SWIMMING POOL HEAT PUMP


1.1 With your Heat Pump
- Water connection assembly 50 mm (pcs: 2) - User and service manual - Condensed connection - 10 meters signal wire - Waterproof box - Winter cover - Anti-vibration base (pcs: 4)




Technical data PRO-ELYO Inverter pool heat pumps CE Standard, R410A, Heating and Cooling, inverter compressor, compressor defrosting, ABS Cabinet
* Above data are subjects to modification without notice.

The kit By-Pass is the essential accessory for the installation of your heat pump; it is also a tool for the optimization of the heating of the water. The regulation of the valves allows to optimize the flow of water and with the manometer to make sure the optimize running of the compressor.


The unit will work properly in any desired location as long as the following three items are present:
The unit may be installed in virtually any outdoor location as long as the specified minimum distances to other objects are maintained (see drawing below). Please consult your installer for installation with an indoor pool. Installation in a windy location does not present any problem at all, unlike the situation with a gas heater (including pilot flame problems).

ATTENTION: Never install the unit in a closed room with a limited air volume in which the air expelled from the unit will be reused, or close to shrubbery that could block the air inlet. Such locations impair the continuous supply of fresh air, resulting in reduced efficiency and possibly preventing sufficient heat output. See the drawing below for minimum dimensions.
NOTE


Note: If automatic dosing equipment for chlorine and acidity (pH) is used, it is essential to protect the heat pump against excessively high chemical concentrations which may corrode the heat exchanger. For this reason, equipment of this sort must always be fitted in the piping on the downstream side of the heat pump, and it is rSMARTmmended to install a check-valve to prevent reverse flow in the absence of water circulation. Damage to the heat pump caused by failure to observe this instruction is not covered by the warranty.


This arrangement is only an illustrative example.

The factory supplies only the heat pump. All other components, including a bypass if necessary, must be provided by the user or the installer.

After all connections have been made and checked, carry out the following procedure:
Depending on the initial temperature of the water in the swimming pool and the air temperature, it may take several days to heat the water to the desired temperature. A good swimming pool cover can dramatically reduce the required length of time.

Water Flow Switch: It is equipped with a flow switch for protecting the HP unit running with adequate water flow rate .It will turn on when the pool pump runs and shut it off when the pump shuts off.
Time delay - The heat pump has a built-in 3-minute start-up delay to protect the circuitry and avoid excessive contact wear. The unit will restart automatically after this time delay expires. Even a brief power interruption will trigger this time delay and prevent the unit from restarting immediately. Additional power interruptions during this delay period do not affect the 3-minute duration of the delay.
The air drawn into the heat pump is strongly cooled by the operation of the heat pump for heating the pool water, which may cause condensation on the fins of the evaporator.
The amount of condensation may be as much as several liters per hour at high relative humidity. This is sometimes mistakenly regarded as a water leak.
4.6 Pressure gauge display (R410A) Examine the pressure gauge which indicates the refrigerant gas pressure of the unit, the below table shows the normal value of the gas pressure (R410A) when the machine is in power off or running conditions.
Unit Condition Power Off
Ambient (℃) -5~5 5~15 15~25 25~35
Water temp (℃) /
Pressure gauge (Mpa) 0.68~0.93 0.93~1.25 1.25~1.64 1.64~2.1
Ambient (℃) /
Water temp (℃) 10~15 15~20 20~25 25~30 30~35
Pressure gauge (Mpa) 1.3~1.8 1.5~1.9 1.6~2.3 1.9~2.8 2.1~3.5
Unit Condition Running

PRO-ELYO INVERTER 13 / PRO-ELYO INVERTER 21



Above electrical wiring diagram only for your reference, please subject machine posted the wiring diagram.
NOTE
The swimming pool heat pump must be connected ground wire well, although the unit heat exchanger is electrically isolated from the rest of the unit .Grounding the unit is still required to protect you against short circuits inside the unit .Bonding is also required.


Photo(1) Photo(2) Photo(3) Photo(4) Photo(5)





- The side with plug connects with the control panel (photo1) - The other side of the signal wire. (photo2) - Open the wiring panel and put the side without plug through the electrical box. (photo3,4) - Insert the wiring into the designated position (upper right corner) on the PC board. (photo5)


When the swimming pool heat pump is running, the display inform the water temperature. When the Heat
6.2.1 button
Press to start the heat pump unit, the LED display shows the
desired water temperature for 5 seconds, then shows the inlet water
temperature and the operation mode.
Press to stop the heat pump unit and show “OFF”
Press again to turn on/off the machine.
6.2.2 button

Press for 5s to change the “ Heat MODE” or “ Cool MODE” .
6.2.3 and button
Water temperature setting :
Press and to set the water temperature directly.
Parameter checking :
Press first, then press to check the “ User parameter from d1 to d9.
TIME checking :
Press first, then press to check “current time”, press again to check the “Automatic
start time “ press once again to check “ Automatic stop time “ .
Press first ,then press the to enter into “Current time “ displaying . Then press once again
to enter into “HOUR” setting. The “Hour “ flashes, and press the or to set the hour ,then press
to save the “Hour”. Then the “ Minute” flashes, and press the or to set the “Minute” and finally
press the to save the current time setting , or press for quick-exit and saving.
If the current time is in the range of time OFF, the machine will be turn OFF automatically after setting the
time of automatic start and the time of automatic stop. Whereas the machine will operate normally.
Timer On setting:
Press first ,then press the twice to enter into ‘Timer on’ interface. Then press once again
to enter into “HOUR” setting. The “Hour “ flashes, and press the or to set the hour ,then press
TIME setting

to save the “Hour”. Then the “ Minute” flashes, and press the or to set the “Minute” and finally
press the to save the current time setting , or press for quick-exit and saving.
Once you set the timer on successfully , the light
will display.
Timer off setting:
Press first ,then press the three times to enter into ‘Timer off’’ interface. Then press once
again to enter into “HOUR” setting. The “Hour “ flashes, and press the or to set the hour ,then
press to save the “Hour”. Then the “ Minute” flashes, and press the or to set the “Minute” and
finally press the to save the current time setting , or press for quick-exit and saving.
Once you set the timer off successfully , the light
will display.
When you set Timer ON/OFF data 00:00, it means cancel the Timer ON/OFF function.

In order to heat the water in the pool (or hot tub), the filter pump must be running to cause the water to circulate through the heat pump. The heat pump will not start up if the water is not circulating. If the water is not circulating and the Heat Pump is ON the LED controller inform with the error code ON
LED wire controller can operate the water pump after connected additional cable to the pump device in the position of “PUMP” terminal accurately. When HP stop running in 30 seconds, water pump will shut off automatically
6.2.4 System reset function
Cancel Timer ON/OFF

Press and in 10s, the system will reset and display “0000” on the controller.
Symbol of heating, the light will be on when it is in operation.
When defrosting, the light will flash.
Symbol of cooling, the light will be on when it is in operation.
Symbol of automatic stop, the light will be on when it is in operation.
Symbol of automatic start, the light will be on when it is in operation.
Press this button, the light will be on, the heat pump will operate in Powerful only..
While you choose the Smart, the heat pump will just operate in Smart and Powerful.
While you choose the Silent , the heat pump will just operate in Silent and Smart.
The operating logistic of shift between Silent, Smart and Powerful: the default setting in factory is in Smart operating mode.
6.3 The operating logic

6.3.1 The heating operation logic
Working status Working mode Water in temperature Heat pump working level
2 setT-1< and < setT+1 SMART
3 ≧setT+1 Standby
Start-up of heat pump
5 setT-1< and < setT+1 SILENT
6 ≧setT+1 Standby
8 ≧setT+1 Standby
>setT -1 Standby
10 setT-3< and ≦setT-1 SMART
11 ≦setT-3 POWERFUL
Re-start to heat water
>setT -1 Standby
13 setT-3< and ≦setT-1 SILENT
14 ≦setT-3 SMART
15 POWERFUL ≦setT-1 POWERFUL
6.3.2 The Cooling operation logic
Working status Working mode Water in temperature Heat pump working level
2 setT-1< and
3 ≧setT+1 POWERFUL
Start-up of heat pump
5 setT-1< and
6 ≧setT+1 SMART
8 ≦setT-1 Standby
≧setT+1 and
10 ≧setT+3 POWERFUL
Re-start to cool water
≧setT+1 and
12 ≧setT+3 POWERFUL
14 ≦setT Standby




6.4 About the ambient temperature for the working frequency When you choose the “ POWERFUL “ working mode , if the ambient temperature ≧30℃and
and display the error code PP09 for compressor protection.
6.5 About the limitation of water in temperature Water in temperature ≦7℃, the heat pump will stop operation.
code EE3 or ON advertise on the controller.
It is important to program the heat pump link the time program of the water filtration system.
For restart the heat pump, turn off and turn on the electrical power supply to restart the unit.

Press first, then press to check the user parameter from d1 to d9 as below:





Parameter Name Range Remarks
d1 Inlet water temperature -9-99 ℃ Real testing value
d2 Outlet water temperature -9-99 ℃ Real testing value
d3 Ambient temperature -F(-30℃)-70℃ Real testing value
d4 Gas return temperature -F(-30℃)-70℃ Real testing value
d5 Coil temperature -F(-30℃)-70℃ Real testing value
d6 Gas exhaust temperature 0-C5℃(125℃) Real testing value
d7 Steps of electronic expansion valve 0-99 N*5
d8 Compressor operating frequency
0-99Hz Real testing value value
d9 Compressor current 0-30A Real testing value

Recover to Factory default setting
Long press and at the same time for 10 second to recover to factory default setting ,it will display ‘0000’ for 5 seconds is still required to protect you against short circuits inside the unit .Bonding is also required.
(1) When HP stop running in 30 seconds, water pump will shut off automatically
(2) LED wire controller can operate the water pump after connected additional cable to the pump device in the position of “PUMP” terminal accurately.
(3) It is necessary to put an extra 3-phase transfer device for 3 phase water pump.

Malfunction Error code Reason Solution
Inlet water temperature sensor
PP01 The sensor in open or short circuit Check or change the sensor
Outlet water temperature sensor
PP02 The sensor in open or short circuit Check or change the sensor
Heating condenser sensor failure PP03 The sensor in open or short circuit Check or change the sensor
Gas return sensor failure PP04 The sensor in open or short circuit Check or change the sensor
PP05 The sensor in open or short circuit Check or change the sensor
Condenser gas exit sensor failure PP06 The sensor in open or short circuit Check or change the sensor
Antifreeze protection in Winter PP07 Ambient temperature or water inlet
temperature is too low
PP08 Ambient temperature or water inlet
temperature is too low
Ambient temperature is too in
PP09 Ambient temperature is too
Stop the heat pump and wait
the ambient temperature at
less than Air 50℃( less 5 ℃in
The error code will disappear
Stop the heat pump and wait
temperature is too high
High pressure failure EE01 1.Refrigerant is too much
1.Discharge redundant refrigerant
from HP gas system
2.Clean the air exchanger
Low pressure failure EE02 1.Refrigerant is not enough
1.Check if there is any gas
2.Water flow is not enough
leakage ,re-fill the refrigerant
2.Clean the air exchanger
3.Replace the filter or capillary
Water flow failure EE03 or
Low water flow, wrong flow
Check if the water flow is enough
direction, or flow switch failure.
and flow in right direction, or else
the flow switch could be failed.

Malfunction Error code Reason Solution
EE05 Defrosting is not good
The throttling device is
Change the throttling device
Check the water pump
Controller failure EE06 Wire connection is not good
Check or change the signal
Restart the power supply or
Converter failure EE07 Converter board failure Restart the power supply or
change the converter board
EE08 Wire connection is not good
Check or change the wire
Restart the power supply or
EE09 Wire connection between
Restart the power supply or
outdoor board is wrong
change the outdoor board
EE10 Communication wire is
Restart the power supply or
between outdoor board and
change the broken board
Outdoor board or module
Module board failure EE11 The data is wrong or the
Restart the power supply or
module board is broken
change the broken board
Direct main current’s voltage
EE12 The pressure is too high or
Check the power supply
too high or too low
Over current protection EE13 Electric supply pressure is
Check the power supply
too low, the heat pump is
temperature whether it is too
Symbol of Defrosting, the
heating light is on

Malfunctions Observing Reasons Solution
Check cable and circuit breaker
no display.
if it is connected
LED wire controller.
Heat pump under standby
Startup heat pump to run.
Displays the actual time.
reaching to setting value, HP
setting.
status.
few minutes.
water temperature.
display "Defrosting".
controller, and then check the
LED wire controller displays
status after changing the
actual water temperature and
running mode, verifying the
no error code displays.
water inlet and outlet
temperature.
between the motor and fan, if
necessary, it should be
replaced.
LED displays actual water
temperature, no error code
pump unit, and eliminate all
displays.
obstacles to make good air
ventilation.
3 Replace or repair the heat
pump unit.
Water stains on heat pump
unit.
exchanger carefully if it is any
defect.
pump unit, and eliminate all
Too much ice on
obstacles to make good air
Too much ice on evaporator.
ventilation.
pump unit.







NO Part Name ERP NO Part Name ERP 1 Top cover 133070019 23 Terminal block 105000004 2 Back panel 133070031 24 Clip 136010004 3 Evaporator 103000104 25 Titanium heat exchanger 102040410
4 Pillar 108160016 25 Heat exchanger bottom plug 102040410 5 PFC inductor 117220001 25 Water connection cover 102040410 6 Left side panel 133070022 25 Water connection cover 102040410 7 Isolated panel 108160028 26 Pressure gauge 106000001 8 Base tray 108160044 27 Right panel 133070012 9 Top frame bracket 108160027 28 Waterproof controller box 133020003
10 Fan motor bracket(H series) 108160029 29 Controller 117020097 11 Fan motor 112000009 30 Wiring box 108010018 12 Fan blade 132000013 31 High pressure switch 116000008 13 Front panel 133070006 32 Low pressure switch 116000016 14 Front grill 108160012 33 Low pressure switch 116000020 15 Liquid storage pot 105000004 34 Suction valve 120000026 16 Inverter integration mainboard 117100006 35 Piping 114000044 17 slot 136020003 36 4‐way valve 121000009 18 Fan motor capacitor 111000005 37 EEV 119000021 19 Controller box 108160030 38 Water inlet rubber ring (blue) 133020011 20 Compressor 101000115 39 Water flow switch 116000001 21 Electric box cover 108160031 40 Filter 120000066 22 Terminal block box 108160024 41 Water outlet rubber ring (red) 133020012
42 Ambient temperature sensor
clip 113715001

NO Part Name ERP NO Part Name ERP
1 Top cover 133100001 33 Titanium exchanger 102040397
2 Back panel 133070032 33 Heat exchanger bottom plug 102040397
3 Evaporator 133000036 33 Water connection cover 102040397
4 Isolated panel 108120026 33 Water connection cover 102040397
5 Fan motor bracket 108120010 34 Water flow switch 116000001
6 Top frame bracket 108120005 35 Terminal blocks panel 108120020
7 Pillar 108120007 36 Five‐position blocks 115000004
8 Left side panel 133100012 39 Clip 136010004
9 PFC Inductor 117220002 40 Wiring box 108010018
10 Base tray 108120025 41 High pressure gauge 106000001
11 Fan motor 112000009 42 Right side panel 133070033
12 Fan motor 112000009 43 Terminal blocks plastic cover 133100011
13 Fan blade 132000013 44 Waterproof controller box 133020003
14 Fan blade 132000013 45 Controller 117020097
15 Front panel 133100006 46 Low pressure switch 116000019
16 Front grill 108160012 47 Low pressure switch 116000016
17 Front grill 108160012 48 Suction valve 120000023
18 Compressor 101000130 49 Water inlet rubber ring (blue) 133020011
19 Main board fixed panel 108050029 50 High pressure switch 116000008
20 Frequency conversion integrated
motherboard 117100008 51 Piping 113010013
21 Main board fixed panel 108050029 52 Temperature sensor casing 113190001
22 Controller box 108120027 53 4 way valve 121000009
23 Fan motor capacitor 111000005 54 Water outlet rubber ring (red) 133020012
30 Controller box cover 108120028 55 EEV 119000021
31 temperature sensor 117110014 56 Filter 120000066
32 Heat exchanger temperature sensor
clamp 108010025 57 Ambient temperater sensor
58 Liquid storage pot 105000008
clip 133020010

NO Part Name ERP NO Part Name ERP 1 Top cover 133100001 33 Heat exchanger bottom plug 102040411 2 Back panel 133070032 33 Water connection cover 102040411 3 Evaporator 103000109 33 Water connection cover 102040411 4 Isolated panel 108120009 34 Water flow switch 116000001 5 Fan motor bracket 108120010 35 Terminal blocks panel 108120020 6 Top frame bracket 108120006 36 Three‐position blocks 115000025 7 Pillar 108120007 37 Block panel bracket 108010023 8 Left side panel 133100012 38 Water pump blocks 115000027 10 Fan motor 112000009 39 Clip 136010004 11 Thin‐film capacitor 111000028 40 Wiring box 108010018 12 Capacitor clip 108010007 41 High pressure gauge 106000001 13 Electric reactor 117230001 42 Right side panel 133070033 14 Fan blade 132000013 43 Terminal blocks plastic cover 133100011 15 Front panel 133100006 44 Waterproof controller box 133020003 16 Front grill 108160012 45 Controller 117020097 17 Front grill 108160012 46 Low pressure switch 116000020 18 Controller box 108070028 47 Low pressure switch 116000016 19 IPM module 117080004 48 Suction valve 120000023 20 Fan motor capacitor 111000005 49 Water inlet rubber ring (blue) 133020011 21 Thermistor 117150001 50 High pressure switch 116000008 22 AC contactor 104000003 51 Piping 113010013 23 Termical blocks 115000009 52 Temperatur sensor casing 113190001 24 Compressor 101000114 53 4 way valve 121000009 25 Scaleboard 108120015 54 Water outlet rubber ring (red) 133020012 26 Outdoor power board 117190004 55 EEV 119000022 27 slot 136020003 56 Filter 120000066 28 linear transformer 117030005 57 Ambient temperater sensor clip 133020010 29 Indoor transfer board 117180021 58 Liquid storage pot 105000008 30 Outdoor control mould 117200003 59 Scaleboard 108120016 31 Temperature sensor 117110014 60 Controller box cover 108120018
32 Heat exchanger temperature
sensor clamp 108010025 61 Controller box 108120013
33 Titanium exchanger 102040411 62 Base 108120003

9.3 Maintenance (1) You should check the water supply system regularly to avoid the air entering the system and occurrence of low water flow, because it would reduce the performance and reliability of HP unit.
(2) Clean your pools and filtration system regularly to avoid the damage of the unit as a result of the dirty of clogged filter.
(3) You should discharge the water from bottom of water pump if HP unit will stop running for a long time (especially during the winter season).
(4) In another way, you should check the unit is water fully before the unit start to run again.
(5) After the unit is conditioned for the winter season, he is preconize to cover the heat pump with special winter heat pump.
(6) When the unit is running, there is all the time a little water discharge under the unit.

1.1 In accordance with these provisions, the salesman guarantees that the product corresponding to this warranty (“the
product”)does not present any non-conformance at the moment of its delivery.
1.2 The warranty period of the product is of two (2) years and it will take effect as of the time of delivery to the buyer.
1.3 If a Product non-conformance occurs and the buyer notifies it to the salesman during the Warranty Period, the salesman should
repairor replace the Product at his own cost in the appropriate place, unless it is impossible or disproportionate.
1.4 When the Product cannot be repaired nor be replaced, the buyer shall be able to ask for a proportional price reduction or, if the
non-conformance is sufficiently important, the discharge of the sales contract.
1.5 The replaced or repaired parts by virtue of this warranty will not extend the warranty term of the original Product, although they
willhave its own warranty.
1.6 For the effectiveness of this warranty, the buyer will have to credit the acquisition date and delivery date of the Product.
1.7 When the delivery of the Product to the buyer had been more than six months before and the buyer alleges non-conformance
with the Product, the buyer will have to prove the origin and existence of the alleged fault.
1.8 The present Warranty Certificate does not limit or prejudges the rights the consumers are entitled by virtue of local prevailing and
applicable regulations.
2.1 This warranty covers the products referred to in this manual.
2.2 This Warranty Certificate will be solely applicable in the countries of the European Union.
2.3 For the effectiveness of this warranty, the buyer will have to strictly follow the manufacturer instructions included in the
documentation enclosed with the Product, whenever this warranty is applicable according to the Product range and model.
2.4 When a calendar for the substitution, maintenance or cleaning of certain parts or components of the Product is specified, the
Warrantywill only be valid when the calendar has been observed.
3.1 This warranty will be solely applicable to those sales to consumers, being understood “consumers” as those people who acquire
the Product with a purpose that does not fall within the scope of their professional activity.
3.2 No warranty is granted referred to the wear and tear caused by the use of the Product. In relation to the parts, components and/or
consumable materials such as batteries, light bulbs etc, it will refer to the provisions of the documentation enclosed with the Product, when
applicable.
3.3 The warranty does not cover those cases where the Product: (I) has been incorrectly treated; (II) has been repaired, maintained
ormanipulated by a nonauthorized person, or (III) has been repaired or maintained with nonoriginal pieces.
When the non-conformance of the Product is a consequence of an incorrect installation or start-up, this warranty will only cover those
installations or start-ups included in the contract of sale of the Product and carried out by the salesman or under his/her responsibility.


Declares under their own responsibility that all the heat pumps: Pro Elyo Inverter
Manufactured since 31/03/2012, independent of the serial number, are in compliance with:
Machine safety directive 2006/42/EC.
Electromagnetic compatibility directive 2004/108/EC and its modifications.
Low-voltage equipment directive 2006/95/EC.
Directive 2000/14/CE concerning noise produced by equipment for outdoors use, as amended by Directive 2005/88/EC.
Restrictions in the use of certain risky substances in the electrical and electronic instruments 2002/95/EC (RoHS).
Relative to the electrical and electronic waste products 2002/96/EC (RAEE). Relative to the electrical and electronic
instruments and the management of their waste products Spanish R.D. 208/2005.
The registration, the evaluation, the authorization and the restriction of the chemical substances EC Nº 1907/2006 (REACH).

Pompe à chaleur pour piscine
La signification des codes d'erreur affichés à l'écran et la façon de les effacer.
| Code | Signification | Solution | |
|---|---|---|---|
| PP01 | The sensor in open or short circuit | Check or change the sensor | p.26 |
| PP02 | The sensor in open or short circuit | Check or change the sensor | p.26 |
| PP03 | The sensor in open or short circuit | Check or change the sensor | p.26 |
| PP04 | The sensor in open or short circuit | Check or change the sensor | p.26 |
| PP05 | The sensor in open or short circuit | Check or change the sensor | p.26 |
| PP06 | The sensor in open or short circuit | Check or change the sensor | p.26 |
| PP07 | Ambient temperature or water inlet temperature is too low | p.26 | |
| PP08 | Ambient temperature or water inlet temperature is too low | p.26 | |
| PP09 | Ambient temperature is too high | Stop the heat pump and wait the ambient temperature at less than Air 50℃( less 5 ℃in allowance) The error code will disappear automatically | p.26 |
| PP10 | Cooling condenser temperature is too high | Stop the heat pump and wait the cooling condenser temperature drop down | p.26 |
| EE01 | 1.Refrigerant is too much 2. Air flow is not enough | 1.Discharge redundant refrigerant from HP gas system 2.Clean the air exchanger | p.26 |
| EE02 | 1.Refrigerant is not enough 2.Water flow is not enough 3. Filter jammed or capillary jammed | 1.Check if there is any gas leakage ,re-fill the refrigerant 2.Clean the air exchanger 3.Replace the filter or capillary | p.26 |
| EE03 or "ON" | Low water flow, wrong flow direction, or flow switch failure. | Check if the water flow is enough and flow in right direction, or else the flow switch could be failed. | p.26 |
| EE05 | Defrosting is not good Lack of gas The throttling device is jammed Low water flow | Defrosting by hand Plus the gas Change the throttling device Check the water pump | p.27 |
| EE06 | Wire connection is not good Controller failure | Check or change the signal wire Restart the power supply or change the controller | p.27 |
| EE07 | Converter board failure | Restart the power supply or change the converter board | p.27 |
| EE08 | Wire connection is not good Controller failure | Check or change the wire connection Restart the power supply or change the controller | p.27 |
| EE09 | Wire connection between communication wire and outdoor board is wrong Outdoor board failure | Rewiring Restart the power supply or change the outdoor board | p.27 |
| EE10 | Communication wire is broken Outdoor board or module board failure | Restart the power supply or change the broken board | p.27 |
| EE11 | The data is wrong or the module board is broken | Restart the power supply or change the broken board | p.27 |
| EE12 | The pressure is too high or too low The inner communication contactor is broken | Check the power supply Change the contactor | p.27 |
| EE13 | Electric supply pressure is too low, the heat pump is overload | Check the power supply Check the water temperature whether it is too high | p.27 |
Problèmes fréquents, causes probables et solutions.
| Problème | Cause possible | Solution | |
|---|---|---|---|
| Heat pump is not running | No power supply | Check cable and circuit breaker if it is connected | p.28 |
| Heat pump is not running | Heat pump under standby status | Startup heat pump to run. | p.28 |
| Heat pump is not running | 1. Water temperature is reaching to setting value, HP under constant temperature status. 2. Heat pump just starts to run. 3. Under defrosting. | 1. Verify water temperature setting. 2. Startup heat pump after a few minutes. 3. LED wire controller should display "Defrosting". | p.28 |
| Water temperature is cooling when HP runs under heating mode | 1. Choose the wrong mode. 2. Figures show defects. 3. Controller defect. | 1. Adjust the mode to proper running 2. Replace the defect LED wire controller, and then check the status after changing the running mode, verifying the water inlet and outlet temperature. 3. Replace or repair the heat pump unit | p.28 |
| Short running | 1. Fan NO running. 2. Air ventilation is not enough. 3. Refrigerant is not enough. | 1. Check the cable connections between the motor and fan, if necessary, it should be replaced. 2. Check the location of heat pump unit, and eliminate all obstacles to make good air ventilation. 3 Replace or repair the heat pump unit. | p.28 |
| water stains | 1. Concreting. 2. Water leakage. | 1. No action. 2. Check the titanium heat exchanger carefully if it is any defect. | p.28 |
| Too much ice on evaporator | 1. Check the location of heat pump unit, and eliminate all obstacles to make good air ventilation. 2. Replace or repair the heat pump unit. | p.28 |