CORPORATE OFFICE 13131 WES T LITTLE YORK ROAD HOUSTON, TX 7704 1 PHONE: (713) 466- 0277 (800 ) 231- 1412 FACSIMILE: (713) 896 - 5226 1 TOSH I BA G9000 80/100/160/225 kVA GUIDE SPECIFICATION THREE PHAS.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 2.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 3 Table of Contents 1 SCOPE ..........................................................................................................................................................
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 4 9.2 R EMOTE S TATUS A LARM P ANEL (RSAP) ............................................................................................................................... 15 10 TOSHIBA DISTRIBUTION CABNET (TDC) (OPTION) .
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 5 1 SCOPE 1.1 Sy stem Th ese specifications desc ribe a high eff iciency continuous duty, three-pha se, on-line, solid-state Uninterruptible Power Supply system (UPS).
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 6 2.3 Sy stem Operation: The UPS shall operate as a f ully automatic on-line sy stem i n the following modes: 2.3.1 Normal I GBT Rectifier c onverts AC input power to DC power for the inverter and for cha rging the batteries.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 7 3.2.3 Clearances for installation Ceiling L evel : 20 ” minimum from top of UPS to ceiling Front : 40 ” minimum for maintenan.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 8 Current THD : <3% THD at 60% – 100% load <6% THD at 25% – 59% load (No input harmonic filter require d) 4.1.3 Charging Function: DC Nominal Voltage : 480 V AC Ripple on DC Bus : < 0.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 9 Harmonic Voltag e Distortion : < 2% THD (100% L inear L oad) : < 5% THD (100% Non-linear L oad) Phase Displacement : 1° Ma.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 10 5.2.3 Battery Protection The converter shall be provided with monitoring and control cir cuits to protect the battery sy stem from damag e due to excessive discharg e.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 11 5.3.5 Overload Capacity : The I nverter output shall be c apable of providing an overload curre nt of 125% for 2 min. and 150% for 1 min. A messag e on the control panel shall indicate this condition.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 12 I f the by pass sourc e is bey ond the conditions stated be low, interrupted transfer sha ll be made upon detection of a f ault condition. By pass voltage greater than + 10%, -10% from the UPS rated output voltag e.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 13 5.5.4 Mimic Panel A one-line diag ram of the sy stem shall be display ed on the touch pane l display panel to provide a visual status of contactors within UPS.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 14 6 MECHANICA L DESIGN 6.1 UPS Enclosure The UPS shall be a free standing NEMA1 enclosure equipped with a leveling c hannel base. The enclosure shall include provisions for hoisting , jacking, and fo rklift handling.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 15 9.1.2 HTTP Familiarity The RemotEy e I I shall provide a HTTP interfac e for the UPS to allow easy access of the UPS information from any machine with a web browser. At any ti me, a network workstation or management sta tion shall be able to open a RemotEy e II website.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 16 10 TOSHIBA DISTRIBUTION CABN ET (TDC) (OP TION) The manufacture r can optionally provide a matching TDC for the UPS. The TDC can include a step-down, 480/208/120 V transformer in a matching NEMA1 cabinet.
Guide Specification – 3-Phase Static Uninterr uptible Power Supply 17 14 EXTENDED SER VICES (OPTION) The UPS manufacturer c an offer : Startup Service Maintenance Contrac ts (Silver, Gold, Platinum).
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Toshiba G9000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Toshiba G9000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Toshiba G9000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Toshiba G9000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Toshiba G9000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Toshiba G9000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Toshiba G9000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Toshiba G9000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.