Installation Instructions T ype C Boilers G.C.N: 41-116-06 41-116-07 LEA VE THESE INSTRUCTIONS WITH THE END-USER Countr y of destination: GB.
2 T ABLE OF CONTENTS 1. GENERAL INFORMA TION 1.1 G ENERAL I NSTR UCTIONS 1.2 O VERALL V IEW 2. INST ALLA TION 2.1 R EFERENCE S T ANDARDS 2.2 S ITING THE A PPLIANCE 2.3 O VERALL D IMENSIONS 2.4 C LEARANCES 2.5 M OUNTING THE A PPLIANCE 2.6 E LECTRICAL C ONNECTION 2.
This manual is an integr al and essential par t of the product. It should be k ept with the appliance so that it can be consulted by the user and our authorised personnel.
4 4 - Visual check of the comb ustion process or analysis of comb ustion by- products (see section 4.5) and cleaning of the burner if needed. 5 - If called f or by point. 3, dismantling and cleaning of the comb ustion chamber . 6 - If called f or by point.
5 The technical inf or mation and instructions provided herein below are intended f or the installer so that the unit ma y be installed correctly and saf ely .
F or saf ety pur poses, ha v e a competent person carefully check the electrical system in the proper ty , as the manuf acturer will not be held liab le f or damage caused by the f ailure to ear th the appliance properly or by anomalies in the supply of power .
V IEW OF THE B OILER C ONNECTIONS L EGEND : A = Central Heating Flow C = Gas Inlet E = Central Heating Return F = Saf ety V alve G = Pump transpor tation screw (remov e bef ore igniting the boiler) H .
8 P IPE W ORK : Copper tubing to BS EN 1057:1996 is recommended f or water pipes . Jointing should be either with capillar y soldered or compression fittings. Where possible pipes should ha v e a gradient to ensure air is carried naturally to air release points and water flo ws naturally to dr ain taps.
Ø 60/100 mm F IG . 2.6 A BC D E F G J K HI L G F The boiler is designed to be connected to a coaxial flue discharge system. 9 2.9 F LUE C ONNECTIONS F LUE S YSTEM The provision f or satisf actory flue ter mination must be made in accordance with BS 5440-1.
Ø 80 mm In addition, it is also possible to use a split (twin pipe) system by fitting a special adaptor to the flue connector and using the aper ture for the air v ent intak e located on the top par t of the combustion chamber . T o utilise the air intake it is necessar y to: 1.
L = Sum of the total length of exhaust + air intak e piping. 11 Exhaust T ype C12 (xx) C32 (xx) C42 (xx) Restrictor ø 46 mm L min = 0.5 m L max = 1 m Maximum Extension Exhaust/Air L = 4 m Risk of Con.
12 T o connect a room ther mostat and/or time clock, it is necessar y to: 1. - Open the control panel as indicated in section 4.3; 2.- Remove scre ws “ A ” and remov e the inspection co ver from the re verse of the control panel; 3.
2.11 E LECTRICAL D IA GRAM 13 F IG . 2.12 L EGEND : A - On/Off Switch B - On/Off L.E.D . C - Heating Switch D - Heating L.E.D . E - Reset Button F - Ignition F ailure (Loc k out) L.
14 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 L EGEND : 1. F an 2. Main heat e xchanger 3. Overheat thermostat 4. Bur ner 5. Ignition electrodes 6. Detection electrode 7. Regulation ther mostat 8. F rost thermostat 9. Gas valv e 10. Pump pressure s witch 11.
15 3. D .H.W . ST ORA GE CYLINDER The microSYSTEM can be connected to a storage cylinder (both open-v ented and unv ented) f or the production of domestic hot water (D .H.W .). Cylinders of different capacities can be used depending on site requirements (see T ABLE 3.
16 T echnical Data Capacity Coil C.H.W . D .H.W . Max Heating Heat Ioss Surface Flow/rate Flo w/rate Output MODEL It. m 2 m 3 /h It/h kW kWh/24h Contract STI 125 Indirect 125 0.75 0.5 194 11.3 2 1 266 15.5 2 340 19.8 Comfort STI 125 Indirect 125 0.75 0.
17 MTS (GB) Limited suppor t the initiative . Within the information pack you will find a cop y of the logbook. It is impor tant that this is completed in the presence of your customer , they are sho wn how to use it, and it is signed by them.
In order to access the inside of the boiler , it is necessary to unscrew the f astening scre ws “ A ” of the control panel located on the lower part of the panel itself. The control panel mov es downw ard and when pulled f orward rotates on two later al hinges.
19 The flue connector has two aper tures, readings can be taken f or the temper ature of the combustion b y-products and of the combustion air , as well as of the concentrations of O 2 and CO 2 , etc. . T o access these intak es it is necessar y to unscrew the front screw and remo v e the metal plate with sealing gasket.
The boiler is fitted with the f ollowing de vices (see section 4.2 f or ref erences). 1 - I GNITION F AILURE : This indicates ignition f ailure when a flame is not detected within 7 seconds of star ting an ignition sequence. The L.E.D . “ F ” will illuminate to signal the shutdown status .
21 The boiler can be con verted to use either methane (natural) gas (G20) or LPG (G30 - G31) by an A uthorised Service Centre. The operations that must be perf ormed are the follo wing: 1 . Replace the jets on the main burner (see table in section 5); 2.
22 It is recommended that the follo wing inspections be carried out on the boiler at least once a year: 1 - Check the seals f or the w ater connections; replace any f aulty seals. 2 - Check the gas seals; replace any f aulty gas seals . 3 - Visual check of the entire unit.
23.
Manuf acturer: Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A v enue High Wycombe Bucks HP13 5FT T elephone: (01494) 755600 F ax: (01494) 459775 Internet: http://www .mtsgb .ltd.uk E-mail: inf o@mtsgb .
Servicing Instructions T ype C Boilers G.C.N: 41-116-06 41-116-07 LEA VE THESE INSTRUCTIONS WITH THE END-USER Countr y of destination: GB.
2 1. SER VICING INSTR UCTIONS 1.1 R EPLACEMENT OF P AR TS 1.2 T O G AIN G ENERAL A CCESS - Removing the front panel - Removing the sealed chamber front co ver - Removing the side panels 1.
2. The control panel mov es downw ard and when pulled f orward, rotates on two lateral hinges; the panel sta ys in a semi- horizontal position, which allows access to the inner parts of the boiler (F IG .
4 1.2.2 Removing the sealed c hamber front co ver 1. Remov e the screws “C” (F IG . 1.6); 2. Lift the sealed chamber front cov er from the locating pins (F IG . 1.7). F IG . 1.6 C C F IG . 1.7 1.2.3 Removing the side panels 1. Remov e the f our screws “D” for each side panel (F IG .
1.3.3 Removing the electr odes Bef ore carr ying out this procedure, unscre w and slide the burner forw ard (see pre vious section). 1. Remov e rubber gasket “G” (F IG . 1.12); 2. T o remove the detection electrode disconnect the cab le at its connection point close to the P .
6 3. Remov e scre w “H” ( F IG . 1.14); 4. Gently slide the electrode downw ard (F IG . 1.15) . T o replace, repeat the steps in rev erse order , paying par ticular attention to the follo wing: a .
1. Disconnect electrical connections “N” and silicon pipe “O” (F IG .1.22); 2. Remov e scre w “P” and remov e the f an collar clamp “Q” (F IG .1.23); 3. Remov e scre ws “R” (F IG .1.24); 4. Remov e f an and mounting plate (F IG .1.
8 1.4 S ER VICING AND R EMO V AL OF THE G AS V AL VE 1.4.1 Setting the gas pressures 1 2 3 4 A B C F G D Setting the minimum and the maxim um power of the boiler 1. Check that the supply pressure to the gas v alv e is a minimum of 20 mbar f or natural gas.
9 GAS BURNER PRESSURE OPERA TING POWER Regulating the heating power f or natural gas (G20) GAS BURNER PRESSURE OPERA TING POWER Regulating the heating power f or butane gas (G30) GAS BURNER PRESSURE OPERA TING POWER Regulating the heating power f or propane gas (G31) 21 RFFI 28 RFFI 2.
10 F IG . 1.28 F IG . 1.29 F IG . 1.30 U V V 1.4.3 Removing the gas v alve Impor tant! Before removing the gas v alv e , ensure the gas supply is tur ned off . 1. Disconnect all the cables from the solenoid and modureg; 2. Remov e the spark generator (see pre vious section); 3.
11 1. 5. 2 Removing the safety v alve 1. Loosen nut “ Y ” (F IG . 1.33); 2. Disconnect the discharge pipe work from below the boiler ; 3. Unscrew and remo v e the valv e . 1.5.3 Removing the automatic air vent 1. Unscrew v alv e top “ Z ” (F IG .
12 1.5.4 Removing the pump 1. Remov e the U-clips “ A1 ” and “ B1 ” (F IG . 1.36); 2. Remov e the retaining clip “ C1 ” (F IG . 1.37); 3. Release the nut “ D1 ” (F IG . 1.38); 4. Remov e the pipe “ E1 ” (F IG . 1.39); 5. Remov e the scre w “ F1 ” (F IG .
13 1.5.6 Removing the e xpansion vessel 1. Release nuts “ H1 ” and remov e the gas pipe (F IG . 1.44); 2. Release nut “ I1 ” (F IG . 1.45); 3. Remov e loc k-nut “ J1 ” (F IG . 1.46); 4. Remov e the e xpansion v essel (F IG . 1.47). 1.5.5 Removing the pressure gauge 1.
14 1.5.6 Removing the o verheat thermostat 1. Disconnect the ov erheat thermostat electr ical connections “ K1 ” (F IG . 1.48); 2. Then remov e the thermostat from its mounting by releasing the securing clip (F IG . 1.49). 1.5.7 Removing the fr ost thermostat 1.
15 1.6.2 Removing the P .C.B.s 1. Isolate electricity; 2. Remov e the scre ws “ O1 ” (F IG . 1.56); 3. Separate the f acia panel from the rear of the control panel; 4. Unplug all electrical connections from the P .C .B. and remov e the scre ws “ P1 ” and remov e the P .
16 B063 2. F A UL T FINDING P RELIMINAR Y CHECKS MAKE SURE THA T : IS THE SUPPL Y L.E.D. ILLUMINATED? IS THE L.E.D. ILLUMINA TED? NO NO NO YES NO 1 - C HECK THE FUSES 2 - C HECK THERE IS POWER SUPPLIED TO THE P .C.B. S 3 - C HECK / REPLACE THE P. C . B .
17 B063 IS THE PUMP RUNNING? NO YES PO WER T O THE PUMP? 1 - C HECK THE OPERA TION OF THE PUMP 2 - R ELEASE /R EPLACE THE PUMP 1 - C HECK THE PUMP CABLE 2- C HECK /R EPLA CE P.
18 B063 IS THE BURNER ALIGHT? YES NO YES YES BOILER WORKING? YES NO NO NO NO YES 5- C HECK /R EPLACE P . C . B . (CBM2) 4-C HECK /R EPLACE P .C .B. (CBM2) 4 - C HECK /R EPLA CE P .
19 B063 3. ELECTRICAL DIA GRAMS SE011A L EGEND : A - On/Off Switch B - On/Off L.E.D . C - Heating Switch D - Heating L.E.D . E - Reset Button F - Ignition F ailure (Loc k out) L.
20 B063 SF008A.
21 B063 21/28 RFFI 354 353 352 351 33 63 61 9 10 11 12 7 4 3 2 60 62 1 11 12 11 11 65 67 68 69 64 11 72 104 100 97 99 98 77 79 80 81 101 80 106 107 105 103 75 76 102 13 64 66 11 64 64 82 59 89 74 13 2.
22 B063 998616 573521 573520 570760 998612 573528 998447 569390 998627 999542 574279 999475 998809 999476 998424 998836 999091 999577 999499 999245 998517 998484 571651 997182 998943 998489 999894 998.
23 B063 NO TES.
23 99 84 1550 000 - Manuf acturer: Merloni T ermoSanitari SpA - Italy Commercial subsidiar y: MTS (GB) LIMITED MTS Building Hughenden A v enue High Wycombe Bucks HP13 5FT T elephone: (01494) 755600 F ax: (01494) 459775 Inter net: http://www .mtsgb .ltd.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Ariston 41-116-07 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Ariston 41-116-07 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Ariston 41-116-07, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Ariston 41-116-07 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Ariston 41-116-07, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Ariston 41-116-07.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Ariston 41-116-07. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Ariston 41-116-07 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.