RV-KD SERIES FORCED DRAFT 15# & 150# EFFECTIVE DATE: 8/11/03 STEAM BOILERS (RV450-RV800) REPLACES:
NOTES: 1. ALL DIMENSIONS ARE IN INCHES. THOSE IN PARENTHESES ARE CENTIMETERS. D 11 1/4" TYP 2. LOCATION DIMENSIONS (28.57) A B H ARE ALL ±1/2". V 3. GAS TRAIN, CONTROL AND BURNER CONFIGURATION WILL 18" C VARY DEPENDING ON JOB (45.72) BURNER SPECIFICATIONS & CONDITIONS. SERVICE AREA 55" 4. DIMENSIONS ARE SUBJECT (139.7) 48" TO CHANGE WITHOUT NOTICE. 11 (121.9) CONSULT FACTORY FOR 14" RLOLESNNNESO EDTcOMMER CERTIFIED DIMENSIONS. (35.6) 5. ALL FLANGES ARE 150# UNLESS OTHERWISE NOTED. 32" MINIMUM TUBE (81.3) REMOVAL CLEARANCE PLAN VIEW 19 3 2 4 1 9 G 17 7 6 16 14 5 104 3/4" (266.1) 8 100 1/4" (254.6) 10 79 1/2" 8 (5 2 1 1/ 68 .2" ) 15 (201.9) 7 13 7 1/2" 33 1/2" 7 X (19.1) (85.1) 12 18 REAR VIEW LEFT SIDE VIEW FRONT VIEW
1. L.W.C.O./PUMP CONTROL - 157 2. PROBE TYPE AUX. L.W.C.O. 3. PRESSURE CONTROLS 4. RELIEF VALVE(S) 5. FORCED DRAFT BURNER6. SURFACE BLOWOFF 1" NPT 7. CLNOUT./INSP. OPNG.-1 1/2"NPT 8. NORMAL BOILER WATER LEVEL 9. ELEC. ENCLOSURE10. FLAME OBSERVATION PORT11. WIDTH OVER BASE 12. COMB. CHAMBER DRAIN 1" NPT 13. OIL CONNECTION 14. HEIGHT OVER FLOW NOZZLE 15. HEIGHT OVER JACKET16. FEEDWATER CONN. 2" NPT 17. LIFTING LUGS 18. JACKET ACCESS PANELS 19. PRESSURE GAUGE
BOILER MODELRV450 RV500RV550RV600 RV700RV800
A-LENGTH OVER JACKET120 1/2" 13 (306.1) (30 1/4" 30.8)143 1/4" (363.9)152 3/4" (388.0)175 1/4" (445.1)197 3/4" (502.3)
B-FLUE LOCATION18 3/4" 18 (47.6) (3/4" 47.6)18 3/4" (47.6)18 3/4" (47.6)20 3/4" (52.7)20 3/4" (52.7)
C-FLUE DIAMETER16" (40.6)16" (40.6)16" (40.6)16" (40.6)20" (50.8)20" (50.8)
D-LENGTH OVER BASE164 7/16" 17 (417.6) (44 1/8" 42.2)187" (474.9)196 5/8" (499.4)225 7/8" (573.7)248 3/8" (630.8)
G-SUPPLY NOZZLE SIZE15 PSI8" FLG 8" (20.3) (FLG 20.3)10" FLG (25.4)10" FLG (25.4)10" FLG (25.4)10" FLG (25.4)
150 PSI6" FLG 6" (15.2) (FLG 15.2)6" FLG (15.2)6" FLG (15.2)6" FLG (15.2)6" FLG (15.2)
H-BURNER EXTENSIONCONSULT FACTORY FOR BURNER EXTENSION APPLICATIONS
V-SUPPLY NOZZLE LOC.59 13/16" 64 (151.9) (3/8" 164.1)71 1/16" (180.4)75 7/8" (192.7)87 1/8" (221.2)98 3/8" (249.8)
X-BLOWDOWN CONNECTION15 PSI1 1/2" 1 (3.8) (1/2" 3.8)2" (5.1)2" (5.1)2" (5.1)2" (5.1)
150 PSI1" (2.54) (1" 2.54)1" (2.54)1" (2.54)1" (2.54)1" (2.54)
783 NORTH CHILI AVE BRYAN BOILERS PERU, INDIANA 46970O RD ER N O .:
ORDER REV. NO.:
FORM NO.: 2169
Fig. 1
Page 2 · cliquer pour agrandir
Page 2
BRYAN BOILERS RV SERIES FORCED DRAFT KNOCKDOWN STEAM BOILERS
Form # >> 2169 Date >> 10/1/2003
Fig. 2 · Form # >> 2169 Date >> 10/1/2003
BOILER MODELRV450RV500RV550RV600RV700RV800
INPUTMBH4,5005,0005,5006,0007,0008,000
(KW)1,318.51,465.01,611.51,758.02,051.02,344.0
OUTPUT*MBH3,6004,0004,4004,8005,6006,400
(KW)1,054.81,172.01,289.21,406.41,640.81,875.2
BOILER HORSEPOWERHP108120131143167191
(KW)1,0581,1761,2841,4011,6371,872
TUBE DIAMETERINCHES1.501.501.501.501.501.50
(CM)3.813.813.813.813.813.81
NUMBER OF TUBES6167758195109
PRESSURE VESSEL GAL 198 216 237 255 294 333 VOLUME (L) 749.4 817.6 897.0 965.2 1,112.8 1,260.4
GAL198216237255294333
(L)749.4817.6897.0965.21,112.81,260.4
HEATING SURFACESQ FT544597688722847972
(SQ M)50.655.563.967.178.790.3
STEAM OUTPUT*LBS/HR3,7114,1244,5364,9485,7736,598
(KG/HR)1,683.51,870.52,057.62,244.62,618.72,992.8
OPERATING WEIGHTLBS10,26111,61112,31213,62215,51217,392
(KG)4,654.55,266.95,584.56,178.87,036.27,889.1
SHIPPING WEIGHTLBS8,6109,81010,33511,49513,06014,615
(KG)3,905.54,449.84,688.05,214.15,924.06,629.4
RELIEF VALVE TYPICAL - 15 PSIG (103.4 KPA)
QUANTITY(2) 12-206(2) 12-206(2) 12-206(2) 14-206(2) 14-206(3) 14-206
SIZEINCHES2½ x 2½2½ x 2½2½ x 2½2½ x 2½2½ x 2½2½ x 2½
(CM)6.35 x 6.356.35 x 6.356.35 x 6.356.35 x 6.356.35 x 6.356.35 x 6.35
CAPACITY-TOTALMBH7,0587,0587,0589,3529,35214,028
(KW)2,068.02,068.02,068.02,740.12,740.14,110.2
RELIEF VALVE TYPICAL - 150 PSIG (1,034.2 KPA)
QUANTITY(1) 6021ED (1) 6021FE(2) 6021FE(2) 6021FE(1) 6021FE (1) 6021GF(1) 6021FE (1) 6021GF(2) 6021GF
SIZEINCHES3/4 x 1 1 x 1¼1 x 1¼1 x 1¼1 x 1¼ 1¼ x 1½1 x 1¼ 1¼ x 1½1¼ x 1½
(CM)1.90 x 2.54 2.54 x 3.172.54 x 3.172.54 x 3.172.54 x 3.17 3.17 x 3.812.54 x 3.17 3.17 x 3.813.17 x 3.81
CAPACITY-TOTALMBH4,2345,1665,1666,8176,8178,468
(KW)1,240.61,513.61,513.61,997.41,997.42,481.1
* Output based on nominal 80% of input. Actual combustion efficiencies will vary and are fuel dependant.
Poser une question sur : Bryan Boilers RV450
Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.
0 questions
Aucune question pour l'instant sur le Bryan Boilers RV450
Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.
Document d'origine
Bryan Boilers RV450 manuel PDF
2pages·397 KB·Chauffe-eau·PDF
Cliquez sur une page ci-dessus pour l'ouvrir ici
Page 1 / …
100%
Chargement des pages…
défiler ou +/− pour zoomer · glisser pour déplacer · Échap pour fermer
Related manuals
More from this brand and category, plus related models worth a look.