Thermidistat™ Control Installation, Start-Up, and Operating Instructions NOTE: Read the entire instruction manual before starting the installation. This symbol → indicates a change since the last issue. INDEX Page SAFETY CONSIDERATIONS ...........
INSTALLATION Step 1—Thermidistat Control Location Thermidistat Control should be mounted: • Approximately 5 ft (1.5m) from floor. • Close to or in a frequently used room, preferably on an inside partitioning wall. • On a section of wall without pipes or duct work.
3. A2—for 2-speed air conditioner 4. H2—for 2-speed heat pump 5. dF—for 1-speed dual fuel 6. d2—for 2-speed dual fuel 7. HS—for 1-speed heat pump with Intelligent Heat Staging (3-stage auxiliary heat with 40FK, FK4C, or FV4A Series fan coils.
3. Use up and down buttons to move between F and C on large display. 4. Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.
Option 10—Dual Fuel Equipment All dual fuel installations must be equipped with a high pressure switch to turn off compressor under a high indoor coil pressure condition.
will be supplied, resulting in additional outputs being turned on. If room overheats, specified outputs will not turn off, guaranteeing a sufficiently warm leaving air temperature during defrost.
3. Use up and down buttons to move between OF and ON on large display. Factory default is OF. 4. Press SET TIME/TEMP button again to flash upper small display for selection of another option, or press END to exit configuration mode.
TO TEST COOLING AND DEHUMIDIFICATION: Press MODE button until COOL icon turns on. Cooling begins within 10 sec and remains on for 4 minutes. If system is 2-speed, low speed comes on for first 2 minutes, followed by high speed for second 2 minutes. At the end of 4-minute run, cooling stops, and MODE reverts back to OFF.
4. Auto and Fan Humidify The 2 choices of AUTO and FAN can be selected together. This provides both functions simultaneously. 5. Humidify Off The humidify function can be turned off completely. This does not require changing existing set points. To Select Humidification (Between NORMAL, FAN, AUTO, FAN and AUTO, or OFF) (See Table 4.
humidity removal is desired, this should be done, if possible. Fan coils have the capability of removing this off delay, furnaces do not. On FK or FV Fan Coils, set delay tap to 0/0. On standard fan coils, a jumper can be cut to disable off delay. Refer to fan coil Installation Instructions for details.
Vacation Dehumidification Normal Dehumidify, Cool to Dehumidify, and Dehumidify OFF, are all available in vacation mode, and selection of 1 of these can be different from that of occupied. Vacation dehumidification selection and set points are remembered the next time vacation is used.
THERMIDIST A T CONTROL CONFIGURA TION RECORD Date Owner/Operator A) Hardware Configuration Switch A ____ AC/HP Select. (OFF = AC) Switch B ____ 1 or 2-Speed Compressor . (OFF = 1-Speed) Switch C ____ Smar t Recov ery . (OFF = Enable) Switch D ____ Installer T est.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Carrier Access Thermidistat c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Carrier Access Thermidistat - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Carrier Access Thermidistat, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Carrier Access Thermidistat va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Carrier Access Thermidistat, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Carrier Access Thermidistat.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Carrier Access Thermidistat. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Carrier Access Thermidistat ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.