Installation, Operating, and Maintenance Instructions For Use With Positive Pressure Chillers SAFETY CONSIDERA TIONS Positive pressure storage systems are designed to pro- vide safe and reliable service when operated within de- sign specifications.
CONTENTS Page SAFETY CONSIDERA TIONS ...................1 INTRODUCTION ..............................2 INST ALLA TION ............................. 2-10 Complete Pre-Installation Checks .............2 • IDENTIFY UNIT • INSPECT SHIPMENT Mount the Pumpout Unit .
T able 1 — Positive Pressure System Assembly Numbers POSITIVE PRESSURE SYSTEM ASSEMBL Y NUMBER PUMPOUT UNIT ASSEMBL Y NO. REFRIGERANT COMPRESSOR MOTOR (V -Ph-Hz) MAXIMUM RLA LRA STORAGE T ANK 19XB04280205 19EA42-748 R-22 208-3-60 13.2 63.5 28 cu ft 19XB04280206 19EA44-748 R-22 230-3-60 1 1.
CONDENSER W A TER CONNECTIONS (FIELD PIPING) REFRIGERANT INLET V AL VE VENT V AL VE CONTROL BOX (WIRING BY CONTRACTOR) COMPRESSOR VA LV E S VA LV E S 19EA PUMPOUT UNIT 19EA CONTROL BOX (INTERIOR) 19EA PUMPOUT UNITS Fig.
* 3 ⁄ 8 -16 bolts × 1-in. lg; 4 required. Fig. 2 — 19EA Pumpout Unit: T ypical Chiller Mount Fig. 3 — Pumpout Unit Contact Surfaces and Dimensions ELECTRICAL CONNECTION OPTION LIST TRADE SIZE Q.
T able 2 — Physical Data 19EA Pumpout Unit ENGLISH (SI) Pumpout Unit Weight* lb (kg) 210 (95) Pumpout Condenser W ater Flow Rate gpm (L/s) 5 to 7 (.32 to .
T able 3 — 19XB Storage T ank Rated Dry Weight and Refrigerant Capacity English SIZE CODE T ANK OD (in.) DR Y WEIGHT* (lb) MAXIMUM REFRIGERANT CAP ACITY (lb) ASHRAE/ANSI 15 UL 1963 R-22 R-134a R-22 R-134a 0428 24.00 2380 1842 1860 1704 1716 0452 27.
DIMENSIONS ENGLISH (ft-in.) T ANK SIZE A B CDE F G H J K LM NP R S T 0428 10- 5 9-10 4-9 2-4 3 ⁄ 4 1-2 3 ⁄ 8 3-1 3 ⁄ 16 4-1 1 3-8 1 ⁄ 8 3- 8 2-9 7 ⁄ 16 3-2 0-3 1 ⁄ 2 4-8 3 ⁄ 4 1-7 7 ⁄ .
GENERAL PIPING CONNECTION SIZES CONNECTION SIZE (in.) Refrigerant T ransfer Connections 1 ⁄ 2 ODS (female) Condenser W ater Cooling Connectors 1 ⁄ 2 NPT (female) Safety Relief Head Pumpdown Conden.
T able 4 — Relief Devices STORAGE T ANK SIZE RELIEF V AL VE OUTLET SIZE QUANTITY REQUIRED F ACTOR lb air min Kg air min 28 1 in. NPT Female Connector 2 31.4 14.2 52 1 in. NPT Female Connector 2 52.3 23.7 LEGEND Ground Field Wiring Factory Wiring Contactor T erm.
CONTROLS AND COMPONENTS Figure 1 shows the major components of the PPS system. Pumpout Unit — The pumpout unit consists of a spring- mounted direct motor-driven reciprocating compressor , a water- cooled refrigerant condenser , an oil separator , suction and discharge valves to control refrigerant flow , and prewired safety and control devices.
NOTE: During this operation, maintain water circulation through the chiller cooler and condenser vessels to prevent tube freeze-up. DISTILLING THE REFRIGERANT — Refrigerant vapor is transferred from.
e. Open valve 5 fully after the chiller pressure rises above the freezing point of the refrigerant. Let the storage tank and chiller pressure equalize. Open refrigerant charg- ing valve 7 and storage tank charging valve 10 to let liquid refrigerant drain into the chiller .
3. Remove any remaining refrigerant. a. T urn on chiller water pumps. b. T urn on pumpout condenser water . c. Place valves in the following positions: V A L V E 1 a 1 b23 4567 81 0 1 1 CONDITION C C C C C d.
d. Close valve 1a. e. T urn of f pumpout compressor . f. Close valves 1b, 3, and 4. V A L V E 1 a 1 b 23458 1 1 CONDITION C C CCCCC C g. T urn of f pumpout condenser water . h. T urn of f chiller water pumps and lock out chiller compressor . T ransfer All Refrigerant to Chiller Cooler V essel: 1.
PUMPOUT COMPRESSOR OIL CHARGE — Use oil con- forming to Carrier specifications for reciprocating compres- sor use. Oil requirements are listed in T able 6. T able 6 — Pumpout Compressor Oil Requirements REFRIGERANT ISO VISCOSITY CARRIER SPECIFICA TION NO.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Carrier 19XB c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Carrier 19XB - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Carrier 19XB, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Carrier 19XB va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Carrier 19XB, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Carrier 19XB.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Carrier 19XB. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Carrier 19XB ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.