HO T W A TER MODELS V -33 THR OUGH V -180 INST ALLA TION AND OPERA TING INSTR UCTIONS GAS-FIRED CAST -IR ON BOILERS FOR NA TURAL AND L.P . PR OP ANE GASES CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .P A GE Ratings and Dimensions .
2 V ICTOR Y Dimensions (inches) Figure 1. Left End View Figure 2. Front View Figure 3. Right End View NO TE: Height Dimension increases to 30-3/16" and depth dimension increases to 22-1/4" when combustib le floor kit is used.
V ICTOR Y 3 I NST ALLA TION REQUIREMENTS The installation must conf or m to the requirements of the a uthority having jurisdiction or , in the absence of such requirements, to the National Fuel Gas Code , ANSI Z223.1- l atest edition. This installation must also conf or m to the additional require- ments in this Slant/Fin instruction book.
4 V ICTOR Y Reference T able No. * Appliance Connector Requirements* (ANSI Z223.1) Victor y Boilers T ype “B” See table 11-1 f or minimum and maximum of v ent 11-1 (V -90, V -120, V -150 and V -180) height and lateral length restriction.
V ICTOR Y 5 HORIZONT AL PRESSURE VENTING All VICT OR Y models are cer tified for horizontal pressure venting with the f ollowing restrictions: 1. V ent Material A . The vent system f or horizontal venting m ust be UL list- ed single wall Saf-T 3" diameter #AL 29-4C s stainless steel manuf actured by Heat-F ab, Inc.
Model/V ent Siz e V -90, V -120, V -150 and V -180 boilers ma y be vented into a chimney (see “Chimney and type “B” v enting” paragraph on page 4) or into a type “B” v ent, ONL Y when converted to the 5" dia.
V ICTOR Y 7 Figure 6b. V enting with “B” vent or metal-lined chimney for V -90, V -120, V -150 and V -180 only Minim um vent connector s diameter is 5 inches.
8 V I CTOR Y Figure 7. Horizontal V enting (3 IN.): All Victor y Models All items shown belo w are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT . Use only 3" dia. Saf-T vent (#AL 29-4C* stainless steel) venting materials by Heat-F ab Inc.
V I CTOR Y 9 Figure 8. Horizontal V enting (3 IN.): All Victor y Models All items shown belo w are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT . Use only 3" dia. Saf-T vent (#AL 29-4C* stainless steel) venting materials by Heat-F ab Inc.
1 0 V ICTOR Y Figure 9. V ertical V enting (3 IN.): All Victory Models All items shown belo w are REQUIRED. All vent joints must be LIQUID and PRESSURE TIGHT . Use only 3" dia. Saf-T vent (#AL 29-4C* stainless steel) venting materials by Heat-F ab Inc.
V ICTOR Y 1 1 at test pressures equal to or less than 1/2 PSIG. D . All gas piping used should be inspected thoroughly f or cleanliness bef ore makeup .
1 2 V ICTOR Y B . PUMP LOCA TION-Locating low-head pump(s) on return to boiler is acceptable for smaller boiler siz es in residences of one or two stories. The alter nate pump location shown in illustration on page 11 is required in l arge, multi-story building installations, especially when high-head pumps are used.
V ICTOR Y 1 3 8. T urn on all electr ic power to the appliance . 9. Set ther mostat to desired setting. 10. If the appliance will not operate, f ollow the instructions "T o T ur n Off Gas T o Appliance" and call your service technician or gas supplier .
1 4 V ICTOR Y 2. Safety Shutdown Chec kout a. For proper operation the pilot should engulf the thermocouple, powerpile generator or flame sen- sor as shown belo w .
V ICTOR Y 1 5 burners as described on page 13. * T o clean burners run a clean flue brush up the tube until all f oreign matter is removed. IV . SAFETY CHECK FOR CONTR OL SYSTEM 1. Remove Control Co ver T o remov e control cov er , remov e the two sheet metal screws in the top of the top co ver .
1 6 V ICTOR Y A PPENDIX A Remov al Of Existing Boiler From Common V ent System "At the time of remov al of an existing boiler , the follo wing s teps shall be f ollowed with each appliance remain.
V ICTOR Y 1 7 Sequence of Operations Wiring Diagrams CA UTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. “V er ify proper oper ation after ser vicing. ” THERMOST A T CALLS FOR H EA T C IRCULA TOR CONTINUES TO RUN.
1 8 V I CTOR Y PUMP OR V AL VE ZONING OF W A TER BOILERS COMBINA TION CONTROLS WITH T TV Z TERMINALS* Pump Zoning system using R845 Rela y . One R-845A needed f or each circulator . NO TE: Pumps are powered from C1. T otal pump load must not e xceed 7.
V ICTOR Y 1 9 B URNERS F AIL T O OPERA TE C A USE 1. Safety pilot out, or flame too lo w . 2. Gas supply valv e shut off . 3. Electric switch open. 4. Blown or def ective line fuse . 5. Operating or limit control contacts open or dir ty . 6. Defectiv e gas v alve or pressure regulator; or plugged bleed l ine.
20 V I CTOR Y PIPING A HEA TING - COOLING SYSTEM T O A W A TER BOILER AND CHILLER Figure below illustrates a method of piping a heating-cooling system to a water boiler and a chiller . Hand valves (sho wn) or automatic valv es must be installed to prev ent circulation of c hilled water in the boiler or hot w ater in the chiller .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Slant/Fin V-180 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Slant/Fin V-180 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Slant/Fin V-180, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Slant/Fin V-180 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Slant/Fin V-180, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Slant/Fin V-180.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Slant/Fin V-180. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Slant/Fin V-180 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.