by FRIEDRICH prior to repairs being made.