USER'S GUIDE JY992D53201C This manual contains text, diagrams and explanations which will guide the reader in the correct installation and operation of the FX and FX 0N , 485 communication adapters. It should be read and understood before attempt- ing to install or use these units.
1 INTRODUCTION ①⑥ LINK SG SDB SDA RDB RDA FG 24+ 24G 〈 FX-485ADP 〉 MITSUBISHI FX-485ADP ① Direct mounting hole ② Power LED · · · ③ R D L E D ······· ④ S D L E D ······· ⑤ Terminal screws (M3 (0.12)) ⑥ Extension cable ⑦ Terminal cover ⑧ Groove for mounting DIN rail (DIN rail width : 35 (1.
Station No.15 ↑ FX series PC Max. 16 stations including A series PCs (total extension distance 500m) (2) Computer and PC by 1 : n configuration In this case, the number of link stations is 16 PCs at maximum for one computer, including the FX series PCs and A series PCs.
For setting up the system, the 485ADP can be connected to the following PCs. PC series FX 0N FX , FX 2C PC version Ver. 1.20 or later Ver. 3.30 or later Remarks Exclusive protocol format 1 and format 4 are supported. Exclusive protocol format 1 and format 4 are supported.
*1 R is the terminating resistance. Connect the terminating resistance (330 Ω ) between terminals SDA and SDB , and terminals RDA and RDB . For details see section 2.3. *2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100 Ω or less.
*1 R is the terminating resistance. Connect the terminating resistance (110 Ω ) between terminals RDA and RDB . For details see section 2.3. *2 Connect terminal FG to earth terminal of the PC main body grounded with resistance of 100 Ω or less. However, as for the computer link unit of the A series PC, see the manual of the computer link unit.
Classification of terminating resistances In this product, two sets of terminal end resistances (330 Ω ✕ 2, 110 Ω ✕ 1) are packaged, and the terminating resistances to be connected differ as shown below depending on the circuit being used.
FX 0N FX, FX 2C The communication format of the PC is set using special D8120. Operating ambient temperature Humidity no condensation Shock resistance Noise immunity Dielectric withstand voltage Insul.
X0000 ~ X0177 Y0000 ~ Y0177 M0000 ~ M0511 S0000 ~ S0127 M0000 ~ M8254 TS000 ~ TS063 CS000 ~ CS031 CS235 ~ CS254 TN000 ~ TN063 CN000 ~ CN031 CN235 ~ CN254 D0000 ~ D0255 D1000 ~ D2499 D8000 ~ D8255 ( ) .
In case of trouble, check the following points, and remedy according to the troubleshooting guide in the 485PC- IF manual. (1) Power LED Lit Otherwise (2) As for SD LED, RD LED, check and remedy according to the troubleshooting guide in the 485PC-IF manual.
Prior to start of operation, follow the procedure below. As for detail of procedure, see the 485PC-IF manual. 6 Determine system configuration Setting of transfer specification (D8120) Setting of stat.
Guidelines for the safety of the user and protection of the FX-485ADP, FX 0N -485ADP communication adapter JY992D53201C Effective AUG. 1997 Specifications are subject to change without notice.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Mitsubishi Electronics FX-485ADP c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Mitsubishi Electronics FX-485ADP - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Mitsubishi Electronics FX-485ADP, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Mitsubishi Electronics FX-485ADP va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Mitsubishi Electronics FX-485ADP, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Mitsubishi Electronics FX-485ADP.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Mitsubishi Electronics FX-485ADP. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Mitsubishi Electronics FX-485ADP ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.