POMPE À CHALEUR POUR PISCINE Manuel d’installation et d’utilisation
FR
NL
ZWEMBAD WARMTEPOMP Gebruiker en service manual
ES
BOMBA DE CALOR PARA PISCINA Manual del usuario y de servicio
DE
SCHWIMMBAD-WÄRMEPUMPE Benutzerund Wartungshandbuch
IT
PISCINA POMPA DI CALORE Istruzioni per l'uso e di servizio
PRO ELYO INVERBOOST NN




ENGLISH--------------------------------------------------------------------------P07
FRENCH---------------------------------------------------------------------------P55
NEDERLAND---------------------------------------------------------------------P100
SPANISH--------------------------------------------------------------------------P144
GERMANY------------------------------------------------------------------------P189
ITALY ------------------------------------------------------------------------------P232



repealing Regulation (EC) n° 842/2006
and not contained in foams shall ensure that the equipment is checked for leaks.
CO2 equivalent: at least every 12 months.
Picture of the equivalence CO2
Load and Tons amounting CO2 Frequency of test
From 2 at 30 kg load = from 5 at 50 Tons Each year
Concerning the Gaz R 410a, 2.39kg amounting at 5 tons of CO2, commitment to check each year.
certification, which implies appropriate knowledge of the applicable regulations and standards as well as the necessary
competence in emission prevention and recovery of fluorinated greenhouse gases and handling safety the relevant type
and size of equipment.
such equipment specifying the following information:
a) The quantity and type of fluorinated greenhouse gases installed;
b) The quantities of fluorinated greenhouse gases added during installation, maintenance or servicing or due to leakage;
c) Whether the quantities of installed fluorinated greenhouse gases have been recycled or reclaimed, including the name
and address of the recycling or reclamation facility and, where applicable, the certificate number;
d) The quantity of fluorinated greenhouse gases recovered
e) The identity of the undertaking which installed, serviced, maintained and where applicable repaired or decommissioned
the equipment, including, where applicable, the number of its certificate;
f) The dates and results of the checks carried out;
g) If the equipment was decommissioned, the measures taken to recover and dispose of the fluorinated greenhouse gases.
shall keep copies of the records for at least five years.
Leak checks · Training and certification · Record keeping

SWIMMING POOL HEAT PUMP
PRO ELYO INVERBOOST NN

Thank you for using PRO ELYO INVERBOOST NN swimming pool heat pump for your pool heating, it will heat your
pool water and keep the constant temperature when the air ambient temperature is at -20 to 43℃

installation of your heat pump. * The installer must read the manual and attentively follow the instructions in implementation and maintenance. * The installer is responsible for the installation of the product and should follow all the instructions of the manufacturer and the regulations in application. Incorrect installation against the manual implies the exclusion of the entire guarantee. * The manufacturer declines any responsibility for the damage caused with the people, objects and of the errors due to the installation that disobey the manual guideline. Any use that is without conformity at the origin of its manufacturing will be regarded as dangerous.
*Please always empty the water in heat pump during winter time or when the ambient temperature drops below
0℃, or else the Titanium exchanger will be damaged because of being frozen, in such case, your warranty will be lost.
*Please always cut the power supply if you want to open the cabinet to reach inside the heat pump, because there is high voltage electricity inside.
*Please well keep the display controller in a dry area, or well close the insulation cover to protect the display controller from being damaged by humidity.

1.1 With your Heat Pump - Water connection assembly 50 mm (pcs: 2) - User and service manual - Condensed connection - 10 meters’ signal wire - Waterproof box - Winter cover - Anti-vibration base (pcs: 4)








For the transportation, the heat pump is fix on the pallet and cover with a carton box. To preserve from any damage, the heat pump must be transfer on is pallet. All material, Even if the transport is chargeable to supplier, can be damaged during its routing at the customer and it is the responsibility of the addressee to make sure of the correspondence of the delivery The addressee has to written all the reserves at the reception on the delivery note of the carrier if he notices damages of the packaging. DO NOT FORGET TO CONFIRM BY REGISTERED LETTER TO THE CARRIER UNDER 48 H.
Heat pump must be stored and transfer in vertical position in its original packaging. If it is not the case, she cannot be operated at once, a minimum period of 24H is necessary before to switch on the electrical power.

2.3 Transfer to the final position During the unpacking of the product and the transfer from is palette of origin to final place, it is necessary to maintain the heat pump vertical position. Water connection are not there to assure the function of handle, on the contrary support the weight of the heat pump on the water connection must be damage definitively the product. The manufacturer could not be take the responsible in case of damage.

Technical data PRO ELYO INVERBOOST NN pool heat pumps CE Standard, R410A, Heating and Cooling, Auto mode ,inverter compressor, compressor defrosting, ABS Cabinet
PRO ELYO
PRO ELYO
PRO ELYO
PRO ELYO
MODEL
INVERBOOST
INVERBOOST
INVERBOOST
INVERBOOST
INVERBOOST
NN 07
NN 10
NN 14
NN 17
NN 21
CODE 68815 68816 68817 68818 68819
* Performance at Air 26℃, Water 26℃, Humidity 80%
Heating capacity kW 7-3.1 10-2.3 13-3 17-3.8 20-4.6
Power consumption kW 1.01-0.26 1.49-0.14 1.94-0.19 2.54-0.24 2.98-0.29
* Performance at Air 15℃, Water 26℃, Humidity 70%
Heating capacity kW 5.1-2.5 7.1-1.9 9.6-2 11.5-3 14-3
Power consumption kW 1-0.38 1.4-0.25 1.84-0.26 2.2-0.36 2.7-0.36
Compressor type GMCC /TOSHIBA MITSUBISHI
Rated current A 4.4 6.5 8.5 11.0 13.0
Minimum fuse A 7 10 13 16 20
m³ 10-26 12-36 18-66 28-86 58-122
Advised water flux m3/h 2.5 3.0 4.0 5.0 6.0
drop Kpa 12 12 14 15 18
Heat exchanger Twist-titanium tube in PVC
Water connection mm 50
Fan speed RPM 500-850 500-650 550-850 450-650 450-650
Power input of Fan W 5-25 10-100 10-120 10-120 10-120
Noise level(1m) dB(A) 40-50 40-52 40-54 41-56 41-56
Refrigerant (R410a) g 950 1050 1600 2300 2600
CO2 equivalent Tonne 1.99 2.2 3.35 4.81 5.43
Net weight kg 54 68 78 98 108
Gross weight kg 66 73 83 113 123
Net dimension mm 990*380*560 1050*440*709 1113*450*870
Packing dimension mm 1060*430*705 1130*470*850 1140*480*1010
* Above data are subject to modification without notice.

Technical data PRO ELYO INVERBOOST NN pool heat pumps CE Standard, R410A, Heating and Cooling, Auto mode ,inverter compressor, compressor defrosting, ABS Cabinet
* Performance at Air 26℃, Water 26℃, Humidity 80%
Heating capacity kW 26-6.8 26-6.8 35-8 35-8
Power consumption kW 3.88-0.43 3.88-0.43 5.22-0.5 5.22-0.5
* Performance at Air 15℃, Water 26℃, Humidity 70%
Heating capacity kW 19-5.4 19-5.4 24-5.6 24-5.6
Power consumption kW 3.6-0.66 3.6-0.66 4.8-0.68 4.8-0.68
Voltage V 220~240V /50Hz
/1PH 380V/50Hz /3PH 220~240V /50Hz
Rated current A 17.0 6.2 22.9 8.4
Minimum fuse A 26 9 34 13
(with pool cover) m³ 68-135 68-135 78-160 78-160
Advised water flux m3/h 8.0 8.0 10.0 10.0
Water pressure drop Kpa 20 20 25 25
Heat exchanger Twist-titanium tube in PVC
Water connection mm 50
Fan speed RPM 500-850
Power input of Fan W (10-120)*2
Noise level(1m) dB(A) 42-60
Refrigerant (R410a) g 3800 3800 4000 4000
CO2 equivalent Tonne 7.94 7.94 8.36 8.36
* Dimension / Weight
Net weight kg 120 120 130 130
Gross weight kg 138 138 148 148
Net dimension mm 1050*460*1285
Packing dimension mm 1140*500*1435
* Above data are subject to modification without notice.




Anti-vibration base, 4 pcs
Draining jet, 2 pcs
Waterproof box, 1 pc




10M signal wire, 1 pc Modbus signal wire,1 pc
Water connection assembly, 2 sets
The kit By-Pass is the essential accessory for the installation of your heat pump, it is also a tool for the optimization of the heating of the water. The regulation of the valves allows to optimize the flow of water and with the manometer to make sure the optimize running of the compressor, see paragraph 5.6 controls of the pressure.

Winter Cover,1 pc

Anti-vibration bases 1. Take out 4 Anti-vibration bases 2. Put them one by one on the bottom of machine like the picture.
Draining jet 1. Install the draining jet under the bottom panel 2. Connect with a water pipe to drain out the water.




Water Inlet & outlet junction 1. Install the two joints like the picture shows 2. Screw them onto the water Inlet & outlet junction


Cable wiring 1. Open the wiring block box (marked red) on the side of machine 2. Fix the other side on joints inside the electric box.

Water pump wiring (Dry contact) 1. Open the wiring block box (marked red) on the side of machine 2. Fix the other side on joints inside the electric box.


The unit will work properly in any desired location as long as the following three items are present:
The unit may be installed in virtually any outdoor location as long as the specified minimum distances to other objects are maintained (see drawing below). Please consult your installer for installation with an indoor pool. Installation in a windy location does not present any problem at all, unlike the situation with a gas heater (including pilot flame problems).

ATTENTION: Never install the unit in a closed room with a limited air volume in which the air expelled from the unit will be reused, or close to shrubbery that could block the air inlet. Such locations impair the continuous supply of fresh air, resulting in reduced efficiency and possibly preventing sufficient heat output. See the drawing below for minimum dimensions.

NOTE
Note: If automatic dosing equipment for chlorine and acidity (pH) is used, it is essential to protect the heat pump against excessively high chemical concentrations which may corrode the heat exchanger. For this reason, equipment of this sort must always be fitted in the piping on the downstream side of the heat pump, and it is recommended to install a check-valve to prevent reverse flow in the absence of water circulation. Damage to the heat pump caused by failure to observe this instruction is not covered by the warranty.



This arrangement is only an illustrative example.
The factory supplies only the heat pump. All other components, including a bypass if necessary, must be provided by the user or the installer.


After all connections, have been made and checked, carry out the following procedure:
Depending on the initial temperature of the water in the swimming pool and the air temperature, it may take several days to heat the water to the desired temperature. A good swimming pool cover can dramatically reduce the required length of time.
Water Flow Switch: It is equipped with a flow switch for protecting the HP unit running with adequate water flow rate. It will turn on when the pool pump runs and shut it off when the pump shuts off.
Time delay - The heat pump has a built-in 3-minute start-up delay to protect the circuitry and avoid excessive contact wear. The unit will restart automatically after this time delay expires. Even a brief power interruption will trigger this time delay and prevent the unit from restarting immediately. Additional power interruptions during this delay period do not affect the 3-minute duration of the delay.

The air drawn into the heat pump is strongly cooled by the operation of the heat pump for heating the pool water, which may cause condensation on the fins of the evaporator.
The amount of condensation may be as much as several litters per hour at high relative humidity. This is sometimes mistakenly regarded as a water leak.
5.6 Pressure gauge display (R410A) Examine the pressure gauge which indicates the refrigerant gas pressure of the unit, the below table shows the normal value of the gas pressure (R410A) when the machine is in power off or running conditions.
Unit Condition Power Off
Ambient (℃) -5~5 5~15 15~25 25~35
Water temp (℃) /
Pressure gauge (Mpa) 0.68~0.93 0.93~1.25 1.25~1.64 1.64~2.1
Ambient (℃) /
Water temp (℃) 10~15 15~20 20~25 25~30 30~35
Pressure gauge (Mpa) 1.3~1.8 1.5~1.9 1.6~2.3 1.9~2.8 2.1~3.5
Unit Condition Running

6.1 Inverter swimming pool heat pump wiring diagram Ref. PRO ELYO INVERBOOST NN 07/10/14/17/21 Basic Electrical Wiring


Ref. PRO ELYO INVERBOOST NN 07/10/14/17/21 Electrical Wiring with MODBUS module


Ref. PRO ELYO INVERBOOST NN 07/10/14/17/21


6.2 Inverter swimming pool heat pump wiring diagram Ref. PRO ELYO INVERBOOST NN 26/35 Basic Electrical Wiring


Ref. PRO ELYO INVERBOOST NN 26/35 Electrical Wiring with MODBUS module


Ref. PRO ELYO INVERBOOST NN 26/35 Electrical Wiring with WIFI module


6.3 Inverter swimming pool heat pump wiring diagram Ref. PRO ELYO INVERBOOST NN 26T/35T Basic Electrical Wiring


Ref. PRO ELYO INVERBOOST NN 26T/35T Electrical Wiring with MODBUS module


Ref. PRO ELYO INVERBOOST NN 26T/35T Electrical Wiring with WIFI module

* Above electrical wiring diagram only for your reference, please subject machine posted the wiring diagram.

6.4 Electrical connection The power supply for the heat pump must come, preferably, from an exclusive circuit with regulatory protection components (30mA differential protection) and a magneto-thermal switch.
- The electrical installation must be carried out by a specialized professional (electrician) in accordance with the standards and regulations in force in the country of installation.
- The heat pump circuit must be connected to a safety earth circuit at the terminal block.
- The cables must be properly installed to prevent interference.
- The pump is intended for connection to a general power supply with earth connection.
- Section of the cable; This section is indicative and should be checked and adapted according to the needs and conditions of use.
- The tolerance of acceptable voltage variation is +/- 10% during operation. The connections must be dimensioned according to the power of the device and the state of installation.
Models Circuit breaker
2,5 mm² 4 mm² 6 mm² 10 mm²
PRO ELYO INVERBOOST NN 07 7 A 84 m 135 m 200 m 335 m
PRO ELYO INVERBOOST NN 10 10 A 57 m 90 m 130 m 225 m
PRO ELYO INVERBOOST NN 14 13 A 43 m 68 m 100 m 170 m
PRO ELYO INVERBOOST NN 17 16 A 34 m 54 m 80 m 135 m
PRO ELYO INVERBOOST NN 21 20 A 29 m 45 m 66 m 110 m
PRO ELYO INVERBOOST NN 26 26 A 135 m 210 m 315 m 525 m
PRO ELYO INVERBOOST NN 26T 9 A 105 m 160 m 240 m 400 m
PRO ELYO INVERBOOST NN 35 34 A 21 m 34 m 49 m 84 m
PRO ELYO INVERBOOST NN 35T 13 A - 27 m 39 m 68 m
These values are given as a guideline, only the intervention of an authorized technician can determine
the values corresponding to your installation. The electric line must be equipped with a ground connection and with a circuit breaker with difference 30mA in head.

Photo(1) Photo(2) Photo(3) Photo(4) Photo(5)





- The side with plug connects with the control panel (photo1) - The other side of the signal wire. (photo2) - Open the wiring panel and put the side without plug through the electrical box. (photo3,4) - Insert the wiring into the designated position on the Modbus Module or PCB(without Modbus). (photo5)
Photo(6) Photo(7) Photo(8) Photo(9)




- Open the terminal cover (photo6)
- Take the Modbus/Fluidra Connect signal wire from the accessories (photo7) and put the round end of the signal wire into the signal wire from Modbus/Fluidra Connect Module. (photo 8) - Three wire terminal :“A+” ,“B- ”, “GND” (Photo 9)

Dry contact timer connection

Dry contact pump connection

Timer


When the heat pump connects to the power, the LED display shows a code for 3 seconds which indicates the heat pump model. 7.2 The keys and their operations
Press to start the heat pump unit, the LED display shows the desired water temperature for 5 seconds, then shows the inlet water temperature and the operation mode.
Press to stop the heat pump unit and show “OFF”
Press again to turn on/off the machine.
Press for 5 secondes to switch the heating mode and auto mode.
Clock/unclock the display:
Hold and for 5 seconds to lock/Unlock the display. Water temperature setting:
Press or to set the water temperature directly.

Press first, then press to check the User parameter from d0 to d14
Code Condition Scope Remark
d0 IPM mould temperature 0-120℃ Real testing value
d1 Inlet water temp. -9℃~99℃ Real testing value
d2 Outlet water temp. -9℃~99℃ Real testing value
d3 Ambient temp. -30℃~70℃ flash if Real value
d4 Frequency limitation code 0,1,2,4,8,16 Real testing value
d5 Piping temp. -30℃~70℃ flash if Real value
d6 Gas exhaust temperature 0℃~C5℃(125℃) Real testing value
d7 Step of EEV 0~99 N*5
d8 Compressor running frequency 0~99Hz Real testing value
d9 Compressor current 0~30A Real testing value
d10 Current fan speed 0-1200 (rpm) Real testing value
d11 Error code for last time All error code
d12 MOBUS COM 0 - 5 Setting, Modbus Only
d13 MODBUS ID Address 1 - 88 Setting, Modbus Only
d14 Product Code 0000- FFFF Setting, Modbus Only
Remark:
d4:Frequency limitation code,
8:Drive voltage frequency limit; 16:Drive high temperature frequency limit
Press first, then press to check/adjust the User parameter from P1 to P7
Code Name Scope Default Remark
P0 Mandatory defrosting 0-1 0 0: Default normal operation 1: mandatory defrosting. P1 Working mode 0-1 1 1:Heating mode, 0:cooling mode,
P2 Timer on/off 0-1 0 1 Timer on/off is under function,0 Timer on/off is out of function (The setting of P5 and P6 won’t work)
P3 Water pump 0-1 0 1:Always running; 0:Depends on the running of compressor
P4 Current time HH:MM 00:00 0-23:0-59
P5 Timer on HH:MM 00:00 0-23:0-59
P6 Timer off HH:MM 00:00 0-23:0-59
P7 Water temp. calibration -9~9 0 Default setting: 0
P12 MOBUS COM 0 - 5 0 Modbus Only(default value after reset)
P13 MODBUS ID Address 1 - 88 9 Modbus Only(default value after reset)

Code with connect Parameter P Description 68815 0CCF PAC PROELYO INVERBOOST NN 7-3.1 68816 0CD0 PAC PROELYO INVERBOOST NN 10-2.3 68817 0CD1 PAC PROELYO INVERBOOST NN 13-3 68818 0CD2 PAC PROELYO INVERBOOST NN 17-3.8 68819 0CD3 PAC PROELYO INVERBOOST NN 20-4.6 68820 0CD4 PAC PROELYO INVERBOOST NN 26-6.8 68821 0CD5 PAC PROELYO INVERBOOST NN 26-6.8 T 68822 0CD6 PAC PROELYO INVERBOOST NN 35-8 68823 0CD7 PAC PROELYO INVERBOOST NN 35-8 T
Product code parameter P (Modbus Only): Press + for 5 second, the first digital number flashes, press
or to choose the target number from 0-F, then press go to adjust the second number. So does the
third and forth number. Lastly press to save the setting and exit, or it automatically exit after 15 seconds.
After the setting, the product code parameter P couldn’t be reset, even if system reset,Its setting value is always retained.

Press and in 10s, the system will reset and display “0000” on the controller.
Symbol of heating, the light will be on when it is in operation. When defrosting, the light will flash.
Symbol of cooling, the light will be on when it is in operation.
Symbol of automatic stop, the light will be on when it is in operation.
Symbol of automatic start, the light will be on when it is in operation.
Press this button, the light will be flash, the heat pump will operate in ‘Full output’ only.
While you choose the Smart, the heat pump will just operate in ‘Medium output’ and ‘Full output’ When in ‘Medium output’, the light of Smart will flash. When in ‘Full output’, the lamp of Smart is lighting, the lamp of Powerful will be flash.
While you choose the Silent, the heat pump will just operate in ‘Medium output’ and ‘Small output’ When in ‘Small output’, the light of Silent will flash. When in ‘Medium output’, the lamp of Silent is lighting, the lamp of Smart will be flash.

7.2.12 Auto Mode There are 3 models for the unit, Heating only, Auto mode(heating and cooling switch), Cooling only.
You can switch Heating only and Auto mode by pressing for 5 seconds, no matter the unit is on or off.


Set water temperature (Tset)
Current water in temperature (Tset +2℃)
After 3 minutes or above, it will switch to
light together · light on · Current working mode

NO Working status Working mode Water in temperature Heat pump working level 1
≦Tset-1 POWERFUL 2 Tset-1< and < Tset+1 SMART 3 ≧Tset+1 Standby 4 SILENT
≦Tset-1 SMART 5 Tset-1< and < Tset+1 SILENT 6 ≧Tset+1 Standby 7 POWERFUL
Start-up of heat pump
NO Working status Working mode Water in temperature Heat pump working level 1
≦Tset-1 Standby 2 Tset-1< and
≦Tset-1 Standby 5 Tset-1< and Tset-1 POWERFUL 8 ≦Tset-1 Standby 9 Restart cooling from standby status is the same as the Start-up
Start-up of heat pump

Malfunction Error code Reason Solution
Inlet water temperature sensor
2.Re-fix the wiring of the sensors
Outlet water temperature sensor
2.Re-fix the wiring of the sensors
Heating piping sensor failure PP03
2.Re-fix the wiring of the sensors
Gas return sensor failure PP04
2.Re-fix the wiring of the sensors
Ambient temperature sensor failure PP05
2.Re-fix the wiring of the sensors
Exhaust piping sensor failure PP06
2.Re-fix the wiring of the sensors
Ambient temperature or water inlet
Antifreeze protection in Winter PP07
temperature is too low
1.Beyond the scope of using
Low ambient temperature protection PP08
Piping temperature too high protection under cooling mode
T2 water temp. Too low protection under cooling mode PP11
High pressure failure EE01
Fan motor speed is abnormal or fan

Malfunction Error code Reason Solution
system Check the motor
Low pressure failure EE02
gauge to check the pressure value
Water flow failure EE03
water supply is cut off
1.Lack of gas
2.Low water flow
if too low, fill with some gas
3.Pipingsystem has been blocked
4.Exhaust temp. Sensor failure
T6 Exhaust too high
instantaneously 2. Wrong connection for compressor
3.Compressor accumulations of liquid and
oil lead to the current becomes larger

Malfunction Error code Reason Solution
controller and main board EE08
Main control board and Driving
VDC voltage too high protection EE10
supply and restart after 3 minutes
IPM module protection EE11
accumulation lead to the current
VDC voltage too low protection EE12
Input current over high protection.
IPM module thermal circuit is abnormal EE14

Malfunction Error code Reason Solution
is too low or fan motor
damaged, change another one 3. Change another fan blade
too low or fan motor damaged,
PFC module protection EE16
DC fan motor failure EE17
PFC module thermal circuit is abnormal EE18 The driver board is damaged
too low or fan motor damaged,
too low or fan motor damaged,
PFC module high temperature protection EE19
Input power failure EE20 The supply voltage fluctuates too much Check whether the voltage is stable

Malfunction Error code Reason Solution
1.Compressor runs out of step 2. Wrong program
Software control exception EE21
change a new one
the unstable rotate speed
Current detection circuit failure EE22
change a new one
change a new one
Compressor start failure EE23
according to the circuit diagram
Check the compressor or change
Ambient Temperature device failure on Driver board
EE24 Ambient Temperature device failure Change driver board or main board
Compressor phase failure EE25 Compressors U, V, W are connected to one phase or two phases.
Check the actual wiring according to the circuit diagram
check the 4-way valve if it has
Four-way valve reversal failure EE26
T3 or T5 malfunction)
EEPROM data read malfunction EE27
or failed input of EEPROM data
The inter-chip communication failure on the main control board
EE28 Main board failure

Malfunctions Observing Reasons Solution
Check cable and circuit breaker if
no display.
LED wire controller.
Heat pump under standby
Startup heat pump to run.
Displays the actual time.
reaching to setting value, HP
setting.
status.
minutes.
water temperature.
display "Defrosting".
LED wire controller displays
controller, and then check the
cooling when HP runs
actual water temperature and no
status after changing the running
error code displays.
mode, verifying the water inlet
and outlet temperature.
between the motor and fan, if
necessary, it should be replaced.
LED displays actual water
temperature, no error code
pump unit, and eliminate all
displays.
obstacles to make good air
ventilation.
3 Replace or repair the heat pump
unit.
water stains Water stains on heat pump unit.
exchanger carefully if it is any
defect.
pump unit, and eliminate all
Too much ice on
obstacles to make good air
Too much ice on evaporator.
ventilation.
pump unit.




















1 Top cover 1330900291
37 Water connection sets 113900082
2 Ambient temp. sensor TH1 117110020 38 Red rubber ring 133020011
3 Ambient temp. sensor clip 133020010 39 Rubber ring on water connection 133020026
40 Water flow switch 112100021-1
5 Isolation panel 108050073
41 Sealing ring 116000001
6 Reactor 117230003 42 Titanium heat exchanger 102040549
7 Top frame 108110038
43 Water out temp. sensor TH5 117110011
44 Exchanger temperature sensor clip 108010025
9 Fan motor bracket 108110043 45 Water connection sets 113900082
10 Left side panel 1330900261 46 Blue rubber ring 133020011
11 Fan motor 112000031 47 Water in temp. sensor TH6 117110012
12 Fan blade 132000015 48 Drainage plug 150000110
13 DC motor cover 108010024
14 Front panel 1330900251 50 EEV to distribution piping 113080051
15 Front grill 108010014 51 Liquid storage tank to expansion valve 113120002
16 Base tray 108110044 52 4 way valve 121000006
17 Compressor 101000162 53 Exchanger to Filter 113170021
18 Liquid storage tank 105000004 54 Filter 120000066
19 Compressor Heating belt 142000074 55 Filter to liquid storage tank 113130002
20 Compressor damping feet 136020019 56 Exhaust temp. sensor TH3 117110021
21 Right panel 133090028 57 High pressure switch 116000066
22 Terminal Board 108010065 58 Exhaust pipe 113010159
23 Pressure gauge 110800001 59 Low pressure switch 116000072
24 5-seat terminal 115000004
60 Low pressure switch 116000071
25 Clip 136010004 61 Suction valve 120000026
26 Terminal blocks plastic cover 1332500051 62 Gas return piping 113020246
27 wire connection 110000008 63 4-way valve to exchanger 113030081
28 Wiring box 108010018 64 4-way valve to collective piping 113060084
29 Controller 117020150 65 Electric box cover 108050017
30 Waterproof controller box 113712007 66 Wire trunking 136020003
31 Collective piping 103000202
32 Sensor casing pipe 113100009 68 Electric box 108110045
33 Clip 69 magnet ring 117240003
34 Pipe temp. sensor TH2 117110004 70 magnet ring 117240002
35 Distribution piping 103000202
71 Modbus Module 117010095
36 Back panel 1330900271
4 Evaporator 103000202 · 8 Pillar 108110004






1 Top cover 1332600011 37 EEV 119000021
2 Back panel 1332600021 38 EEV to distribution piping 113080056
3 Ambient temp. sensor TH1 117110020 39 Liquid storage tank to EEV 113120019
4 Ambient temp. Sensor clip 133020010
40 4 way valve to exchanger 113030093
5 Evaporator 103000204 41 Exchanger to Filter 113170032
6 Sensor casing pipe 113190001 42 Exhaust pipe 113010171
113190001 43 Exhaust temp. sensor TH3 117110021
8 Pipe temp. sensor TH2 117110004 44 4 way valve 121000009
9 Isolation panel 108560010 45 High pressure switch 116000068
10 Reactor 117230002 46 4-way valve to collective piping 113060096
11 Top frame 108560002 47 Filter 120000066
12 Pillar 108560003 48 Gas return piping 113020259
13 Fan motor bracket 108560011 49 Suction valve 120000026
14 Fan motor 112000031 50 Low pressure switch 116000073
15 Fan blade 132000023 51 Low pressure switch 116000074
16 Left side panel 1332600051 52 Filter to liquid storage tank 113130002
17 Front grill 108170017 53 Water connection sets 113900082
18 Front panel 1332600031 54 Red rubber ring 133020012
19 Base tray 108560009 55 Rubber ring on water connection 133020026
20 Compressor 101000150 56 Water flow switch 112100021-1
21 Compressor Heating belt 142000076 57 Sealing ring 116000001
22 Liquid storage tank 105000004 58 Exchanger temperature sensor clip 108010025
23 Compressor damping feet 101000150 59 Water out temp. sensor TH5 117110011
108010065 60 Water in temp. sensor TH6 117110012
25 5-seat terminal 115000004 61 Drainage plug
26 Right panel 1332600041 62 Titanium heat exchanger 102040555
27 Pressure gauge 110800001 63 Blue rubber ring 133020011
28 Clip 136010004 64 Water connection sets 113900082
29 Terminal blocks plastic cover 1332500051 65 Wire trunking 136020003
30 Wiring box 108010018 66 PCB 117100015-V1.5
31 Waterproof controller box 113712007 67 Electric box cover 108540006
32 Wire connection 110000008 68 magnet ring 117240003
33 Controller 117020150 69 Electric box 108560012
34 Distribution piping 103000204 70 magnet ring 117240002
35 Rubber block 136020005 71 Modbus Module 117010095
36 collective piping 103000204
7 Clip · 24 Terminal Board · 150000110

NO Parts Name 68819 NO Parts Name 68819 1 Top cover 1332600011 37 EEV 119000021
2 back panel 1332600021 38 EEV to distribution piping 113080056 3 Ambient temp. sensor TH1 117110020 39 Liquid storage tank to EEV 113120019 4 Ambient temp. sensor clip 133020010
40 4 way valve to exchanger 113030093 5 Evaporator 103000206
41 Exchanger to Filter 113170032 6 Sensor casing pipe 113190001
42 Exhaust pipe 113010171 7 Clip 113190001
43 Exhaust temp. sensor TH3 117110021 8 Pipe temp. sensor TH2 117110004 44 4 way valve 121000009 9 Isolation panel 108560010 45 High pressure switch 116000068 10 Reactor 117230002 46 4-way valve to collective piping 113060096 11 Top frame 108560002 47 Filter 120000066
12 Pillar 108560003 48 Gas return piping 113020259 13 Fan motor bracket 108560011
49 Suction valve 120000026 14 Fan motor 112000031 50 Low pressure switch 116000073
15 Fan blade 132000023 51 Low pressure switch 116000074 16 Left side panel 1332600051 52 Filter to liquid storage tank 113130002 17 Front grill 108170017 53 Water connection sets 113900082 18 Front panel 1332600031 54 Red rubber ring 133020012
19 Base tray 108560009 55 Rubber ring on water connection 133020026 20 Compressor 101000150 56 Water flow switch 112100021-1 21 Compressor Heating belt 142000076 57 Sealing ring 116000001 22 Liquid storage tank 105000004 58 Exchanger temperature sensor clip 108010025 23 Compressor damping feet 101000150 59 Water out temp. sensor TH5 117110011 24 Terminal Board 108010065
60 Water in temp. sensor TH6 117110012 25 5-seat terminal 115000004 61 Drainage plug 150000110 26 Right panel 1332600041 62 Titanium heat exchanger 102040590 27 Pressure gauge 110800001 63 Blue rubber ring 133020011 28 Clip 136010004 64 Water connection sets 113900082
29 Terminal blocks plastic cover 1332500051 65 Wire trunking 136020003
30 Wiring box 108010018 66 PCB 117100015-V1.5 31 Waterproof controller box 113712007
67 Electric box cover 108540006 32 Wire connection 110000008 68 magnet ring 117240003 33 Controller 117020150 69 Electric box 108560012 34 Distribution piping 103000206
70 magnet ring 117240002 35 Rubber block 136020005
71 Modbus Module 117010095 36 Collective piping 103000206














9.3 Maintenance (1) You should check the water supply system regularly to avoid the air entering the system and occurrence of low water flow, because it would reduce the performance and reliability of HP unit.
(2) Clean your pools and filtration system regularly to avoid the damage of the unit as a result of the dirty of clogged filter.
(3) You should discharge the water from bottom of water pump if HP unit will stop running for a long time (especially during the winter season).
(4) In another way, you should check the unit is water fully before the unit start to run again.
(5) After the unit is conditioned for the winter season, it is recommended to cover the heat pump with special winter heat pump.
(6) When the unit is running, there is all the time a little water discharge under the unit.

Pompe à chaleur pour piscine
PRO ELYO INVERBOOST NN
La signification des codes d'erreur affichés à l'écran et la façon de les effacer.
| Code | Signification | Solution | |
|---|---|---|---|
| PP01 | 1. The sensor in open or short circuit 2. The wiring of sensor is loose | 1. Check or change the sensor 2.Re-fix the wiring of the sensors | p.44 |
| PP02 | 1. The sensor in open or short circuit 2. The wiring of sensor is loose | 1. Check or change the sensor 2.Re-fix the wiring of the sensors | p.44 |
| PP03 | 1. The sensor in open or short circuit 2. The wiring of sensor is loose | 1. Check or change the sensor 2.Re-fix the wiring of the sensors | p.44 |
| PP04 | 1. The sensor in open or short circuit 2. The wiring of sensor is loose | 1. Check or change the sensor 2.Re-fix the wiring of the sensors | p.44 |
| PP05 | 1. The sensor in open or short circuit 2. The wiring of sensor is loose | 1. Check or change the sensor 2.Re-fix the wiring of the sensors | p.44 |
| PP06 | 1. The sensor in open or short circuit 2. The wiring of sensor is loose | 1. Check or change the sensor 2.Re-fix the wiring of the sensors | p.44 |
| PP07 | Ambient temperature or water inlet temperature is too low | Normal protection | p.44 |
| PP08 | 1.Beyond the scope of using environment 2. Sensor abnormality | 1. Stop using, beyond the scope of using 2.Change the sensor | p.44 |
| PP10 | 1. Ambient temperature is too high or the water temperature is too high in cooling mode 2. Refrigeration system is abnormal | 1. Check the scope of using 2. Check refrigeration system | p.44 |
| PP11 | 1. Low water flow 2. T2 temperature sensor abnormal | 1. Check water pump and waterway system 2. Change T2 temperature sensor | p.44 |
| EE01 | 1. Ambient temperature is too high 2. Water temperature is too high 3. Water flow is too low Fan motor speed is abnormal or fan motor has damaged | 1. Check the water flow or water pump 2. Check the fan motor 3. Check and repair the piping system | p.44 |
| EE02 | 1. EEV has blocked or pipe system is jammed 2. Motor speed is abnormal or motor has damaged 3. Gas leakage | 1. Check the EEV and piping system Check the motor 2. Through the high pressure gauge to check the pressure value | p.45 |
| EE03 Or” ON” | 1. Water flow switch is damaged 2. No/ Insufficient water flow. | 1. Change the water flow switch 2. Check the water pump or the waterway system | p.45 |
| EE04 | 1. Low water flow 2. Water flow switch is stuck and the water supply is cut off 3. T2 sensor is abnormal | 1. Check the water way system 2. Check the water pump or water flow switch 3. CheckT2 sensor or change another one | p.45 |
| EE05 | 1.Lack of gas 2.Low water flow 3.Pipingsystem has been blocked 4.Exhaust temp. Sensor failure | 1. Check the high pressure gauge, if too low, fill with some gas 2. Check the waterway system and water pump 3. Check the piping system if there was any block 4. Change a new exhaust temp. sensor | p.45 |
| EE06 | 1. Wire connection is not good, or damaged signal wire 2. Controller failure | 1. Check and re-connect the signal wire 2. Change a new signal wire 3. Turn off electricity supply and restart machine 4. Change anew controller | p.45 |
| EE07 | 1. The compressor current is too large instantaneously 2. Wrong connection for compressor phase sequence 3.Compressor accumulations of liquid and oil lead to the current becomes larger 4. Compressor or driver board damaged 5. The water flow is abnormal 6. Power fluctuations within a short time | 1. Check the compressor 2. Check the waterway system 3. Check if the power in the normal range 4. Check the phase sequence connection | p.45 |
| EE08 | 1. Poor signal wire connection or damaged signal wire 2. Controller malfunction | 1. Check and re-connect the signal wire 2. Change a new signal wire 3. Turn off electricity supply and restart machine 4. Change anew controller | p.46 |
| EE09 | 1. Poor connection of communication wire 2. The wire is damaged | 1. Check the wire connection 2. Change a new wire | p.46 |
| EE10 | 1. Mother line voltage is too high 2. Driver board is damaged. | 1. Check if the power is in the normal range 2. Change driver board or main board | p.46 |
| EE11 | 1. Data mistake 2. Wrong compressor phase connection 3. Compressor liquid and oil accumulation lead to the current becomes larger 4. Compressor or driver board damaged | 1. Program error, turn off electricity supply and restart after 3 minutes 2. Change driver board 3. Check compressor sequence connection | p.46 |
| EE12 | 1. Mother line voltage is too low 2. Driver board is damaged. | 1. Check if the power is in the normal range 2. Change driver board | p.46 |
| EE13 | 1. The compressor current is too large momentary 2. The water flow is abnormal 3. Power fluctuations within a short time 4. Wrong PFC inductor | 1. Check the compressor 2. Check the waterway system 3. Check if the power is in the normal range 4. Check if the correct PFC inductor is used | p.46 |
| EE14 | 1. Output abnormity of IPM module thermal circuit 2. Fan motor is abnormal or damaged Fan blade is broken | 1. Change a driver board 2. Check if the motor speed is too low or fan motor damaged, change another one 3. Change another fan blade | p.46 |
| EE15 | 1. Output exception of IPM module thermal circuit 2. Motor is abnormal or damaged 3. Fan blade is broken | 1. Change a driver board 2. Check if the fan motor speed is too low or fan motor damaged, change another one 3. Change another fan blade | p.47 |
| EE16 | 1. Output exception of PFC module 2. Motor is abnormal or damaged 3. Fan blade is broken 4. Input voltage leap, input power is abnormal | 1. Change a driver board 2. Check if the motor speed is too low or fan motor damaged, change another one 3. Change another fan blade 4. Check the input voltage | p.47 |
| EE17 | 1. DC motor is damaged 2. Main board is damaged 3. The fan blade is stuck | 1. Detect DC motor, replace with a new one 2. Change a new main board 3. Find out the barrier and work it out | p.47 |
| EE18 | The driver board is damaged | 1. Change a new driver board 2. Check if the fan motor speed is too low or fan motor damaged, change another one | p.47 |
| EE19 | 1. PFC module thermal circuit output abnormal 2. Motor is abnormal or damaged 3. Fan blade is broken 4. The screw in the driver board is not tight | 1. Change a new driver board 2. Check if the motor speed is too low or fan motor damaged, change another one 3. Change another fan blade 4. Check if the screw is loose | p.47 |
| EE20 | The supply voltage fluctuates too much | Check whether the voltage is stable | p.47 |
| EE21 | 1.Compressor runs out of step 2. Wrong program 3. Impurity inside compressor causes the unstable rotate speed | 1. Check the main board or change a new one 2. Enter correct program | p.48 |
| EE22 | 1. Voltage signal abnormal 2. Driver board is damaged | 1. Check the main board or change a new one 2. Change a new driver board | p.48 |
| EE23 | 1. Main board is damaged 2. Compressor wiring error or poor contact or unconnected 3. Liquid accumulation inside 4. Wrong phase connection for compressor | 1. Check the main board or change a new one 2. Check the compressor wiring according to the circuit diagram Check the compressor or change a new one | p.48 |
| EE24 | Ambient Temperature device failure | Change driver board or main board | p.48 |
| EE25 | Compressors U, V, W are connected to one phase or two phases. | Check the actual wiring according to the circuit diagram | p.48 |
| EE26 | 1. Four-way valve reversal failure 2. Lack of refrigerant (no detect when T3 or T5 malfunction) | 1. Switch to Cooling mode to check the 4-way valve if it has been reversed correctly 2. Change a new 4-way valve 3. Fill with gas | p.48 |
| EE27 | 1. Wrong EEPROM data in the program or failed input of EEPROM data 2. Main board failure | 1. Re-enter correct EEPROM data 2. Change a new main board | p.48 |
| EE28 | Main board failure | 1. Turn off electricity supply and restart it 2. Change a new main board | p.48 |
Problèmes fréquents, causes probables et solutions.
| Problème | Cause possible | Solution | |
|---|---|---|---|
| Heat pump is not running | No power supply | Check cable and circuit breaker if it is connected | p.49 |
| Heat pump is not running | Heat pump under standby status | Startup heat pump to run. | p.49 |
| Heat pump is not running | 1. Water temperature is reaching to setting value, HP under constant temperature status. 2. Heat pump just starts to run. 3. Under defrosting. | 1. Verify water temperature setting. 2. Startup heat pump after a few minutes. 3. LED wire controller should display "Defrosting". | p.49 |
| Water temperature is cooling when HP runs under heating mode | 1. Choose the wrong mode. 2. Figures show defects. 3. Controller defect. | 1. Adjust the mode to proper running 2. Replace the defect LED wire controller, and then check the status after changing the running mode, verifying the water inlet and outlet temperature. 3. Replace or repair the heat pump unit | p.49 |
| Short running | 1. Fan NO running. 2. Air ventilation is not enough. 3. Refrigerant is not enough. | 1. Check the cable connections between the motor and fan, if necessary, it should be replaced. 2. Check the location of heat pump unit, and eliminate all obstacles to make good air ventilation. 3 Replace or repair the heat pump unit. | p.49 |
| water stains | 1. Concreting. 2. Water leakage. | 1. No action. 2. Check the titanium heat exchanger carefully if it is any defect. | p.49 |
| Too much ice on evaporator | 1. Check the location of heat pump unit, and eliminate all obstacles to make good air ventilation. 2. Replace or repair the heat pump unit. | p.49 |