Manuel d'utilisation / d'entretien du produit PR0091 du fabricant Mercury
Aller à la page of 21
Mercur y 6-5 Stat – Installation & User Guide Mercury 6-5 5 Channel Thermost at Inst allation Guide For Product: - PR0091 En sur e t ha t a ll po wer is sw it ched of f b efore inst a lling or ma int a ini n g this product Revision 1.
Mercur y 6-5 Stat – Installation & User Guide Table of Contents: THE MERCURY RANGE .................................................................................................................................... 3 Description ...............
Mercur y 6-5 Stat – Installation & User Guide The Mer cury Rang e From Resource Data Managemen t This documentation refers to the Mercury 6-5 - 5 Channel Thermostat Description The Mercury 5 Channel Thermostat ha s 5 thermostat f unctions.
Mercur y 6-5 Stat – Installation & User Guide Connections All connections are ma de to the back of the controller. The dia gram below shows the connection detail. Inputs and outputs are assigne d according to the chosen config uration. See Specification for further details on connectio ns.
Mercur y 6-5 Stat – Installation & User Guide Setting up the controller Access to the controller ca n be achieved several ways • Through the front mounted buttons • Direct access by PC or palm top into the rear co mms port. This requires a software package available on the RDM website • Through the RDM Data Directo r or Data Manager.
Mercur y 6-5 Stat – Installation & User Guide Recommended set-up method If you are not connecting to a network and want to set up the co ntroller through the buttons we recommend you use the following order from the function menu. rtc. Real time clock (This will automa tically synchronise on netw ork systems) a.
Mercur y 6-5 Stat – Installation & User Guide Parameter Tables: Parameter table for 5 Channel Thermosta t En sur e t ha t a ll po wer is Number Parameter Range o C ( o F ) Step Units Default P-01 Stat1 Temp Cut-In -49 to 30 o C (-56.2 to 86) 0.1 Deg 15.
Mercur y 6-5 Stat – Installation & User Guide Parameter table for 5 Channe l Thermostat Continued....... Number Parameter Range o C ( o F ) Step Units Default P-31 Stat4 Temp Cut-In -49 to 30 o C (-56.2 to 86) 0.1 Deg 15.0 P-32 Stat4 Diff 0 to 10 o C (32 to 50) 0.
Mercur y 6-5 Stat – Installation & User Guide Parameter table for 5 Channe l Thermostat Continued....... Number Parameter Range Step Units Default P79 Tuesday On Time 1 00:00 to 23:59 00:01 hh:m.
Mercur y 6-5 Stat – Installation & User Guide Network Configuration The final section to set-up is the network addres s. In all instance s, this mu st be done before the controller is plugged into the site network. The controllers have an aut o-initialise function, whic h will automatically log the device onto the site network.
Mercur y 6-5 Stat – Installation & User Guide Over-ride Operation The 5 Channel Thermostat can op erate either from its in ternal channel time settings or from a network Data Manager GP Timer channe l (P70 sets the mode either loca l or remo te).
Mercur y 6-5 Stat – Installation & User Guide Normal Operation During normal operation, the controlle r will display "on". If the 5 Channel Thermostat is on a network and on- line, the green network LED will be on . If any alarms are generated the r ed LED will light.
Mercur y 6-5 Stat – Installation & User Guide Thermostat Cooling/Heating Operation The diagrams below outline the operatio n of a channel when it is configured fo r he ating or cooling applications. In this instance the 5 Channel Thermo stat’s local timer is on.
Mercur y 6-5 Stat – Installation & User Guide Viewing Apart from setting up the controller, you can also view the status of the inputs a nd outputs. 1. IO. View Inputs / Outputs and States a. From the function menu, select “IO”, press enter b.
Mercur y 6-5 Stat – Installation & User Guide Network Alarms The table below shows the text and associated type numbe r that is se nt to the sy stem "front end".
Mercur y 6-5 Stat – Installation & User Guide Specification General Power requirements: Supply Voltage Range: 100 - 240 Vac ±10% Supply Frequency: 50 - 60 Hz ±10% Maximum supply current: <1 Amp (With no relay loads) Typical supply current: <0.
Mercur y 6-5 Stat – Installation & User Guide Inputs: Input resistance: 3.01K Ohms (for PTC or NTC type probes) Input type PT1000 NTC2000 N T C 2 k 2 5 Comms: RS232 with flow control En sur e t ha t a ll po wer is sw it ched of f b efore inst a lling or ma int a ini n g this product Revision 1.
Mercur y 6-5 Stat – Installation & User Guide Installation: Panel Cut-out: 72mm 93mm 34mm 17mm 2 holes: 3.5mm dia. Fixing: The controller can be fixed either by 2 X M3 screws fr om the re ar or by the plastic retaining de vice (PR0329), obtainable from RDM.
Mercur y 6-5 Stat – Installation & User Guide Wiring: Relay 4 and 5 N/O are fed from the supply input ! Note: Suitable mechanical restraints on the wi ring to the controller may be required; depen dant on cable types, to prevent undue stress or distorti on on the controlle r connectors.
Mercur y 6-5 Stat – Installation & User Guide Fuse: The host equipment must provide a suitable exter nal over-curre nt protection d evice such as: - Fuse: 6.
Mercur y 6-5 Stat – Installation & User Guide Revision History Revision Date Change s 1.0 27/10/2006 First Issue 1.1 01/03/2007 General Tidy Up 1.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Mercury PR0091 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Mercury PR0091 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Mercury PR0091, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Mercury PR0091 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Mercury PR0091, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Mercury PR0091.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Mercury PR0091. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Mercury PR0091 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.