GENERAL
The LA/LB line is a flexible performer. LA300, LB360 & 480 can be positioned in up to 12 different positions and sus- pended in various positions. The LB600 can be positioned in up to 7 different arrangements and suspended also. The LA/ LB line will give you the power to condition large amounts of building space and the ability to conform to almost any situa- tion.
This product was manufactured in a plant whose quality system is certified/registered as being in conformity with ISO9001.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE


L A 300 C 00 A 6 A AA 1 A
NOTE: LB600 matches with both HB480 and HB600
NOTE: LB480 Indoor and HB480 Outdoor Units do
Outdoor Condensing Units for maximum effi- ciency.
match up, but do not meet ASHRAE 90.1 stan- dards for efficiency.

Figure 2 shows three of the common installation arrange- ments. Refer to the unit installation instructions for other pos- sibilities.
Evaporator blower units are designed with two distinct mod- ules to provide maximum application flexibility. The 25, 30 and 40 ton units are shipped as single packages with the blower module mounted on top of the coil module, The blower module can be repositioned in the field to meet almost any installation requirement. Blower and coil modules for the 50 ton units are shipped separately to simplify handling. These modules can be connected in the field with the same flexibility as the smaller units.
Units may be bottom-supported or ceiling-suspended and can be arranged to meet almost any space or duct require- ments. Each unit is available with a choice of blower motors, drive packages and other accessories to make them suitable for most applications.
The blower module includes the blower wheels and room for a field-mounted motor and drive. The coil module includes direct expansion coils, 2 in. throwaway filters, liquid line sole- noid valves for both capacity reduction and pumpdown, ther- mal expansion valves, distributors and a condensate drain pan.
PART LOAD OPERATION These evaporator blowers have multiple coils with pre-piped distributors, expansion valves and solenoid valves. Field modifications are not required for part load operations. Capacity reduction not only provides economical operation, but also maintains more even temper- ature and humidity levels in the conditioned space.
Every evaporator coil is pressurized with air to 325 psig and leak tested under water. After the headers are brazed onto the coil and the coil is installed in the unit, the coil is pressur- ized with a combination of Refrigerant-22 and nitrogen to 150 psig for pressure testing and additional leak testing. After the coil is evacuated and dehydrated, it is pressurized with a holding charge of Refrigerant-22 for storage and/or shipping.
EASY SERVICE Serviceable expansion valves are provided on every unit. These superior valves are factory-installed to provide many years of trouble-free operation. If service is required, it is not necessary to unbraze any joints.
PUMP-OUT Evaporator blowers include a solenoid valve for non-recycling pump-out. When a cooling requirement in the conditioned space is needed, the refrigerant is pumped into the high side of the system before unit start-up.
Steam coils, hot water coils, base sections, suspension hard- ware, blower motors and drive packages are available as field-installed accessories to provide additional application flexibility.
BASE SECTIONS (25, 30 and 40 ton only: Base sections can be used to elevate units above the floor. If desired, out- door air may be introduced through these sections by cutting an access opening to accommodate the outdoor air duct con- nection. These bases have a durable finish to match the evaporator blower unit. They may have to be insulated for certain applications.
These evaporator blowers, combined with condensing units, provide years of quiet, efficient and dependable operation. These units are manufactured under ISO 9001 Quality Sys- tem Certification.
For Indoor Unit Installation details, please see document 035- 18496-000.
SUSPENSION PACKAGES: These accessories can be used to suspend horizontal units from above without interfering with access to the unit. They can also be used for elevating a floor-mounted unit (either horizontal or vertical) to provide additional height for the installation of a trap at the conden- sate drain connection. All suspension packages can be used with vibration isolators.
These evaporator blowers can be arranged for a variety of air discharge patterns in either the horizontal or vertical position.
HOT WATER COILS: Drainable water coils are available for field installation between the blower and the coil modules of both horizontal and vertical units. Since their casings match the dimensions and the finish of the basic units, they become an integral part of the unit after installation. The coils slide out of their casings for easy installation. Coils have copper tubes that have been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. Coils are leak-tested at 325 psig under water and dried before their connections are capped for storage and shipping. FIGURE 2: UNIT INSTALLATION


STEAM COILS (LA300 & LB360 only): A steam coil is avail- able on the 25 & 30 Ton for installation between the blower and coil modules of both horizontal and vertical units. Since the casing matches the dimensions and the finish of the basic unit, it becomes an integral part of the unit after installation. The coil slides out of the casings for easy installation and is pitched in the casings to facilitate condensate drainage. The coil has copper tubes that have been mechanically expanded into aluminum fins. Both headers are located on the same end of the coil. The coil is leak-tested at 325 psig and dried before the connections are capped for storage and shipping.
rounding space. 5 HP motors are inherently protected. 7.5 HP - 15 HP require motor overload protection.
DRIVE PACKAGES: Different size pulleys and belts are available for each unit to provide a blower RPM range to meet almost any air delivery requirement. Variable pitch motor pulleys can be adjusted to provide the proper blower RPM. All drive packages are rated at least 25% above the nominal HP rating of the blower motor. Two-groove pulleys and two belts are provided on every drive package rated at 5 HP and above.
BLOWER MOTORS: Different HP motors are available for each unit to meet almost any air delivery requirement. All motors are UL approved, have permanently lubricated ball bearings and are field-mounted within the insulated cabinet of the units to minimize the transmission of sound to the sur-
STARTERS AND HEATER ELEMENTS (7.5 - 15 HP): The blower motors that are available for the units do not have inherent protection and require external motor overload pro- tection. See details in Table 7.


should be secured to the unit using the hardware
D
AX
AX BX
VERTICAL LA300, LB360, LB480 UNIT SUPPORTED FROM BELOW
BX
BLOWE R S E CTION
BLOWE R S E CTION
E VAP. C OIL
B
E VAP. COIL S E CTION
S E CTION
HOR IZONTAL LE U360 OR 480 UNIT S US PE NDE D FR OM ABOVE
B
S US PE NS ION
ANGLE S 1
BX
D
BX
The s ame channels can be used in either position. W hen used to support at vertical unit, these channels s hould be cut to match the bottom dimension of the evaporator coil s ection.
The s uspension channels have two s ets of mounting holes to accommodate horizontal units with or without a heating coil. O n a horizontal unit without a heating coil, the s uspension channels will extend 3" beyond both ends of the unit.
The same channels can be used to s upport a horizontal, fl oor- mounted unit from below.
4 After these bottom channels are cut per Note 1, a new hole will have to be drilled at the cut end if the unit is to be mounted on isolators.
1-1/2


Do not operate the supply air blower motor above its nominal HP rating when a unit is equipped with a hot water coil accessory. Do not use steam in hot water coils.
Do not operate the supply air blower above its nominal HP rating when a unit is equipped with a steam coil accessory.
Although these coils are suitable for a much higher pressure, steam above 25 psig provides too much heat that could damage the blower motor.




See detailed drawings for piping and drain connections on following pages.
TABLE 12: UNIT DIMENSIONS - LA300, LB360, LB480


FIGURE 6: 25 TON LIQUID LINE SOLENOID WIRING FIGURE 7: 30, 40 & 50 TON LIQUID LINE SOLENOID WIRING

LIQUID
LIQUID SYS. #2
SUCTION
SYS. #1
SUCTION
SYS. # 2
FIGURE 10: LB480 PIPING CONNECTIONS
FIGURE 8: LA300 PIPING CONNECTIONS
TABLE 13: UNIT CONNECTION SIZES
LIQUID (SYS. #2)
SUCTION (SYS. #1)
SUCTION (SYS. #2)
FIGURE 9: LB360 PIPING CONNECTIONS


4.7"
13.5"
Line Sys. #1
4.0"
10.1"
3.8" Liquid
Line Sys. #2
24.0"
Line Sys. #2
3.0"
23.86"
6.0" 2.1"
13.5"
Line Sys. #1
3.0"
6.7"


TABLE 14: HOT WATER COIL DIMENSIONS
COIL MODEL
UNIT MODEL
DIMENSIONS
A B C D E F
1HW0406 LA300 LB360 100-1/8 37-7/8 6-3/4 3-7/8 1-3/8 1-3/8
1HW0407 LB480 LB600 103-1/8 45-1/4 6-1/2 4 1-5/8 1-5/8

TABLE 15: STEAM COIL DIMENSIONS 1
COIL MODEL
UNIT MODEL
DIMENSIONS
A B C D E F G
1NF0454 LA300 LB360 100-1/8 37-7/8 4-3/8 18-3/8 1-1/2 2 2-1/2

BASE MODEL
UNIT MODEL
DIMENSIONS
A B
1BS0406 LA300 LB360 100-1/8 37-7/8
1BS0407 LB480 103-1/8 45-1/4

MODEL
DESCRIPTION
LA300 LB360 LB480 LB600
Rows Deep X Rows High 4 x 40 4 x 40 4 x 50 4 x 62
Finned Length, Inches 93 93 96 96
Face Area, Feet2 25.8 25.8 33.3 41.3
Tube (copper) OD, Inches 3/8
Fins (Aluminum) per 1 inch 16
Liquid, Inches 7/8
Suction, Inches 2 1/8 1 1/8 1 3/8 2 1/8
CENTRIFUGAL BLOWERS (2 PER UNIT) Diameter X Width, Inches (Forward Curved) 18 x 18 20 x 18
16 x 20 x 2 - 6 -
20 x 20 x 2 - 3 -
Size and Quantity Per Model, Inches
20 x 22 x 2 - - -
16 x 25 x 2 - - 6
20 x 25 x 2 10 6 3
25 x 25 x 2 - - 6
Total Face Area / feet2 34.7 42.6 53.1
System 1 49.65 30.08 37.83 46.59
(LBS R-22)
System 2 - 30.08 37.83 46.59
Tube (copper) OD, Inches 1/2 1/2 1/2
Rows Deep 2 2 2
Fins (Aluminum) per 1 inch 12 12 8
Face Area, Feet2 21.2 27.2 27.2
Connections (Supply & Return), Inches 1 3/8 OD (Copper) 1 5/8 OD (Copper)
Tube (copper) OD, inches 1 (Outside) 5/8 (Inside)
Fins (Aluminum) per 1 inch 8
N/A
Face Area, feet2 18.2
Connection, (Brass) Inches (NPTE)

MODEL
DESCRIPTION
LA300 LB360 LB480 LB600
Basic Unit (Less Motor & Drive) 980 980 1260 1474
Shipping Weight (lbs) 1180 1180 1510 1572
Operating Weight (lbs) 1125 1146 1426 1640
Hot Water Coil 150 150 190 190
Steam Coil 160 160 - -
117 (5hp) 117 (5hp) - -
Blower Motor (1750 RPM)
120 (7.5hp) 120 (7.5hp) 120 (7.5hp) 141 (10hp)
- 141 (10hp) 141 (10hp) 217 (15hp)
Accessories

UNIT MODEL HP FLA VOLTAGE (3PH-60HZ) MIN. CIRCUIT AMPACITY MAX. FUSE SIZE
(Amps)
16.7 208 21 35
15.2 230 19 30
7.6 460 10 15
6.1 575 8 15
24.2 208 30 50
22 230 28 45
11 460 14 20
9 575 11 20
16.7 208 21 35
15.2 230 19 30
7.6 460 10 15
6.1 575 8 15
24.2 208 30 50
22 230 28 45
11 460 14 20
9 575 11 20
30.8 208 39 60
28 230 35 60
14 460 18 30
11 575 14 20
24.2 208 30 50
22 230 28 45
11 460 14 20
9 575 11 20
30.8 208 39 60
28 230 35 60
14 460 18 30
11 575 14 20
30.8 208 39 60
28 230 35 60
14 460 18 30
11 575 14 20
46.2 208 58 100
42 230 53 90
21 460 26 45
17 575 21 35

CFM
RPM
8,000 9,000 10,000 11,000 12,000
SP2 BHP3 KW SP2 BHP3 KW SP2 BHP3 KW SP2 BHP3 KW SP2 BHP3 KW
635 0.56 2.4 2.3 0.43 2.7 2.6 0.31 3.3 3.1 0.13 3.8 3.5 - - -
700 0.80 3.0 2.8 0.68 3.3 3.1 0.54 3.7 3.5 0.38 4.2 3.9 0.20 4.8 4.5
775 1.12 3.7 3.4 1.00 4.0 3.7 0.85 4.4 4.1 0.70 4.8 4.5 0.54 5.3 5.0
800 1.23 3.9 3.7 1.11 4.3 4.0 0.97 4.7 4.4 0.82 5.1 4.8 0.66 5.6 5.2
875 1.60 4.8 4.5 1.48 5.1 4.8 1.34 5.6 5.2 1.19 6.0 5.7 1.04 6.6 6.2
900 1.73 5.1 4.8 1.61 5.5 5.1 1.47 5.9 5.5 1.33 6.4 6.0 1.17 7.0 6.5
940 1.95 5.6 5.2 1.82 6.0 5.6 1.70 6.5 6.1 -
1. Unit resistance is based on a dry evaporator coil and clean filters. 2. Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information. 3. Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat- ing device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP rating of the motor.
CFM
RPM
10,000 11,000 12,000 13,000 14,000
SP2 BHP3 KW SP2 BHP3 KW SP2 BHP3 KW SP2 BHP3 KW SP2 BHP3 KW
600 0.20 3.1 2.9 0.02 3.6 3.4 -
635 0.31 3.3 3.1 0.13 3.8 3.5 -
700 0.54 3.7 3.5 0.38 4.2 3.9 0.20 4.8 4.5 0.03 5.3 5.0 - - -
775 0.85 4.4 4.1 0.70 4.8 4.5 0.54 5.3 5.0 0.39 5.8 5.5 0.20 6.4 6.0
800 0.97 4.7 4.4 0.82 5.1 4.8 0.66 5.6 5.2 0.52 6.1 5.7 0.35 6.7 6.3
875 1.34 5.6 5.2 1.19 6.0 5.7 1.04 6.6 6.2 0.93 7.1 6.6 0.77 7.7 7.2
900 1.47 5.9 5.5 1.33 6.4 6.0 1.17 7.0 6.5 1.07 7.5 7.0 0.90 8.2 7.6
940 1.70 6.5 6.1 1.55 7.0 6.6 1.40 7.7 7.2 1.31 8.3 7.8 1.09 9.0 8.4
1. Unit resistance is based on a dry evaporator coil and clean filters. 2. Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information. 3. Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat- ing device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP rating of the motor.

10 BHP
900 RPM
8 BHP
TOTAL STATIC PRESSURE, IWG
800 RPM
5 BHP
6 BHP
700 RPM
3 BHP
4 BHP
600 RPM
2 BHP
500 RPM
0 0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230
Available external static pres- sure for unit accessories and the duct system.
Internal unit resistance based on a dry coil plus 2" throwaway filters.

CFM
RPM
12,800 14,400 16,000 17,600 19,200
SP2 BHP KW SP2 BHP KW SP2 BHP KW SP2 BHP KW SP2 BHP KW
600 0.20 4.3 3.7 -
640 0.38 4.8 4.1 0.19 5.6 4.8 -
700 0.65 5.5 4.7 0.47 6.4 5.5 0.28 7.2 6.2 -
775 0.99 6.5 5.6 0.84 7.4 6.4 0.66 8.4 7.2 0.46 9.4 8.1 0.23 10.4 9.0
800 1.11 6.8 5.9 0.96 7.8 6.7 0.79 8.8 7.6 0.59 9.8 8.4 0.36 10.8 9.3
900 1.65 8.1 7.0 1.52 9.3 8.0 1.36 10.5 9.0 -
915 1.73 8.3 7.2 1.60 9.5 8.2 1.44 10.7 9.2 -
CFM
RPM
16,000 18,000 20,000 22,000 24,000
SP2 BHP KW SP2 BHP KW SP2 BHP KW SP2 BHP KW SP2 BHP KW
600 0.82 6.0 5.2 0.59 7.2 6.2 0.35 8.4 7.2 0.08 9.7 8.4 - - -
660 1.17 7.3 6.3 0.96 8.5 7.3 0.73 9.8 8.5 0.45 11.2 9.7 0.14 12.7 11.0
700 1.40 8.2 7.1 1.21 9.4 8.1 0.98 10.7 9.2 0.70 12.2 10.5 0.40 13.7 11.8
760 1.76 9.5 8.2 1.59 10.8 9.3 1.38 12.3 10.6 1.11 13.8 11.9 0.81 15.6 13.5
800 2.00 10.4 9.0 1.85 11.8 10.2 1.64 13.3 11.5 1.38 14.9 12.9 1.09 16.9 14.6
900 2.60 12.8 11.0 2.49 14.5 12.5 2.35 16.0 13.8 -
930 2.78 13.5 11.6 2.68 15.3 13.2 -

1000 RPM
12-1/2 BHP
900 RPM
8 BHP
TOTAL STATIC PRESSURE, IWG
10 BHP
800 RPM
5 BHP
6 BHP
700 RPM
600 RPM
500 RPM
0 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Available external static pres- sure for unit accessories and the duct system.
Internal unit resistance based on a dry coil plus 2" throwaway filters.

800 RPM
16 BHP
12 BHP
14 BHP
TOTAL STATIC PRESSURE, IWG
700 RPM
10 BHP
8 BHP
600 RPM
6 BHP
500 RPM
0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360
AvaIlable external static pres- sure for unit accessories and the duct system.
Internal unit resistance based on a dry coil plus 1" throwaway filters.

THE DIMENSIONS OF EACH UNIT SHALL NOT EXCEED THOSE SPECIFIED.
a. Will permit the blower RPM to be adjusted to meet the exact CFM requirement of the system.