D o c u m e n t : V F 0 1 0 H 0 7 A INSTRUCTION MANUAL INSTALLATION - OPERATION - MAINTENA NCE HCV-1JBU Vacuum Contactor, 1.5kV - 600A HCV-1KAU Vacuum Contactor, 1.5kV - 720A Issued: 12/05 Manufactured in the USA Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net.
TOSHIBA INSTRUCTION MANUAL For the Installation, Operation and Maintenance of HCV-1JBU Vacuum Contactor, 1.5kV – 600A HCV-1KAU Vacuum Contactor, 1.5kV – 720A Never attempt to install, operate, mai.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net.
SAFETY Page 1 IMPORTANT MESSAGES Read this manual and follow its instructions. Signal words such as DANGER, WARNING and CAUTION will be followed by important safety information that must be carefully reviewed. Indicates a situation that will result in death, seri ous injury, and severe property damage if you do not follow instructions.
Page 2 SAFETY QUALIFIED OPERATORS ONLY Only qualified persons are to install, operate, or service this equipment according to all applicable codes and established safety practices. A qualified person must: 1) Carefully read the entire instruction manual.
SAFETY Page 3 HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion, and property damage. • Turn off and lock out Primary and Control Circuit Power before servicing. • Keep all panels and covers securely in place. • Never Defeat, Modify, or Bypass any Safety Interlocks • Qualified Operators only DANGER Phone: 800.
Page 4 TABLE OF CONTENTS SAFETY ............................................................................................................................... ....................... 1 INTRODUCTION ....................................................
TABLE OF CONTENTS Page 5 Table 3 – Gap/Wipe Standard Values (contactor in new condition)................................................ 20 Vacuum Check ................................................................................................
Page 6 INTRODUCTION It is the intent of this manual to provide a guide for safely installing, operating and maintaining T oshiba vacuum contactors. This manual consists of a section of general safety instructions and is marked throughout with warning symbols.
GENERAL DESCRIPTION Page 7 COMPONENTS The Toshiba HCV-1JB and HCV-1KA vacuum contactors described in this manual are suitable for use on systems of 1.5kV, 60 0A and 1.5kV, 720A respectively. Arc interruption is accomplished in side sealed vacuum interrupters mounted on tr ack-resistant insulators.
Page 8 GENERAL DESCRIPTION INDICAT ORS AND CON TROLS The following indicator is provided: On-Off Indicator - I ndicates if the contactor is OFF (Green) or ON (Re d). When the in dicator reads OFF, the main contacts of the contacto r are open. When the indicatio n is ON, the main contacts are closed.
RECEIVING, INSPECTION AND HANDLING Page 9 RECEIVING AND UNPACKING The contactor units are subjected to factory production testing prio r to being packed and shipped. ACCEPTANCE IN SPECTION Confirm that the contactor is compl ete, correct as specified and undama ged from shipment and handling.
Page 10 INSTALLATION AMBIENT CONDITIONS Do not install this equipment in a reas where unusual service conditions exist. Using thi s equipment in other than usual service conditions can result in equipment failure. Toshiba HCV-1JBU and HCV-1KAU contactors are intended for use in usual servic e conditions as defined in NEMA ICS 1.
INSTALLATION Page 11 Use two wrenches to torque the connection to prevent applying excessive force to the terminal, which can damage the frame. GROUND CONNECTION S The contactor must be grounded in accordance with the requirements of the National Electrical Code, Article 250 or applicable local standards.
Page 12 PRE-ENERGIZATION CHECK GENERAL BEFORE ENE RGIZING THE CONTAC TOR for the first time, follo w the procedure b elow to verify that the equipment is prope rly installed an d functional. Hazardous Voltage. Tu rn off and lock out all p rimary and control circuit power sources prior to performing this pre-energiz ation check.
OPERATION Page 13 MOVING THE CONT ACTOR FROM TH E OFF TO THE ON POSITION TO MOVE THE CONTACTOR TO THE ON POSITION: 1. Turn ON circuit control power to move the contactor to the ON position 2. Verify that the position indicator reads ON (Red). MOVING THE CONTAC TOR FROM THE ON TO THE OFF POSITION TO MOVE THE CONTACT OR TO THE OFF POSITION: 1.
Page 14 OPERATION Figure 8 – Internal Connection of the Normally Energized Type Figure 9 – Configuration of the Drive Unit 52 CC T1 T2 SWIT CHING TIMER POWER VO LTAGE DETEC T A 1 A 2 OSCIL LATI ON LEGEND 52 CC …. Closing Coil T1-T4 ….. Termi nal Bl ock A1-A2….
OPERATION Page 15 Figure 10 - Standard Operation Circuit of the Normally Energized Type. Remot e Ope r a t i on Swi t c h St op In te rlo ck CR Dr S (D oo r S witc h) St a r t In te rlo ck Local Remot.
Page 16 MAINTENANCE MAINTENANCE PROGRAM In order to ensure conti nued reliable and saf e operation of the equipment, a prog ram of periodic maintenance must be establishe d. Operating and enviro nmental conditions will usually dictate the frequency of inspection required.
MAINTENANCE Page 17 RECOMMENDED INSPECTION AN D MAINTENANCE TYPES NOTE: Refer to the SAFETY s ection of this manual for import ant information. 1. Acceptance Inspection This inspection confirms that the contactor is complete, correct as spe cified and undamaged fro m shipment.
Page 18 MAINTENANCE Table 2 - Check Points for Periodic Inspection Check Point Check Item Check Method Criteria Disposition Operating Mechanism Loose bolts, nuts or screws Tighten using screwdriver or wrench. Make sure all bolts, nuts and screws are tight.
MAINTENANCE Page 19 Table 2 – Check Points for Periodic Inspection (cont.) Check Point Check Item Check Method Criteria What to do Main Circuit Dust on surface of vacuum interrupter Visual inspection. Make sure there is no dust on the surface. Wipe with a clean, dry cloth.
Page 20 MAINTENANCE Table 2 – Check Points for Periodic Inspection (cont.) Check Point Check Item Check Method Criteria What to do Dielectric Strength Measure main circuit Measure dielectric strength between phases and between circuits and ground. 10kV AC or 14kV DC for 1 minute.
MAINTENANCE Page 21 VACUUM CHECK A sufficient level of vacuum is necessary for proper performance of the vacu um interrupters. Although vacuu m leaks are rare, the vacuu m integrity should b e checked periodically.
Page 22 MAINTENANCE CRITERIA: 1. If a current flow above 5 milli-amperes is observed or if breakdown occurs, one or more of the inte rrupters has ins ufficient vacuum and must be replac ed. Exception: If the current exceeds 5 milli- amperes the first time the voltag e is brought up, reduce the voltage to zero and i ncrease it again.
MAINTENANCE Page 23 ELECTRICAL SERVICE LIFE The electrical service life of the vacuum interrupter is defined by the electrode wear and the number of open/close operations (mechanical life). To determine electrode wear, measure the distance between the lever and washer in the closed (ON) state, as shown in Figure 13.
Page 24 DISPOSAL AND STORAGE STORAGE If the contactor is to be stored for a ny length of time prior to installation, the followi ng precautions should be taken. 1. The original packing should be res tored, if possible. 2. Do not subject the equipment to moisture or sunrays.
SPECIFICATIONS Page 25 Table 5 - Ratings Items HCV-1JBU HCV-1KAU Rated Insulation Voltage kV 1.5 Rated Operation Voltage V 208-1500 Rated Operational Current A 600 720 Rated Frequency Hz 50/60 Rated Making Current kA 6.0 (close 100 times) 7.2 (close 100 times) Rated Breaking Current kA 4.
WARRANTY AND LIMITATION OF LIABILITY Page 26 Toshiba International Corporation ("Company") warrants th at all equipment and parts described herein will be free from defects in materials and workmanship.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Toshiba HCV-1JBU c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Toshiba HCV-1JBU - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Toshiba HCV-1JBU, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Toshiba HCV-1JBU va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Toshiba HCV-1JBU, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Toshiba HCV-1JBU.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Toshiba HCV-1JBU. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Toshiba HCV-1JBU ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.