Manuel d'utilisation / d'entretien du produit E1000RM1U du fabricant Minuteman UPS
Aller à la page of 28
User's Manual Enterprise 1U Rackmount Series.
1 © Copyright Para Systems, Inc., 2005 Enterprise 1U Rackmount Series User's Manual 1 . Introduction 2 2 . Controls and Indicators 6 3. Installation 8 4. Operation 12 5 . T roubleshooting 15 6 . Replacing the Battery 16 7 . Obtaining Service 19 8 .
2 IMPORT ANT SAFETY INSTRUCTIONS SA VE THESE INSTRUCTIONS ! English Thank you for purchasing a MINUTEMAN power protection product. It has been designed and manufactured to provide many years of trouble free service.
3 W ARNING: Risk of Electrical Shock. Hazardous live parts inside these power supplies are energized from the battery even when the AC input is disconnected. CAUTION! T o de-energize the outputs of the UPS: 1. If the UPS is on press and release the On/Off/T est button.
4 English After removing your MINUTEMAN UPS from its carton, it should be inspected for damage that may have occurred in shipping. Immediately notify the carrier and place of purchase if any damage is found. Warranty claims for damage caused by the carrier will not be honored.
5 English Para Systems Life Support Policy As a general policy , Para Systems Inc. (Para Systems) does not recommend the use of any of its products in life support applications where failure or mal- f.
6 English The AC normal (green) LED illuminates in a steady state when the UPS is on and operating in the AC normal mode. The AC normal LED will extinguish when operating in the Battery mode. The On-Battery (green) LED illuminates in a steady state when the UPS is operating in the Battery mode.
7 English The Load Level Bar Graph operates as follows: LED #10: >10% load (green/red/yellow) LED will be green and illu- minated when there is at least 10% of the rated capacity . LED #30: >30% load (green/yellow) LED will be green and illumi- nated when there is at least 30% of the rated capacity .
8 English INST ALLA TION PLACEMENT The Enterprise 1U Rackmount Series is intended to be install in a temperature controlled environment that is free of conductive contaminants. Select a loca- tion which will provide good air circulation for the UPS at all times.
9 English INST ALLA TION Be sure to read the installation placement and all the cautions before installing the UPS. Place the UPS in the final desired location and complete the rest of the installation procedure. These UPSs are shipped with the internal batteries disconnected.
10 English Installing the UPS in a 4-post rack USE CAUTION: The UPS is heavy . Use the appropriate number of personnel when installing the UPS. 1. Install the rails in the 4-post rack. (FIG . 1) 2. Install the rack ears on the UPS. (FIG . 2) 3. Align the cleats with the rails and slide the UPS into the rails.
11 English CHARGING THE BA TTER Y The Enterprise 1U Rackmount Series UPS will charge the internal batteries whenever the UPS is connected to an AC source.
12 English SYSTEM OVERVIEW This Line-Interactive 1U Rackmount model UPS protects internetworking and telecommunications equipment from blackouts, brownouts, overvoltages, and surges. The A VR function continuously corrects the volt ages, in-between the brownout and overvoltage transfer points (85 - 150V AC), to a safe usable level.
13 English ALARMS ON BA TTER Y When the UPS is operating on the batteries, the On-Battery LED will illuminate and the audible alarm will sound once every ten-seconds. The alarm will stop once the UPS returns to the AC normal mode. LOW BA TTER Y W ARNING The UPS will sound two beeps every five-seconds when the battery reserve runs low .
14 English COMMUNICA TIONS PORTS (RS232 and USB) The RS232 communication port is a standard DB9 female with both RS232 and simulated contact closure cap ability . The Enterprise 1U Rackmount Series UPS will poll the port and activate the port for RS232 or contact closure in accordance with the type of cable it finds connected to the port.
15 English Possible Cause Symptom What T o Do Press and release the On/Off/ T est button to start UPS On/Off/T est button not pushed UPS will not turn on Reset circuit breaker by pressing the plunger back in.
16 English REPLACING THE BA TTER Y W ARNING! This Uninterruptible Power Supply contains potentially hazardous voltages. Do not attempt to disassemble the UPS beyond the battery replacement procedure. This UPS contains no user serviceable parts. Repairs and Battery replacement must be performed by QUALIFIED SERVICE PERSONNEL ONL Y .
17 English BA TTER Y REPLACEMENT PROCEDURE PLEASE READ THE CAUTIONS AND W ARNINGS BEFORE A TTEMPTING TO REPLACE THE BA TTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system.
18 English 8. Remove the four retaining screws for the battery ret aining bracket. (FIG . 3) 9. Remove the battery retaining bracket. (FIG . 3) 10. Grasp the battery tray and gently pull the battery tray out far enough to get to the battery connectors (red and black).
19 English IF THE UPS REQUIRES SERVICE 1.Use the TROUBLESHOOTING section to eliminate obvious causes. 2.V erify there are no circuit breakers tripped. A tripped circuit breaker is the most common problem.
20 English Default 120V AC User selectable 120/127V AC 700V A 490W 1500V A 900W 1000V A 700W Protection W aveform T ype Over-Current, Short-Circuit Protected and Latching Shutdown Sine Wave Frequency 50/60Hz, +/-0.
21 English BA TTER Y SYSTEM T ypical Recharge T ime T ypical Battery Life Battery Quantity/Rating 3-5 years, depending on discharge cycles and ambient temp 4-6V9Ah 4-6V9Ah 8 hours from total discharge.
22 English (These items may require optional software or hardware) Function Factory Default Description User Choices Set inverter output voltage Shut- down T ype Set audible alarm state Enable/ Disabl.
23 English Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and operated within specified conditions, against faulty materials or workmanship for a period of three years from the date of purchase.
24 English EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL P ARA SYSTEMS BE LIABLE FOR DIRECT , INDIRECT , SPECIAL, INCIDENT AL, OR CONSEQUEN- TIAL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT , EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.
25 English DECLARA TION OF CONFORMITY Application of Council Directive(s): 89/336/EEC, 73/23/EEC S tandard(s) to which Conformity is declared: Manufacturer’s Name: Para Systems, Inc.
26 English Notes:.
Para Systems, Inc. 1455 Lemay Dr . Carrollton, TX 75007 Phone: 1-972-446-7363 Fax: 1-972-446-901 1 Internet: minutemanups.com UPS Sizing: sizemyups.com PN - 34000256 Rev .
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Minuteman UPS E1000RM1U c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Minuteman UPS E1000RM1U - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Minuteman UPS E1000RM1U, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Minuteman UPS E1000RM1U va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Minuteman UPS E1000RM1U, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Minuteman UPS E1000RM1U.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Minuteman UPS E1000RM1U. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Minuteman UPS E1000RM1U ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.