ITT Whirlpool Bath Pump (BPHV)

52 pages·2.1 MB·Pompe à eau·PDF·EN
ITT Whirlpool Bath Pump (BPHV)
Table des matières 80 sections BPHV · ITT · Commercial Water · Variable Speed Water Booster with Vertical Multistage Pump and Fused Disconnect · … AfficherMasquer
BPHVp.1ITTp.1Commercial Waterp.1Variable Speed Water Booster with Vertical Multistage Pump and Fused Disconnectp.1C US UL ®p.1Engineered for lifep.1CONTENTSp.2Selection Chart… …………………………………………………………………………………………… 3p.2Main Components…………………………………………………………………………………………… 4p.2Part Numbering……………………………………………………………………………………………… 5p.2Markets and Applications………………………………………………………………………………… 6-8p.2Hydrovar Specifications / Listings………………………………………………………………………… 9-11p.2Multi-Pump Example………………………………………………………………………………………… 12p.2Operation / Selecting… …………………………………………………………………………………… 13p.2Fused Disconnect… ………………………………………………………………………………………… 15p.2Motor Data… ……………………………………………………………………………………………… 17p.2Variable Speed Curves… ……………………………………………………………………………… 19-36p.2Technical Data - Pump Hydraulics… ………………………………………………………………… 37-40p.2Dimensions / Weights… ……………………………………………………………………………… 41-46p.2Technical Data - References… ………………………………………………………………………… 48-49p.2PHV SERIES SELECTION CHART (PACKAGED HYDROVAR) HYDRAULIC PERFORMANCE RANGE AT 60 Hzp.3MAIN COMPONENTS of PHV Series constant pressure variable speed systemp.4“QCZJ7 Packaged Pumping System”p.4PART NUMBERING / IDENTIFICATION CODES — PHV SERIESp.5PHV 02 M 2 1 B E 0 Pp.5HV M 3 4 10p.5MARKETS AND APPLICATIONSp.6Booster MARKETS SERVED Sets MUNICIPAL, COMMERCIAL, INDUSTRIALp.6PHV Seriesp.6SPECIFICATIONSp.6MARKETS AND APPLICATIONS (continued)p.7MUNICIPAL, AGRICULTURAL, LIGHT INDUSTRY, WATER TREATMENT, HEATING AND AIR CONDITIONINGp.8MAIN CHARACTERISTICS OF FREQUENCY CONVERTERS USED IN THE PHV BOOSTER SETSp.9CHARACTERISTICS OF THE ELECTRIC PUMPS USED IN PHV SERIES BOOSTER PACKAGEp.101, 2, 3 AND 4 SSV VERTICAL MULTI-STAGE PUMPSp.10SV33 AND 46 MULTI-STAGE PUMPSp.10REFERENCE STANDARDSp.10HYDROVAR VERSIONSp.11INTRODUCTIONp.11STANDARD OPTIONAL FEATURES VERSIONSp.11CASCADE SERIAL (MASTER + BASIC)p.11APPLICATION EXAMPLE – MULTI-PUMP “CASCADE”p.12MASTER INVERTERp.12RS 485 CONNECTIONp.12BASIC INVERTERp.12OPERATION DESCRIPTIONp.13SETS WITH VARIABLE-SPEED MOTORS AND PRESSURE TRANSDUCER CONTROLp.13PSp.13OPERATING CHARACTERISTICS AND LIMITSp.13NOISE EMISSION LEVELSp.1360 Hz 3500 RPM LpA (dB ±4)p.13SELECTING A SETp.14CALCULATING THE FLOW RATEp.14CALCULATING THE HEADp.14SELECTING A BOOSTER SETp.14TANKp.14FUSED DISCONNECT BOX:p.15CUSTOMER SUPPLIEDp.15DISCONNECT FUSE BLOCKp.15HYDROVARp.15SINGLEp.1512 AWGp.15U1p.15U2p.15PHASEp.15MTR MOTORp.15VOLTAGEp.15W1p.15W2p.15GNDp.15GND PEp.1516 AWG GNDp.15THREE PHASEp.15L2 12 AWGp.15Hydrovar VFD Motorp.16ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series)p.16MOTOR DATAp.173500 RPM, 60 Hzp.17NOTES:p.17PERFORMANCE WITH VARYING SPEED FOR CENTRIFUGAL PUMPSp.18
Page 1 of the ITT Whirlpool Bath Pump (BPHV) user manual — C US UL ®
Page 1 · cliquer pour agrandir
Page 1

BPHV

ITT

Commercial Water

Variable Speed Water Booster with Vertical Multistage Pump and Fused Disconnect

ITT Whirlpool Bath Pump (BPHV) — BPHV diagram (page 1)
Fig. 1

C US UL ®

Engineered for life

Listed

Page 2 of the ITT Whirlpool Bath Pump (BPHV) user manual — Table des matières
Page 2 · Table des matières
Table des matières

Table des matières

BPHVp.1ITTp.1Commercial Waterp.1Variable Speed Water Booster with Vertical Multistage Pump and Fused Disconnectp.1C US UL ®p.1Engineered for lifep.1CONTENTSp.2Selection Chart… …………………………………………………………………………………………… 3p.2Main Components…………………………………………………………………………………………… 4p.2Part Numbering……………………………………………………………………………………………… 5p.2Markets and Applications………………………………………………………………………………… 6-8p.2Hydrovar Specifications / Listings………………………………………………………………………… 9-11p.2Multi-Pump Example………………………………………………………………………………………… 12p.2Operation / Selecting… …………………………………………………………………………………… 13p.2Fused Disconnect… ………………………………………………………………………………………… 15p.2Motor Data… ……………………………………………………………………………………………… 17p.2Variable Speed Curves… ……………………………………………………………………………… 19-36p.2Technical Data - Pump Hydraulics… ………………………………………………………………… 37-40p.2Dimensions / Weights… ……………………………………………………………………………… 41-46p.2Technical Data - References… ………………………………………………………………………… 48-49p.2PHV SERIES SELECTION CHART (PACKAGED HYDROVAR) HYDRAULIC PERFORMANCE RANGE AT 60 Hzp.3MAIN COMPONENTS of PHV Series constant pressure variable speed systemp.4“QCZJ7 Packaged Pumping System”p.4PART NUMBERING / IDENTIFICATION CODES — PHV SERIESp.5PHV 02 M 2 1 B E 0 Pp.5HV M 3 4 10p.5MARKETS AND APPLICATIONSp.6Booster MARKETS SERVED Sets MUNICIPAL, COMMERCIAL, INDUSTRIALp.6PHV Seriesp.6SPECIFICATIONSp.6MARKETS AND APPLICATIONS (continued)p.7MUNICIPAL, AGRICULTURAL, LIGHT INDUSTRY, WATER TREATMENT, HEATING AND AIR CONDITIONINGp.8MAIN CHARACTERISTICS OF FREQUENCY CONVERTERS USED IN THE PHV BOOSTER SETSp.9CHARACTERISTICS OF THE ELECTRIC PUMPS USED IN PHV SERIES BOOSTER PACKAGEp.101, 2, 3 AND 4 SSV VERTICAL MULTI-STAGE PUMPSp.10SV33 AND 46 MULTI-STAGE PUMPSp.10REFERENCE STANDARDSp.10HYDROVAR VERSIONSp.11INTRODUCTIONp.11STANDARD OPTIONAL FEATURES VERSIONSp.11CASCADE SERIAL (MASTER + BASIC)p.11APPLICATION EXAMPLE – MULTI-PUMP “CASCADE”p.12MASTER INVERTERp.12RS 485 CONNECTIONp.12BASIC INVERTERp.12OPERATION DESCRIPTIONp.13SETS WITH VARIABLE-SPEED MOTORS AND PRESSURE TRANSDUCER CONTROLp.13PSp.13OPERATING CHARACTERISTICS AND LIMITSp.13NOISE EMISSION LEVELSp.1360 Hz 3500 RPM LpA (dB ±4)p.13SELECTING A SETp.14CALCULATING THE FLOW RATEp.14CALCULATING THE HEADp.14SELECTING A BOOSTER SETp.14TANKp.14FUSED DISCONNECT BOX:p.15CUSTOMER SUPPLIEDp.15DISCONNECT FUSE BLOCKp.15HYDROVARp.15SINGLEp.1512 AWGp.15U1p.15U2p.15PHASEp.15MTR MOTORp.15VOLTAGEp.15W1p.15W2p.15GNDp.15GND PEp.1516 AWG GNDp.15THREE PHASEp.15L2 12 AWGp.15Hydrovar VFD Motorp.16ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series)p.16MOTOR DATAp.173500 RPM, 60 Hzp.17NOTES:p.17PERFORMANCE WITH VARYING SPEED FOR CENTRIFUGAL PUMPSp.18
Page 3 of the ITT Whirlpool Bath Pump (BPHV) user manual — PHV SERIES SELECTION CHART (PACKAGED HYDROVAR) HYDRAULIC PERFORMANCE RANGE AT 60 Hz
Page 3 · cliquer pour agrandir
Page 3

PHV SERIES SELECTION CHART (PACKAGED HYDROVAR) HYDRAULIC PERFORMANCE RANGE AT 60 Hz

SSV Pump ModelStageHPFLOW 0 GPM57.51012.51517.520253035404550556065707580859095100105110 HEAD IN FEET 1SV62300279265247226200173142 1SV93442416395369338300259212 1SV155732692657615564505436359 2SV5221721120620019618918217415613511285 2SV83353340331325315304292279249215178136 2SV135586560546530513493473451400347286219 2SV167.5710687671654634611585559496426344254 3SV22124123122120118115111107103989285797163 3SV45245245244241237231217208197186173159143128 3SV77.5440435430423414403390377360343323303280256229 3SV910565559552544530518503484464441415388358326292 3SV1315817809801788772750730703673639603562519470419 4SV2514914914914914814614514314113913613313012612311811410910599 4SV47.5300300300300300295291286283277272265258250242233223213203191 4SV715530530530530523518512504497487478465451439423407388371352332
SSV Pump ModelStageHPFLOW 0 GPM406080100120140160180200220240260280300320 HEAD IN FEET 33SV1/051101101091081051029691847668 33SV2/27.51631631611571521441351241129781 33SV2/010222222220216210202193181168153137 33SV3/015334334330323314302288272253231206 46SV1/0101241211191171141101071039893888275696255 46SV2/015253249246242238232226220213204196186176165153140
ITT Whirlpool Bath Pump (BPHV) — PHV SERIES SELECTION CHART (PACKAGED HYDROVAR) HYDRAULIC PERFORMANCE RANGE AT 60 Hz diagram (page 3)
Fig. 2 · PHV SERIES SELECTION CHART (PACKAGED HYDROVAR) HYDRA…
Page 4 of the ITT Whirlpool Bath Pump (BPHV) user manual — “QCZJ7 Packaged Pumping System”
Page 4 · cliquer pour agrandir
Page 4
ITT Whirlpool Bath Pump (BPHV) — MAIN COMPONENTS of PHV Series constant pressure variable speed system diagram (page 4)
Fig. 3 · MAIN COMPONENTS of PHV Series constant pressure vari…

MAIN COMPONENTS of PHV Series constant pressure variable speed system

  • One multistage vertical pump , Goulds Pumps SSV series.
  • Hydrovar ® pump mounted variable speed drive
  • Pressure transducer for constant pressure control, connected to the Hydrovar drive.
  • NEMA 4X fused disconnect panel with corrosion resistant durable plastic; external on/off switch with lockout/tagout. Panel is bracket mounted directly to pump.
  • Electrical panel for control and protection, with casing made of plastic material, NEMA 4X, equipped with: – fast acting fuses. The panel is mounted on the electric pump

using a bracket.

The pump package comes pre-assembled and tested, complete with operating instructions and panel wiring diagram.

1. Vertical multi-stage stainless pump
2. TEFC standard NEMA 2-pole motor
3. NEMA 4X fused disconnect panel
4. ITT Hydrovar ® variable speed controller
5. cU L flexible liquid tight conduit/wiring
6. Pressure transducer (sensor) with cable

C US UL ®

7. Outdoor use

“QCZJ7 Packaged Pumping System”

Listed

Page 5 of the ITT Whirlpool Bath Pump (BPHV) user manual — HV M 3 4 10
Page 5 · cliquer pour agrandir
Page 5

PART NUMBERING / IDENTIFICATION CODES — PHV SERIES

PACKAGED HYDROVAR VARIABLE SPEED SSV PRODUCT LINE NUMBERING SYSTEM The various versions of the PHV line are identified by a product code number on the pump label. The number is also the catalog number for the package. The meaning of each digit in the product code is shown below.

PHV 02 M 2 1 B E 0 P

Option List in order shownP = Premium Efficiency F = Harmonic Filter T = 500 PSI Transducer

Reduced Stages (33-46SV Only) (can be 0, 1 or 2)*: 0 = 0 reduced 1 = 1 reduced 2 = 2 reduced

Number of Stages: A = 1 E = 5 J = 9 N = 13 S = 17 Z = 24 B = 2 F = 6 K = 10 P = 14 T = 18 C = 3 G = 7 L = 11 Q = 15 V = 20 D = 4 H = 8 M = 12 R = 16 X = 22

Flange TypeA = NPT Oval B = ANSI D = 316SS ANSI

Pump Model: 1 = 1SV 2 = 2SV 3 = 3SV 4 = 4SV 5 = 33SV 6 = 46SV 7 = 66SV 8 = 92SV

* Notes: Indicates num ber of reduced diameter impellers in the total staging. (2 would indicate 2 reduced diameter impellers.)

Voltage2 = 230V 4 = 460V
Hydrovar TypeM = Master Controller

HP Rating: 02 = 2 HP 03 = 3 HP 05 = 5 HP 07 = 7½ HP 10 = 10 HP 15 = 15 HP

PHV - Series (SSV & Hydrovar Package)

1. Not all combinations are available. 4. Fuse box contains class J or equal fast acting fuses. 2. Standard motor is Baldor TEFC, 3 Phase, TC frame. 5. Tank, piping and valves sold separately. 3. Standard Hydrovar VSD is master - capable of multi-control. 6. Includes 300 PSI transducer.

HYDROVAR VARIABLE SPEED CONTROLLERS Hydrovar variable speed drives are identified by the following code. The meaning of each digit in the product code is shown below.

HV M 3 4 10

Filter (optional)Standard = Blank Residential = B

HP Rating: 02 = 2 HP 03 = 3 HP 05 = 5 HP 07 = 7 HP 10 = 10 HP 15 = 15 HP

Voltage2 = 230V 4 = 460V
1. Not all combinations are available. 2. Includes drive, mounting hardware, 300 PSI tran sducer and conduit gland and plugs.
Phase1 = Single Phase 3 = Three Phase
TypeM = Master S = Single B = Basic

HV - Series

Page 6 of the ITT Whirlpool Bath Pump (BPHV) user manual — SPECIFICATIONS
Page 6 · cliquer pour agrandir
Page 6

MARKETS AND APPLICATIONS

Booster MARKETS SERVED Sets MUNICIPAL, COMMERCIAL, INDUSTRIAL

  • APPLICATIONS
  • Water network supply in condominiums, offices, hotels, shopping centers, factories, water treatment, process control.
  • Water supply to agricultural water networks (e.g. irrigation).
  • Variable flow / demand applications requiring constant pressure control.

PHV Series

ITT Whirlpool Bath Pump (BPHV) — PHV Series diagram (page 6)
Fig. 4 · PHV Series

SPECIFICATIONS

  • Flow rate up to 320 GPM.
  • Maximum HP: 15 HP.
  • Head up to 692’ TDH.
  • Soft motor start.
  • Supply voltage: 1Ø, 230V ± 10% up to 3 HP. 3Ø, 400V ± 10% for 3 HP – 15 HP.
  • Vertical design pump : - SV..T series (motor insulation class, F, TEFC enclosure).
  • Input Frequency: 50 or 60 Hz.
  • Maximum operating pressure: 360 PSI for sets with SV..T electric pumps.
  • External control voltage: 0-5 VDC; 0-10 VDC; 0-20 mA.
  • Maximum temperature of pumped liquid: 180° F.
  • Protection class - panel: NEMA 4X. - drive: NEMA 4 up to 15 HP. - outdoor use.
Page 7 of the ITT Whirlpool Bath Pump (BPHV) user manual — MARKETS AND APPLICATIONS (continued)
Page 7 · cliquer pour agrandir
Page 7

MARKETS AND APPLICATIONS (continued)

ITT Whirlpool Bath Pump (BPHV) — MARKETS AND APPLICATIONS (continued) diagram (page 7)
Fig. 5 · MARKETS AND APPLICATIONS (continued)
  • WATER SUPPLY AND PRESSURE BOOSTING
  • Pressure boosting in buildings, hotels, residential complexes
  • Pressure booster stations, supply of water networks
  • Booster packages
  • WATER TREATMENT
  • Ultrafiltration systems
  • Reverse osmosis systems
  • Water softeners and de-mineralization
  • Distillation systems
  • Filtration
  • LIGHT INDUSTRY
  • Washing and cleaning plants (washing and degreasing of mechanical parts, car and truck wash tunnels, washing of electronic industry circuits)
  • Commercial washers
  • Firefighting system pumps
ITT Whirlpool Bath Pump (BPHV) — MARKETS AND APPLICATIONS (continued) diagram (page 7)
Fig. 6 · MARKETS AND APPLICATIONS (continued)
  • IRRIGATION AND AGRICULTURE
  • Greenhouses
  • Humidifiers
  • Sprinkler irrigation
  • HEATING, VENTILATION AND AIR CONDITIONING (HVAC)
  • Cooling towers and systems
  • Temperature control systems
  • Refrigerators
  • Induction heating
  • Heat exchangers
  • Boilers
  • Water recirculation and heating
ITT Whirlpool Bath Pump (BPHV) — MARKETS AND APPLICATIONS (continued) diagram (page 7)
Fig. 7 · MARKETS AND APPLICATIONS (continued)
ITT Whirlpool Bath Pump (BPHV) — MARKETS AND APPLICATIONS (continued) diagram (page 7)
Fig. 8 · MARKETS AND APPLICATIONS (continued)
Page 8 of the ITT Whirlpool Bath Pump (BPHV) user manual — SPECIFICATIONS
Page 8 · cliquer pour agrandir
Page 8

MARKETS AND APPLICATIONS (continued)

MUNICIPAL, AGRICULTURAL, LIGHT INDUSTRY, WATER TREATMENT, HEATING AND AIR CONDITIONING

  • APPLICATIONS
  • Handling of water, free of suspended solids, in the municipal, industrial and agricultural markets
  • Pressure boosting and water supply systems
  • Fire fighting jockey pumps
  • Irrigation systems
  • Wash systems
  • Water treatment plants: reverse osmosis
  • Handling of moderately aggressive liquids, demineralized water, water and glycol, etc.
  • Circulation of hot and cold water for heating, cooling and conditioning systems
  • Boiler feed

SPECIFICATIONS

  • PUMP The SSV pump is a non-self priming vertical multistage pump coupled to a standard motor. The liquid end, located between the upper cover and the pump casing, is held in place by tie rods. The pump casing is available with different configurations and connection types.
  • Delivery: up to 600 GPM
  • Head: up to 1200 feet
  • Temperature of pumped liquid: -20ºF to 250ºF (-30ºC to 120ºC) standard version
  • Maximum operating pressure – with oval flanges: 230 PSI (15 bar) – with round flanges or Victaulic: 360 PSI (25 bar) – SV33, 46: 230, 360 or 575 PSI (16, 25 or 40 bar)* – SV 66, 92: 230 or 360 PSI (16 or 25 bar)*
  • Direction of rotation: clockwise looking at the pump from the top down (marked with an arrow on the adapter and on the coupling).
  • MOTOR
  • Standard NEMA TC Frame motors totally enclosed fan cooled.
  • Efficiency is 75.5% or higher, Class “F” insulation
  • 3500 RPM nominal
  • Standard voltage:
  • Single phase version: 115-208/230 V, 60 Hz up to 3 HP or 208-230 V for 5 HP
  • Three phase version, 2 pole: 208-230/460 V, 60 Hz up to 75 HP * Based on pump staging
Page 9 of the ITT Whirlpool Bath Pump (BPHV) user manual — MAIN CHARACTERISTICS OF FREQUENCY CONVERTERS USED IN THE PHV BOOSTER SETS
Page 9 · cliquer pour agrandir
Page 9

MAIN CHARACTERISTICS OF FREQUENCY CONVERTERS USED IN THE PHV BOOSTER SETS

The PHV series booster sets use a Hydrovar® variable frequency drive, an automatic device that adjusts the speed of the electric pump in order to maintain constant pressure in the system.

Converters with power up to 30 HP can be mounted directly on to the motor. Models with over 30 HP power, are designed for wall mounting only. The pressure is measured by a pressure transmitter which uses a standard 4..20 mA current signal. The system pressure value can be read on the converter’s display. A simple user interface allows you to set the desired pressure value for optimal adjustment, as well as to view the operating data, such as the hours of operation and any alarms triggered. Included diagnostic menu to view temperature, current and voltage values facilitates diagnostics and failure analisys. Indicator lights signal power status, pump running and malfunctions.

ITT Whirlpool Bath Pump (BPHV) — MAIN CHARACTERISTICS OF FREQUENCY CONVERTERS USED IN THE PHV BOOSTER SETS diagram (page 9)
Fig. 9

Modular Hydrovar, Bare Unit

A password is required to access sensitive settings that allow you to program the Hydrovar in order to adapt it to any control requirements, such as flow resistance compensation, external control, periodic testing and so on. When more than one pump is used, the converters exchange information with each other through an RS485 serial line which can connect up to 8 Hydrovar devices plus one external unit for remote control. The Pump-link and Pump-watcher dedicated systems, connected to the Hydrovar®, enable remote control through a traditional telephone line or mobile telephony. A serial port available as standard up to 15 HP allows you to control the Hydrovar® converters from a Modbus® field serial bus line.

ITT Whirlpool Bath Pump (BPHV) — MAIN CHARACTERISTICS OF FREQUENCY CONVERTERS USED IN THE PHV BOOSTER SETS diagram (page 9)
Fig. 10

The converter is equipped with two potential-free relays which can be used for remote signalling of pump running and malfunction status, plus a programmable voltage analogue output for signalling the frequency or pressure. Standard version with two sensor inputs for implementing of two actual values signals within one system (min/ max, difference) or for a second sensor for safety reasons. Specific digital inputs are used for protection against water failure, motor overtemperature, as well as for external enable signal and remote control. The converter also incorporates a dry running protection function via an adjustable minimum pressure threshold.

FCC Class A filter standard for Hydrovar three-phase power supply. E.g. Industrial areas, technical areas of any building fed from a dedicated transformer are examples of environment locations.

PHV Series Hydrovar with SSV Pump

FCC Class B filter standard for Hydrovar single-phase power supply. E.g. Houses, apartments, commercial premises or offices in a residential building are examples of environment locations.

Further information is available in the Hydrovar manual.

Page 10 of the ITT Whirlpool Bath Pump (BPHV) user manual — REFERENCE STANDARDS
Page 10 · cliquer pour agrandir
Page 10

CHARACTERISTICS OF THE ELECTRIC PUMPS USED IN PHV SERIES BOOSTER PACKAGE

1, 2, 3 AND 4 SSV VERTICAL MULTI-STAGE PUMPS

  • Multistage centrifugal vertical electric pumps. All metal parts in contact with pumped liquid are made of 304/316 stainless steel.
  • A version: round flanges, in-line discharge and suction ports, AISI 304
  • B version: ANSI flanges, in-line discharge and suction ports, AISI 316
  • Reduced axial thrusts enable the use of standard motors that are easily found on the market.
  • Standard Baldor, NEMA motors
  • Easy maintenance. No special tools required for assembly or disassembly.
  • ANSI/NSF 61 certified by CSA for potable drinking water.

SV33 AND 46 MULTI-STAGE PUMPS

  • Vertical multistage centrifugal pump with impellers, diffusers and outer sleeve made entirely of stainless steel, and with pump casing and upper head made of cast iron in the standard version.
  • High hydraulic efficiency for significant energy savings.
  • Innovative axial load compensation system on pumps with higher head. This ensures reduced axial thrusts and enables the use of standard motors that are easily found on the market.
  • Standard NEMA Baldor ® motors.
  • Mechanical seal can easily be replaced without disassembling the motor from the pump.
  • Mechanical sturdiness and easy maintenance. No special tools required for assembly or disassembly.
  • ANSI/NSF 61 certified by CSA for potable drinking water.

REFERENCE STANDARDS

  • cUL Listed as pumping packaged unit, 42UC
  • VFD (Hydrovar) UL recognized
  • Baldor motor UL recognized
  • Pumps meet ANSI/NSF 61 certification by CSA for potable drinking water
  • Pumps meet ANSI/UL778 standards
  • Control/disconnect meet UL508A standards
Page 11 of the ITT Whirlpool Bath Pump (BPHV) user manual — STANDARD OPTIONAL FEATURES VERSIONS
Page 11 · cliquer pour agrandir
Page 11

HYDROVAR VERSIONS

INTRODUCTION

The HYDROVAR Concept consists mechanically of two main parts, the Power Unit and the Control Card. In its basic configuration (consists only of the Power Unit) the HYDROVAR can be used as a “Basic Inverter” without the need of the Control Card. In that form the HYDROVAR can be used as a sequence pump in a multi pump system, with at least one master inverter. By extending this “Basic Inverter” with the additional Control Card and LCD display, the HYDROVAR “Master Unit” is able to work in different modes and can be extended by the implementation of different modules.

STANDARD OPTIONAL FEATURES VERSIONS

CASCADE SERIAL (MASTER + BASIC)

In this mode there are various possibilities to combine the different versions of the HYDROVAR. In general, each of the pumps is equipped with a HYDROVAR unit. Each pump of the system (extended up to 8 pumps) is equipped with a HYDROVAR unit (at least one “Master Inverter” and the others can be “Basic Inverters” in order to ensure a proper control of the system) which are connected via the serial interface. Minimum requirement: One “Master Inverter” and the others equipped with “Basic Inverters”.

The whole control is performed via the “Master Inverter” every time, but also an automatic change over of the lag pumps to achieve even operating hours is possible.

Following versions are available:

  • Power size 3 HP up to 15 HP motor mounted single phase and/or three phase power supply .

- PHV: one pump with wiring, fused disconnect, master Hydrovar drive, transducer, conduit.

Page 12 of the ITT Whirlpool Bath Pump (BPHV) user manual — RS 485 CONNECTION
Page 12 · cliquer pour agrandir
Page 12

APPLICATION EXAMPLE – MULTI-PUMP “CASCADE”

MASTER INVERTER

MASTER INVERTER

MASTER INVERTER

MASTER INVERTER

ITT Whirlpool Bath Pump (BPHV) — MASTER INVERTER diagram (page 12)
Fig. 11

RS 485 CONNECTION

With the “master” version of the Hyrdrovar, it is possible to connect up to 8 Hydrovar controller pumps together in parallel. Complete lead/lag and auto alternation.

MASTER INVERTER

BASIC INVERTER

BASIC INVERTER

BASIC INVERTER

ITT Whirlpool Bath Pump (BPHV) — MASTER INVERTER diagram (page 12)
Fig. 12

RS 485 CONNECTION

Reduction of overall cost for multi-pump system is possible using one “master” controller and several “basic” con trollers. The Hydrovar “master” will still control lead/lag, alternation.

Page 13 of the ITT Whirlpool Bath Pump (BPHV) user manual — 60 Hz 3500 RPM LpA (dB ±4)
Page 13 · cliquer pour agrandir
Page 13

OPERATION DESCRIPTION

SETS WITH VARIABLE-SPEED MOTORS AND PRESSURE TRANSDUCER CONTROL

The starting and stopping of the pumps are determined based on the pressure values set on the controller. Each frequency converter is connected to a pressure transducer. The controllers exchange information with each other and provide for cyclic changeover.

The figure shows the operating mode of a two-pump booster set (Typical Field Set).

  • On demand, water is drawn from the tank.
  • When the pressure drops belows the PS setting the first pump starts and the speed is adjusted to maintain a costant pressure as demand increases.
  • If the water consumption increases and the pump reaches maximum speed, the second pump starts and the speed is adjusted to maintain constant pressure.
  • When demand decreases, the speed is reduced until minimum speed is reached and one of the pumps are switched off.
  • If consumption keeps decreasing the pump slows down, fills the tank and stops at the pressure setting.

PS

OPERATING CHARACTERISTICS AND LIMITS

Type of pumped liquids Water containing no gas or corrosive and/or aggressive substances Fluid temperature Above 0° F to 180° F, Pressure transducer limited Ambient temperature Above 0° F to 104° F, VFD/Display, keep away from direct sun Maximum operating pressure 360 PSI (Pump without transducer) Minimum inlet pressure According to NPSH curve and losses, with a minimum margin of 0.5 m Maximum inlet pressure The inlet pressure added to the pressure of the pump at zero flow must be lower than the maximum operating pressure of the set (suction and discharge). Installation Indoors/outdoors, protected from the direct sun. Away from heat sources. Maximum elevation 3300 feet ASL. Maximum humidity 50% without condensation. Hourly starts Maximum 60 up to 10 HP. Above 10 HP and up to 50 HP, maximum 40 starts per hour. Variable speed drive starts. Sound emission See table

* Note: For higher temperature it is necessary to use special materials (only on request).

NOISE EMISSION LEVELS

60 Hz 3500 RPM LpA (dB ±4)

HP NEMA Motor Frame PHV 1 56 < 70 2 56 < 70 3 56 < 70 5 145 < 70 7½ 182-184 < 70 10 215 < 70 15 254 73 20 256 75 25 284 75 30 284 75

* Note: Adjusted from 50 Hz data, may vary.

Show 4 more labels / short text on this page
Pressure · Figure 3 Pmax · Duplex · Flow
Page 14 of the ITT Whirlpool Bath Pump (BPHV) user manual — TANK
Page 14 · cliquer pour agrandir
Page 14

SELECTING A SET

The first thing to do when selecting a package is to determine the quantity of water required and the pressure it must supply.

CALCULATING THE FLOW RATE

  • The quantity of water called water requirement depends on the type of users, e.g. homes, offices, schools, as well as their number. The theoretic requirement is the total amount of water required by all the users. In actual fact, since it is very unlikely that there should be a simultaneous demand by all the users, the real requirement is lower than the theoretic one.

CALCULATING THE HEAD

  • The pressure required depends on the type of user. A number of factors must be taken into account, including the height of the building , the suction conditions and the flow resistance in the pipes.

SELECTING A BOOSTER SET

  • According to the required flow rate and head values, it is possible to identify the most suitable type of electric pump. On two-pump sets the pumps normally act as back-up for one another . A single pump is normally sufficient to provide for average requirements, while in conditions of high demand the back up pump may be called in to assist. With the cyclic changeover function duty assignment is rotated to ensure both pumps remain active and with even running hours, so wear is uniform and the use factor is reduced for longer pump life. This system also ensures continuity of operation in case one of the pumps needs maintenance.The Hydrovar provides automatic lead/lag, alternation when programmed in multi-control and wired via RS485 communication terminals.

TANK

  • Frequent demand or small system losses determine pressure variations that may be compensated for by using a tank . Correct selection of a diaphragm tank reduces the number of pump starts and, if it is installed near the booster set, helps reduce the effect of water hammer, or fast acting flush valves.

The booster sets are ready for installation of diaphragm tanks directly on the delivery manifold, and additional tanks can be connected to the unused end of the manifold.

For peak performance, variable speed booster sets need smaller tanks compared to traditional systems. Generally speaking, a tank with a capacity of just 20% of the nominal capacity of a single pump, expressed in gallons per minute, is required. Example: If my pump is sized for 100 GPM, then we would size a 20 gallon (total capacity) diaphragm tank.

  • Pre-charge the tank with air, 10-15 PSI below your system pressure. Charge dry tank without water pressure or before installing in system.
Page 15 of the ITT Whirlpool Bath Pump (BPHV) user manual — CUSTOMER SUPPLIED
Page 15 · cliquer pour agrandir
Page 15

FUSED DISCONNECT BOX:

CUSTOMER SUPPLIED

DISCONNECT FUSE BLOCK

HYDROVAR

SINGLE

12 AWG

U1

U2

PHASE

MTR MOTOR

CUSTOMER SUPPLIED

VOLTAGE

12 AWG

W1

W2

GND

GND PE

16 AWG GND

CUSTOMER SUPPLIED

DISCONNECT FUSE BLOCK

HYDROVAR

12 AWG

THREE PHASE

U1

U2

L2 12 AWG

MTR MOTOR

CUSTOMER SUPPLIED

12 AWG

VOLTAGE

W1

W2

16 AWG GND

GND

GND PE

ITT Input HP / AMP Wire Tightening Fuse AMP Part Voltage Disconnect Voltage Disconnect Rating Range Torque Supplier Rating Number Rating Part Number

HFD512C1 230/1/60 OT25F3 2 HP / 25A #18-8AWG 7 IN/LB Bussman 20 KTK-R-20 600V

HFD512E1 230/1/60 OT40F3 3 HP / 40A #18-8AWG 7 IN/LB Bussman 30 KTK-R-30 600V

HFD534A1 460/3/60 OT16F3 3 HP / 16A #18-8AWG 7 IN/LB Bussman 10 KTK-R-10 600V

HFD534B1 460/3/60 OT16F3 3 HP / 16A #18-8AWG 7 IN/LB Bussman 15 KTK-R-15 600V

HFD534C1 460/3/60 OT25F3 3 HP / 25A #18-8AWG 7 IN/LB Bussman 20 KTK-R-20 600V

HFD534C2 460/3/60 OT25F3 3 HP / 25A #18-8AWG 7 IN/LB Bussman 20 KTK-R-20 600V

HFD534E2 460/3/60 OT40F3 3 HP / 40A #18-8AWG 7 IN/LB Bussman 30 KTK-R-30 600V

Page 16 of the ITT Whirlpool Bath Pump (BPHV) user manual — ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series)
Page 16 · cliquer pour agrandir
Page 16

SPECIFICATIONS

Hydrovar VFD Motor

HP Model * Power Supply (V) NEMA Class Install. Power Supply (V) HP 2 HVM1202 1x230 4 TEFC Motor 3x230 2 3 HVM1203 1x230 4 TEFC Motor 3x230 3 3 HVM3403 3x460 4 TEFC Motor 3x460 3 5 HVM3405 3x460 4 TEFC Motor 3x460 5 7½ HVM3407 3x460 4 TEFC Motor 3x460 7½ 10 HVM3410 3x460 4 TEFC Motor 3x460 10 15 HVM3415 3x460 4 TEFC Motor 3x460 15

* The new Hydrovar is available single-phase up to 3 HP and 3 HP through 15 HP, 460 volt.

ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series)

The GHV sets come with a fused disconnect on which are installed automatic line protection fast acting fuses for each drive. Class J, 600 volt.

Single-pump sets are supplied as standard with an electrical panel encased in NEMA 4X enclosure, with 2-pole or 3-pole (3 phase) up to 30 amps and featuring a main switch.

The fused disconnect is rated for UL508A.

ITT Whirlpool Bath Pump (BPHV) — ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series) diagram (page 16)
Fig. 13 · ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series)
ITT Whirlpool Bath Pump (BPHV) — ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series) diagram (page 16)
Fig. 14 · ELECTRICAL PANELS - PHV (Packaged Hydrovar ® Series)

Pump Disconnect Switch

Page 17 of the ITT Whirlpool Bath Pump (BPHV) user manual — NOTES:
Page 17 · cliquer pour agrandir
Page 17

MOTOR DATA

3500 RPM, 60 Hz

HP Phase Enclosure Nameplate NEMA Goulds FLA SFA LRA S.F. Efficiency Insulation Voltage Frame PN ¹ Class

1 3 TEFC 230/460 56C V06742 3.7-3.6/1.8 3.99-3.8/1.9 11 1.25 75.5 B

Prem. Eff. TEFC 230/460 56C V06742PE 2.8/1.4 3.12/1.56 12.1 1.25 84.5 B

1½ 3 TEFC 230/460 56C V07742 4.9-4.6/2.3 5.3-5.1/2.54 18.4 1.15 80 B

Prem. Eff. TEFC 230/460 56C V07742PE 4.0/2.0 4.5/2.25 20.1 1.15 85.5 B

2* 3 TEFC 208-230/460 56C V08742 6.2-5.8/2.9 7.2-6.52/3.26 22 1.15 80 B

Prem. Eff. TEFC 208-230/460 56C V08742PE 5/4.75-2.5 6.4-5.8/2.9 30 1.15 86.5 B

3* 3 TEFC 208-230/460 56C V09742 8.1-7.6/3.8 9.5-8.6/4.3 32.9 1.15 82.5 F

Prem. Eff. TEFC 208-230/460 184TC V09742PE 6.8/3.4 8.5-7.7/3.8 32 1.15 88.5 F

5* 3 TEFC 208-230/460 184TC V10742A 13.2-12/6 15-13.6/6.8 47 1.15 85.5 F

Prem. Eff. TEFC 208-230/460 184TC V10742APE 11.2/5.7 14.4-13/6.5 55 1.15 90.2 F

7½* 3 TEFC 208-230/460 184TC V11742A 18.5/17.4 21.7-19.6/9.8 94 1.15 88.5 F

Prem. Eff. TEFC 230/460 213TC V11742APE 17.8/8.9 20.2/10.1 75 1.15 90.2 F

10* 3 TEFC 208-230/460 215TC V12742 25-24/12 30.5-27.6/13.8 105 1.15 85.5 F

Prem. Eff. TEFC 230/460 215TC V12742PE 23.8/11.9 27.6/13.8 112 1.15 89.5 F

15* 3 TEFC 208-230/460 254TC V13742 35/17.5 43-39/19.5 165 1.15 86.5 F

Prem. Eff. TEFC 208-230/460 254TC V13742PE 34.4/17.2 43.8-39.6/19.8 112 1.15 91.7 F

20 3 TEFC 208-230/460 256TC V14742 46/23 59.3-53.6/26.8 160 1.15 89.5 F

Prem. Eff. TEFC 208-230/460 256TC V14742PE 46/23 57.5-52/26 201 1.15 92.4 F

25 3 TEFC 230/460 284TC V15742 59/29.5 74.8-67.6/33.8 182 1.15 88.5 F

Prem. Eff. TEFC 230/460 284TC V15742PE 56/28 69.9-63.2/31.6 236 1.15 93 F

30 3 TEFC 230/460 284TC V16742 68/34 86.7-78.4/39.2 225 1.15 91 F

Prem. Eff. TEFC 230/460 286TC V16742PE 66/33 83.8-75.8/37.9 281 1.15 93 F

40 3 TEFC 230/460 284TC V17742 90/45 103.2/51.6 322 1.15 90.2 F

Prem. Eff. TEFC 230/460 324TSC V17742PE 90/45 102.2/51.1 286 1.15 93.6 F

50 3 TEFC 230/460 326TSC V18742S 112/56 141.8-128.2/64.1 430 1.15 92.4 F

Prem. Eff. TEFC 230/460 326TSC V18742SPE 108/54 124.8/62.4 422 1.15 94.1 F

NOTES:

¹ Locked rotor amps are for high voltage only.

* Currently available on Packaged Hydrovar.

  • Motors are suitable for AQUAVAR ® Variable Speed Drive.

Above data is for Baldor® TC and TSC frame motors. Specifications subject to change without notice.

Page 18 of the ITT Whirlpool Bath Pump (BPHV) user manual — SIZING THE DIAPHRAGM TANK IN SYSTEMS WITH SPEED VARIATION
Page 18 · cliquer pour agrandir
Page 18

PERFORMANCE WITH VARYING SPEED FOR CENTRIFUGAL PUMPS

Fitting the electric pump with a variable speed drive makes it possible to vary the pump rotation speed, normally accor ding to the system pressure parameter. Variations in electric pump speed result in modified performances according to the equivalence relations, called affinity laws.

H

Q1 = n1 Q2 n2

n1

A

H1

H1 = n1 H2 n2

n2

H2

B

P1 = n1 P2 n2

Q1 Q2 Q

n1 = initial speed; n2= speed required. Q1 = initial flow rate; Q2= flow rate required. H1 = initial head; H2= head required. P1 = initial power; P2= power required

Frequency ratios can be used instead of speed in practical applications, keeping 30 Hz as the bottom limit.

Example : 2-pole 50 Hz electric pump n1 =2900 (point A) Flow rate (A) = 100 l/min; Head (A) = 50m By reducing the frequency to 30 Hz the speed is reduced to approx. n2 = 1740 rpm (point B) Flow rate (B) = 60 l/min; Head (B) = 18 m The power of the new work point B is cut to about 22% of the initial power.

SIZING THE DIAPHRAGM TANK IN SYSTEMS WITH SPEED VARIATION

Variable speed booster sets need smaller tanks compared to traditional systems. Generally speaking, a tank with a capacity of just 20% of the nominal capacity of a single pump, expressed in gallons per minute, is needed. The gradual starting of the pumps controlled by the drive reduces the need to limit the number of hourly starts; the main purpose of the tank is to compensate for small system losses, stabilize the pressure and make up for pressure variations caused by sudden demand (fast acting valves).

Make the following calculation: Set made up of three electric pumps, each with a maximum flow rate of 100 GPM, for a total capacity of 300 GPM. The volume required for the tank is 20 gallons. This is total capacity, not drawdown. Mount downstream of the check valves in discharge manifold.

Show 5 more labels / short text on this page
Head · Flow Rate · Head · Power · Flow
Page 19 of the ITT Whirlpool Bath Pump (BPHV) user manual — 6 (P2)
Page 19 · cliquer pour agrandir
Page 19

1SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 1SVB 6 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 22 US GPM 298 feet

FluidWater, pure Duty Chart: 3500 RPM

6 (P2)

Head

Page 20 of the ITT Whirlpool Bath Pump (BPHV) user manual — 9 (P2)
Page 20 · cliquer pour agrandir
Page 20

1SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 1SVB 9 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 22 US GPM 442 feet

FluidWater, pure Duty Chart: 3500 RPM

44.5%

44.5%

44.5%

9 (P2)

Head

Page 21 of the ITT Whirlpool Bath Pump (BPHV) user manual — 15 (P2)
Page 21 · cliquer pour agrandir
Page 21

1SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 1SVB 15 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 22 US GPM 733 feet

FluidWater, pure Duty Chart: 3500 RPM

600 640 680 720

44.5%

200 240 280 320 360 400

44.5%

44.5%

44.5%

15 (P2)

1.5 2 2.5 3

Head · 480 520 560 · 80 120 160

Page 22 of the ITT Whirlpool Bath Pump (BPHV) user manual — 5 (P2)
Page 22 · cliquer pour agrandir
Page 22

2SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 2SVB 5 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 40 US GPM 217 feet

FluidWater, pure Duty Chart: 3500 RPM Head

120 130 140 150 160 170 180 190

57.1%

0 10 20 30 40 50 60 70 80 90 100 110

57.1%

57.1%

0.6 0.8 1 1.2

5 (P2)

26 28 30 32 34 36 38 40 42

200 210 220

Page 23 of the ITT Whirlpool Bath Pump (BPHV) user manual — 5 (P2)
Page 23 · cliquer pour agrandir
Page 23

2SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 2SVB 8 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 40 US GPM 353 feet

FluidWater, pure Duty Chart: 3500 RPM Head

57.1%

57.1%

57.1%

5 (P2)

26 28 30 32 34 36 38 40 42

Show 4 more labels / short text on this page
300 320 · 240 260 280 · 160 180 · 120 140
Page 24 of the ITT Whirlpool Bath Pump (BPHV) user manual — 13 (P2)
Page 24 · cliquer pour agrandir
Page 24

2SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 2SVB 13 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 40 US GPM 586 feet

FluidWater, pure Duty Chart: 3500 RPM

57.1%

57.1%

57.1%

13 (P2)

26 28 30 32 34 36 38 40 42

Head

Page 25 of the ITT Whirlpool Bath Pump (BPHV) user manual — 7 (P2)
Page 25 · cliquer pour agrandir
Page 25

3SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 3SVB 7 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 78 US GPM 441 feet

FluidWater, pure Duty Chart: 3500 RPM Head

7 (P2)

28 32 36 40

44 48 52 56 60 64 68 72 76 80 84

Page 26 of the ITT Whirlpool Bath Pump (BPHV) user manual — 9 (P2)
Page 26 · cliquer pour agrandir
Page 26

3SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 3SVB 9 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 78 US GPM 565 feet

FluidWater, pure Duty Chart: 3500 RPM Head

9 (P2)

28 32 36 40

44 48 52 56 60 64 68 72 76 80 84

Page 27 of the ITT Whirlpool Bath Pump (BPHV) user manual — 13 (P2)
Page 27 · cliquer pour agrandir
Page 27

3SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 3SVB 13 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 78 US GPM 817 feet

FluidWater, pure Duty Chart: 3500 RPM Head

13 (P2)

28 32 36 40

44 48 52 56 60 64 68 72 76 80 84

Page 28 of the ITT Whirlpool Bath Pump (BPHV) user manual — 2 (P2)
Page 28 · cliquer pour agrandir
Page 28

4SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 4SVB 2 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 112 US GPM 148 feet

FluidWater, pure Duty Chart: 3500 RPM Head

3.5 4 4.5

2 (P2)

30 Hz 40 Hz

60 70 80 90

100 110

Page 29 of the ITT Whirlpool Bath Pump (BPHV) user manual — 4 (P2)
Page 29 · cliquer pour agrandir
Page 29

4SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 4SVB 4 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 112 US GPM 299 feet

FluidWater, pure Duty Chart: 3500 RPM Head

5 6 7 8

4 (P2)

30 Hz 40 Hz

60 70 80 90

100 110

Page 30 of the ITT Whirlpool Bath Pump (BPHV) user manual — 7 (P2)
Page 30 · cliquer pour agrandir
Page 30

4SV VARIABLE SPEED CURVE SSVB 304SS Multi-Stage Pumps MODEL: 4SVB 7 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 111 US GPM 526 feet

FluidWater, pure Duty Chart: 3500 RPM Head

7 (P2)

30 Hz 40 Hz

120 5 15 25 35 45 55 65 75 85 95 105 115

60 70 80 90

100 110

Page 31 of the ITT Whirlpool Bath Pump (BPHV) user manual — STAGE 1/1 (P2)
Page 31 · cliquer pour agrandir
Page 31

33SV VARIABLE SPEED CURVE SVB CI/316SS Multi-Stage Pumps MODEL: 33SVB 1/1 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 225 US GPM 83 feet

FluidWater, pure Duty Chart: 3500 RPM Head

STAGE 1/1

STAGE 1/1

2.5 3 3.5

STAGE 1/1 (P2)

140 160 180 200 220

Page 32 of the ITT Whirlpool Bath Pump (BPHV) user manual — STAGE 1 (P2)
Page 32 · cliquer pour agrandir
Page 32

33SV VARIABLE SPEED CURVE SVB CI/316SS Multi-Stage Pumps MODEL: 33SVB 1 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 224 US GPM 110 feet

FluidWater, pure Duty Chart: 3500 RPM Head

90 95 100 105 110 115

STAGE 1

70 75 80 85

76.7%

40 45 50 55 60 65

76.7%

76.7%

20 25 30 35

76.7%

STAGE 1

4 4.5 5

2.5 3 3.5

STAGE 1 (P2)

140 160 180 200 220

Page 33 of the ITT Whirlpool Bath Pump (BPHV) user manual — STAGE 2/1 (P2)
Page 33 · cliquer pour agrandir
Page 33

33SV VARIABLE SPEED CURVE SVB CI/316SS Multi-Stage Pumps MODEL: 33SVB 2/1 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 225 US GPM 191 feet

FluidWater, pure Duty Chart: 3500 RPM Head

120 130 140 150 160 170 180 190 200

STAGE 2/1

76.7%

76.7%

76.7%

76.7%

STAGE 2/1

6 7 8 9

STAGE 2/1 (P2)

140 160 180 200 220

100 110 · 40 50 60

Page 34 of the ITT Whirlpool Bath Pump (BPHV) user manual — STAGE 3/1
Page 34 · cliquer pour agrandir
Page 34

33SV VARIABLE SPEED CURVE SVB CI/316SS Multi-Stage Pumps MODEL: 33SVB 3/1 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 225 US GPM 310 feet

[FT] FluidWater, pure Duty Chart: 3500 RPM Head

STAGE 3/1

76.7%

76.7%

76.7%

76.7%

STAGE 3/1

STAGE 3/1 (P2)

140 160 180 200 220

10 12 14

Page 35 of the ITT Whirlpool Bath Pump (BPHV) user manual — STAGE 1/1
Page 35 · cliquer pour agrandir
Page 35

46SV VARIABLE SPEED CURVE SVB CI/316SS Multi-Stage Pumps MODEL: 46SVB 1/1 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 319 US GPM 100 feet

[FT] FluidWater, pure Duty Chart: 3500 RPM Head

85 90 95 100 105

STAGE 1/1

55 60 65 70 75 80

30 35 40 45 50

77.6%

77.6%

77.6%

30 Hz 40 Hz

77.6%

STAGE 1/1

STAGE 1/1 (P2)

2.5 3 3.5

30 Hz 40 Hz

140 160 180 200 220

240 260 280 300 320 340

Page 36 of the ITT Whirlpool Bath Pump (BPHV) user manual — STAGE 1/1
Page 36 · cliquer pour agrandir
Page 36

46SV VARIABLE SPEED CURVE SVB CI/316SS Multi-Stage Pumps MODEL: 46SVB 1 Stage

Hydraulic Data Maximum Flow Flow at Duty Point Maximum TDH TDH at Duty Point NPSHR 319 US GPM 123 feet

FluidWater, pure Duty Chart: 3500 RPM Head

110 115 120 125 130

STAGE 1

85 90 95 100 105

55 60 65 70 75 80

77.6%

77.6%

30 35 40 45 50

77.6%

77.6%

STAGE 1/1

STAGE 1 (P2)

140 160 180 200 220

240 260 280 300 320 340

Page 37 of the ITT Whirlpool Bath Pump (BPHV) user manual — TECHNICAL DATA – PUMP HYDRAULICS / MOTOR SIZING
Page 37 · cliquer pour agrandir
Page 37

TECHNICAL DATA – PUMP HYDRAULICS / MOTOR SIZING

1SV 3500 RPM Number of Maximum Motor HP for use Motor HP for use Shutoff Shutoff Stages HP With 1.15 SF With Hydrovar TDH TDH MAWP Motor Rotation Draw Motor (1.0 SF) (Feet) (Bar) 22 6.7 7.5 7.5 1100 32.8 20 6.1 7.5 7.5 1005 30.0 580 PSI (40 Bar) CCW 18 5.4 5 7.5 905 27.0 16 4.8 5 5 795 23.7 15 4.6 5 5 742 22.2 13 4 5 5 642 19.2 11 3.4 3 5 550 16.4 9 2.7 3 3 445 13.3 8 2.4 3 3 398 11.9 362 PSI (25 Bar) CW 7 2 2 2 350 10.4 6 1.8 2 2 300 9.0 5 1.5 1.5 1.5 250 7.5 4 1.1 1 1.5 200 6.0 3 0.9 3/4 1 142 4.2 2 0.6 1/2 3/4 100 3.0

2SV 3500 RPM Number of Maximum Motor HP for use Motor HP for use Shutoff Shutoff Stages HP With 1.15 SF With Hydrovar TDH TDH MAWP Motor Rotation Draw Motor (1.0 SF) (Feet) (Bar) 22 7.7 7.5 NA 950 28.4 20 6.8 7.5 7.5 860 25.7 580 PSI (40 Bar) CCW 18 6.2 7.5 7.5 760 22.7 16 5.3 5 7.5 726 21.7 15 4.9 5 5 680 20.3 13 4.6 5 5 595 17.8 11 4 5 5 500 14.9 9 3.3 3 5 407 12.2 8 2.9 3 3 360 10.7 7 2.4 3 3 315 9.4 362 PSI (25 Bar) CW 6 2.1 2 3 270 8.1 5 1.8 2 2 222 6.6 4 1.5 1.5 1.5 175 5.2 3 1.1 1 1.5 137 4.1 2 0.7 3/4 1 92 2.7

3SV 3500 RPM Number of Maximum Motor HP for use Motor HP for use Shutoff Shutoff Stages HP With 1.15 SF With Hydrovar TDH TDH MAWP Motor Rotation Draw Motor (1.0 SF) (Feet) (Bar) 16 17.6 20 20 1010 30.2 580 PSI (40 Bar) CCW 14 15 15 15 894 26.7 13 14 15 15 830 24.8 12 12.8 15 15 760 22.7 11 11.5 10 15 700 20.9 10 10.7 10 15 640 19.1 9 9.7 10 10 575 17.2 8 8.5 7.5 10 505 15.1 362 PSI (25 Bar) CW 7 7.5 7.5 7.5 450 13.4 6 6.5 7.5 7.5 380 11.3 5 5.4 5 7.5 320 9.6 4 4.3 5 5 250 7.5 3 3.3 3 5 190 5.7 2 2.2 2 3 128 3.8

Page 38 of the ITT Whirlpool Bath Pump (BPHV) user manual — TECHNICAL DATA – PUMP HYDRAULICS / MOTOR SIZING
Page 38 · cliquer pour agrandir
Page 38

TECHNICAL DATA – PUMP HYDRAULICS / MOTOR SIZING

4SV 3500 RPM Number of Maximum Motor HP for use Motor HP for use Shutoff Shutoff Stages HP With 1.15 SF With Hydrovar TDH TDH MAWP Motor Rotation Draw Motor (1.0 SF) (Feet) (Bar) 12 26.4 25 NA 930 27.8 580 PSI (40 Bar) CCW 10 21.6 20 25 780 23.3 9 19.2 20 20 700 20.9 8 16.9 15 20 620 18.5 7 14.9 15 15 540 16.1 6 12.9 15 15 460 13.7 362 PSI (25 Bar) CW 5 10.7 10 15 390 11.6 4 8.6 7.5 10 305 9.1 3 6.3 7.5 7.5 228 6.8 2 4.3 5 5 150 4.5

ITT Whirlpool Bath Pump (BPHV) — TECHNICAL DATA – PUMP HYDRAULICS / MOTOR SIZING diagram (page 38)
Fig. 15

33SV 3500 RPM # of Impellers / Maximum Motor HP for use Motor HP for use Shutoff Shutoff Casing / Sleeve Stages requiring Pump Flange # reduced HP with 1.15 SF with Hydrovar TDH TDH Pressure rating Thrust Balancing Rating Diameter Draw Motor (1.0 SF) (Feet) (Bar) (Standard Assy.) Piston 10 54.3 1125 34 10/2 52.8 60 1096 33 10/1 51.3 50 1066 32 9 48.8 1012 30 9/1 47.4 983 29 9/2 45.9 50 954 28 40 Bar (580 PSI) 8 43.4 900 27 8/1 41.9 871 26 Thrust Piston Class 250 / 300 8/2 40.5 40 842 25 Required 7 38 787 23 7/1 36.5 758 23 7/2 35 40 729 22 6 32.6 576 20 6/1 31.1 30 646 19 6/2 29.6 617 18 5 27.1 30 562 17 5/1 25.7 25 533 16 5/2 24.2 25 504 15 4 21.7 450 13 4/1 20.2 20 421 13 4/2 18.8 20 392 12 25 Bar (362 PSI) 3 16.3 337 10 1 3/1 14.7 15 310 9 3/2 13.2 15 281 8 Class 125 / 150 2 10.9 10 225 7 2/1 9.4 10 196 6 2/2 7.9 7.5 167 5 1 5.4 5 7.5 113 3 1/1 4 5 84 3

1 Pump assembly may be modified for 40 bar (580 psi) application – contact factory.

Page 39 of the ITT Whirlpool Bath Pump (BPHV) user manual — 66SV 3500 RPM
Page 39 · cliquer pour agrandir
Page 39

TECHNICAL DATA – PUMP HYDRAULICS / MOTOR SIZING

46SV 3500 RPM # of Impellers / Maximum Motor HP for use Motor HP for use Shutoff Shutoff Casing / Sleeve Stages requiring Pump Flange # reduced HP with 1.15 SF with Hydrovar TDH TDH Pressure rating Thrust Balancing Rating Diameter Draw Motor (1.0 SF) (Feet) (Bar) (Standard Assy.) Piston 10/2 77.8 1210 36.1 9 73.2 75 1137 33.9 9/1 71.5 1111 33.2 9/2 69.7 75 1085 32.4 8 65 1010 30.2 8/1 63.3 60 984 29.4 8/2 61.6 959 28.6 40 Bar (580 PSI) 7 56.9 884 26.4 7/1 55.2 60 858 25.6 7/2 53.4 50 832 24.8 Thrust Piston Class 250 / 300 6 48.8 758 22.6 Required 6/1 47.1 50 732 21.9 6/2 45.3 706 21.1 5 40.7 40 632 18.9 5/1 38.9 40 605 18.1 5/2 37.2 580 17.3 4 32.5 505 15.1 4/1 30.8 30 30 479 14.3 4/2 29 453 13.5 3 24.4 25 379 11.3 25 Bar (362 PSI) 3/1 22.7 20 25 353 10.5 1 3/2 20.9 327 9.8 2 16.3 20 253 7.6 Class 125 / 150 2/1 14/5 15 15 226 6.7 2/2 12.8 200 6.0 1 8.5 10 10 127 3.8 1/1 6.7 7.5 7.5 102 3.0

66SV 3500 RPM

# of Impellers / Maximum Motor HP for use Motor HP for use Shutoff Shutoff Casing / Sleeve Stages requiring Pump Flange # reduced HP with 1.15 SF with Hydrovar TDH TDH Pressure rating Thrust Balancing Rating Diameter Draw Motor (1.0 SF) (Feet) (Bar) (Standard Assy.) Piston 6 73.2 850 25.4 6/1 70.2 75 75 822 24.5 40 Bar (580 PSI) 6/2 67.2 796 23.8 5 61 60 707 21.1 5/1 58 60 681 20.3 Thrust Piston Class 250 / 300 5/2 55 655 19.6 Required 4 48.8 50 566 16.9 4/1 45.8 50 540 16.1 4/2 42.8 40 513 15.3 3 36.6 40 424 12.7 25 Bar (362 PSI) 3/1 33.6 30 398 11.9 1 3/2 30.6 30 372 11.1 2 24.4 25 25 283 8.4 Class 125 / 150 2/1 21.4 20 257 7.7 2/2 18.4 20 230 6.9 1 12.2 15 15 142 4.2 1/1 9.2 10 10 115 3.4

1 Pump assembly may be modified for 40 bar (580 psi) application – contact factory.

Page 40 of the ITT Whirlpool Bath Pump (BPHV) user manual — TECHNICAL DATA
Page 40 · cliquer pour agrandir
Page 40

TECHNICAL DATA

Maximum Inlet Pressure The following table shows the maximum permissible inlet pressure. However, the actual inlet pressure + pressure against a closed valve must always be lower than the maximum permissible operating pressure.

Pump Number of Stages Maximum Inlet Pressure 1SV 2-16 Stages 145 psi (10 bar) 17-22 Stages 215 psi (15 bar) 2SV 2-25 Stages 145 psi (10 bar) 16-22 Stages 215 psi (15 bar) 3SV 2-13 Stages 145 psi (10 bar) 14-16 Stages 215 psi (15 bar) 4SV 2-10 Stages 145 psi (10 bar) 11-12 Stages 215 psi (15 bar) 33SV 1-10 Stages 46SV 1-10 Stages 215 psi (15 bar) 66SV 1-6 Stages 92SV 1-6 Stages

Page 41 of the ITT Whirlpool Bath Pump (BPHV) user manual — HP L1
Page 41 · cliquer pour agrandir
Page 41

PHV — PACKAGED HYDROVAR SERIES — 1SVB

ITT Whirlpool Bath Pump (BPHV) — PHV — PACKAGED HYDROVAR SERIES — 1SVB diagram (page 41)
Fig. 16

Frame L2 DI Weights (lb.) Stage (3-Phase)

(max.)

HP L1

TEFC TEFC L6 L7 L8 MI TEFC Liquid TEFC Hydrovar Disconnect Total (ref.) End Box Weight

6 56C 2 16.63 12.06 20.90 9.87 5.73 7.19 27 51 93 9 3 19.56 13.44 6.70 23.83 30 56 10 5 101 15 182-4TC 5 25.44 15.43 29.71 11.15 6.87 8.50 37 85 137

Page 42 of the ITT Whirlpool Bath Pump (BPHV) user manual — HP L1
Page 42 · cliquer pour agrandir
Page 42

PHV — PACKAGED HYDROVAR SERIES — 2SVB

ITT Whirlpool Bath Pump (BPHV) — PHV — PACKAGED HYDROVAR SERIES — 2SVB diagram (page 42)
Fig. 17

Frame L2 DI Weights (lb.) Stage (3-Phase)

(max.)

HP L1

TEFC TEFC L6 L7 L8 MI TEFC Liquid TEFC Hydrovar Disconnect Total (ref.) End Box Weight

5 56C 2 15.63 12.06 19.90 9.87 5.75 7.19 25 51 91 8 3 18.56 13.88 6.70 22.83 5.50 30 56 10 5 100 13 182-4TC 5 23.50 15.44 27.77 11.15 6.88 8.50 35 85 135 16 26.44 30.71 40 140

Page 43 of the ITT Whirlpool Bath Pump (BPHV) user manual — HP L1
Page 43 · cliquer pour agrandir
Page 43

PHV — PACKAGED HYDROVAR SERIES — 3SVB

ITT Whirlpool Bath Pump (BPHV) — PHV — PACKAGED HYDROVAR SERIES — 3SVB diagram (page 43)
Fig. 18

Frame L2 DI Weights (lb.) Stage (3-Phase)

(max.) TEFC TEFC L6 L7 L8 MI TEFC Liquid TEFC Hydrovar Disconnect Total (ref.) End Box Weight 2 56C 2 15.75 12.06 20.02 9.87 5.75 7.19 33 51 99 4 182-4TC 3 18.75 15.44 23.02 6.88 8.50 37 85 137 7 7½ 23.25 6.70 27.52 11.15 45 124 10 5 184 9 215TC 10 28.88 15.50 33.15 8.06 10.25 47 151 221 13 254TC 15 33.38 16.56 37.65 9.25 10.83 66 250 339

HP L1

Page 44 of the ITT Whirlpool Bath Pump (BPHV) user manual — HP L1
Page 44 · cliquer pour agrandir
Page 44

PHV — PACKAGED HYDROVAR SERIES — 4SVB

ITT Whirlpool Bath Pump (BPHV) — PHV — PACKAGED HYDROVAR SERIES — 4SVB diagram (page 44)
Fig. 19

Frame L2 DI Weights (lb.) Stage (3-Phase)

(max.) TEFC TEFC L6 L7 L8 MI TEFC Liquid TEFC Hydrovar Disconnect Total (ref.) End Box Weight 2 182-4TC 5 15.75 15.44 20.02 6.88 8.50 33 85 133 4 7½ 18.75 6.70 23.02 11.15 39 124 10 5 178 7 254TC 15 24.44 16.56 28.71 9.25 10.31 52 250 325

HP L1

Page 45 of the ITT Whirlpool Bath Pump (BPHV) user manual — HP L1
Page 45 · cliquer pour agrandir
Page 45

PHV — PACKAGED HYDROVAR SERIES — 33SVB

ITT Whirlpool Bath Pump (BPHV) — PHV — PACKAGED HYDROVAR SERIES — 33SVB diagram (page 45)
Fig. 20

Frame L2 DI Weights (lb.) Stage (3-Phase)

(max.) TEFC TEFC L6 L7 L8 MI TEFC Liquid TEFC Hydrovar Disconnect Total (ref.) End Box Weight 1/1 182-4TC 5 20.62 15.44 13.95 6.88 8.50 132 85 10 232 1 6.70 12.27 5 2/1 215TC 10 23.58 15.50 16.91 8.06 10.25 143 151 18 317 3/1 254TC 15 26.54 16.56 19.87 9.25 10.31 152 250 425

HP L1

Page 46 of the ITT Whirlpool Bath Pump (BPHV) user manual — HP L1
Page 46 · cliquer pour agrandir
Page 46

PHV — PACKAGED HYDROVAR SERIES — 46SVB

ITT Whirlpool Bath Pump (BPHV) — PHV — PACKAGED HYDROVAR SERIES — 46SVB diagram (page 46)
Fig. 21

Frame L2 DI Weights (lb.) Stage (3-Phase)

(max.) TEFC TEFC L6 L7 L8 MI TEFC Liquid TEFC Hydrovar Disconnect Total (ref.) End Box Weight 1/1 182-4TC 7½ 22.19 15.44 15.52 6.88 8.50 147 124 10 286 1 215TC 10 15.50 6.70 12.27 8.06 10.25 151 5 313 2/1 254TC 15 25.19 16.56 18.52 9.25 10.31 158 250 18 431

HP L1

Page 47 of the ITT Whirlpool Bath Pump (BPHV) user manual — h pv is the vapor pressure of the liquid at the operating
Page 47 · cliquer pour agrandir
Page 47

NPSH

The maximum possible suction head for installation de pends on the value of the atmospheric pressure (i.e. the elevation above sea level at which the pump is installed) and the temperature of the liquid.

The minimum operating values that can be reached at the pump suction end are limited by the onset of cavitation.

Cavitation is the formation of vapor-filled cavities within liquids where the pressure is locally reduced to a critical value, or where the local pressure is equal to, or just below the vapor pressure of the liquid.

To help the user, with reference to water temperature (40ºF) and to the elevation above sea level, the following tables show the drop in hydraulic pressure head in relation to the elevation above sea level, and the suction loss in relation to temperature.

The vapor-filled cavities flow with the current and when they reach a higher pressure ares the vapor contained in the cavities condenses. The cavities collide, generating pressure waves that are transmitted to the walls. These, being subjected to stress cycles, gradually become de formed and yield due to fatigue. This phenomenon, char acterized by a metallic noise produced by the hammering on the pipe walls, is called incipient cavitation.

Water 68 104 140 176 194 230 248 Temperature (°C)

Suction -.7 2.3 6.6 16.4 24.3 50.5 70.5 Loss (ft)

Elevation Above 1600 3300 4900 6500 8200 9800 Sea Level (ft)

The damage caused by cavitation may be magnified by electrochemical corrosion and a local rise in temperature due to the plastic deformation of the walls. The materials that offer the highest resistance to heat and corrosion are alloy steels, especially austenitic steel. The conditions that trigger cavitation may be assessed by calculating the total net suction head, referred to in technical literature with the acronym NPSH (Net Positive Suction Head).

Suction 1.8 3.6 5.4 7.2 9.0 10.8 Loss (ft)

To reduce it to a minimum, especially in cases of high suc tion head (over 13 – 16 feet) or within the operating limits with high flow rates, we recommend using a suction line having a larger diameter than that of the pump’s suction port. It is always a good idea to position the pump as close as possible to the liquid to be pumped.

The NPSH represents the total energy (expressed in feet) of the liquid measured at suction under conditions of incipi ent cavitation, excluding the vapor pressure (expressed in feet) that the liquid has at the pump inlet.

To find the static height (hz) at which to install the ma chine under safe conditions, the following formula must be verified:

hp + hz ≥ (NPSHr + 2 feet) + hf + hpv where:

hp is the absolute pressure applied to the free liquid sur

face in the suction tank, expressed in feet of liquid; hp is the quotient between the barometric pressure and the specific weight of the liquid.

hz is the suction lift between the pump axis and the free

liquid surface in the suction tank, expressed in feet; hz is negative when the liquid level is lower than the pump axis.

hf is the flow resistance in the suction line and its acces

sories, such as: fittings, foot valve, gate valve, elbows, etc.

h pv is the vapor pressure of the liquid at the operating

temperature, expressed in feet of the liquid. hpv is the quotient between the Pv vapor pressure and the liquid‘s specific weight.

0.5 is the safety factor.

Page 48 of the ITT Whirlpool Bath Pump (BPHV) user manual — TECHNICAL DATA – WATER PROPERTY CHART
Page 48 · cliquer pour agrandir
Page 48

TECHNICAL DATA – WATER PROPERTY CHART

Temp ºF Temp ºC Specific Volume Specific Gravity Weight Vapor Pressure (Cubic ft/lb) @ 39.2ºF @ 60ºF @ 68ºF (lb/cubic ft) (psi Abs) 32 0.0 0.01602 1.000 1.001 1.002 62.42 0.088 35 1.7 0.01602 1.000 1.001 1.002 62.42 0.100 40 4.4 0.01602 1.000 1.001 1.002 62.42 0.122 50 10.0 0.01603 0.999 1.001 1.002 62.38 0.178 60 15.6 0.01604 0.999 1.000 1.001 62.34 0.256 70 21.1 0.01606 0.998 0.999 1.000 62.27 0.363 80 26.7 0.01608 0.996 0.998 0.999 62.19 0.507 90 32.2 0.0161 0.995 0.996 0.997 62.11 0.698 100 37.8 0.01613 0.993 0.994 0.995 62.00 0.949 120 48.9 0.0162 0.989 0.990 0.991 61.73 1.692 140 60.0 0.01629 0.983 0.985 0.986 61.39 2.889 160 71.1 0.01639 0.977 0.979 0.979 61.01 4.741 180 82.2 0.01651 0.970 0.972 0.973 60.57 7.510 200 93.3 0.01663 0.963 0.964 0.966 60.13 11.526 212 100.0 0.01672 0.958 0.959 0.960 59.81 14.696 220 104.4 0.01677 0.955 0.956 0.957 59.63 17.186 240 115.6 0.01692 0.947 0.948 0.949 59.10 24.97 260 126.7 0.01709 0.938 0.939 0.940 58.51 35.43 280 137.8 0.01726 0.928 0.929 0.930 58.00 49.20 300 148.9 0.01745 0.918 0.919 0.920 57.31 67.01 320 160.0 0.01756 0.908 0.909 0.910 56.66 89.66 340 171.1 0.01787 0.896 0.898 0.899 55.96 118.01 360 182.2 0.01811 0.885 0.886 0.887 55.22 153.04 380 193.3 0.01836 0.873 0.874 0.875 54.47 195.77 400 204.4 0.01864 0.859 0.860 0.862 53.65 247.31 420 215.6 0.01894 0.846 0.847 0.848 52.80 308.83 440 226.7 0.01926 0.832 0.833 0.834 51.92 381.59 460 237.8 0.0196 0.817 0.818 0.819 51.02 466.9 480 248.9 0.02 0.801 0.802 0.803 50.00 566.1 500 260.0 0.0204 0.785 0.786 0.787 49.02 680.8 520 271.1 0.0209 0.765 0.766 0.767 47.85 812.4 540 282.2 0.0215 0.746 0.747 0.748 46.51 962.5 560 293.3 0.0221 0.726 0.727 0.728 45.30 1133.1 580 304.4 0.0228 0.703 0.704 0.704 43.90 1325.8 600 315.6 0.0236 0.678 0.679 0.680 42.30 1542.9 620 326.7 0.0247 0.649 0.650 0.650 40.50 1786.6 640 337.8 0.026 0.617 0.618 0.618 38.50 2059.7 660 348.9 0.0278 0.577 0.577 0.578 36.00 2365.4 680 360.0 0.0305 0.525 0.526 0.527 32.80 2708.1 700 371.1 0.0369 0.434 0.435 0.435 27.10 3093.7

Page 49 of the ITT Whirlpool Bath Pump (BPHV) user manual — VOLUME
Page 49 · cliquer pour agrandir
Page 49

VOLUMETRIC CAPACITY

Litres Cubic metres Cubic feet Cubic feet Imp. gal. US gal. per minute per hour per hour per minute per minute per minute l/min m3/h ft3/h ft3/min Imp. gal/min Us gal./min

1,0000 0,0600 2,1189 0,0353 0,2200 0,2640

16,6670 1,0000 35,3147 0,5886 3,6660 4,4030

0,4720 0,0283 1,0000 0,0167 0,1040 0,1250

28,3170 1,6990 60,0000 1,0000 6,2290 7,4800

4,5460 0,2728 9,6326 0,1605 1,0000 1,2010

3,7850 0,2271 8,0209 0,1337 0,8330 1,0000

0,1100 0,0066 0,2339 0,0039 0,0240 0,0290

PRESSURE AND HEAD

Newtons per kilopascal bar Pound force metre millimetre square metre per square inch of water of mercury N/m2 kPa bar psi m H2O mm Hg

1,0000 0,0010 1 x 105 1,45 x 10-4 1,02 x 10-4 0,0075

1000,0000 1,0000 0,0100 0,1450 0,1020 7,5000

100000,0000 100,0000 1,0000 14,5000 10,2000 750,1000

98067,0000 98,0700 0,9810 14,2200 10,0000 735,6000

6895,0000 6,8950 0,0690 1,0000 0,7030 51,7200

2984,0000 2,9840 0,0300 0,4330 0,3050 22,4200

9789,0000 9,7890 0,0980 1,4200 1,0000 73,4200

133,3000 0,1330 0,0013 0,0190 0,0140 1,0000

3386,0000 3,3860 0,0338 0,4910 0,3450 25,4000

LENGTH

millimetre centimetre metre inch foot yard mm cm m in ft yd

1,0000 0,1000 0,0010 0,0394 0,0033 0,0011

10,0000 1,0000 0,0100 0,3937 0,0328 0,0109

1000,0000 100,0000 1,0000 39,3701 3,2808 1,0936

25,4000 2,5400 0,0254 1,0000 0,0833 0,0278

304,8000 30,4800 0,3048 12,0000 1,0000 0,3333

914,4000 91,4400 0,9144 36,0000 3,0000 1,0000

VOLUME

cubic metre litre millilitre imp. gallon US gallon cubic foot m3 litre ml imp. gal. US gal. ft3

1,0000 1000,0000 1 x 106 220,0000 264,2000 35,3147

0,0010 1,0000 1000,0000 0,2200 0,2642 0,0353

1 x 10-6 0,0010 1,0000 2,2 x 10-4 2,642 x 10-4 3,53 x 10-5

0,0045 4,5460 4546,0000 1,0000 1,2010 0,1605

0,0038 3,7850 3785,0000 0,8327 1,0000 0,1337

0,0283 28,3170 28317,0000 6,2288 7,4805 1,0000

Page 50 of the ITT Whirlpool Bath Pump (BPHV) user manual — NOTES
Page 50 · cliquer pour agrandir
Page 50

NOTES

Page 51 of the ITT Whirlpool Bath Pump (BPHV) user manual — NOTES
Page 51 · cliquer pour agrandir
Page 51

NOTES

Page 52 of the ITT Whirlpool Bath Pump (BPHV) user manual — Engineered for life ITT
Page 52 · cliquer pour agrandir
Page 52

ITT 2881 East Bayard Street, Seneca Falls, NY 13148 Phone: (315) 568-7123 • Fax: (315) 568-7973

Engineered for life ITT

www.goulds.com

Goulds Pumps and G&L are registered trademarks of ITT Corporation. ITT, the Engineered Blocks Symbol and Engineered for Life are registered trademarks of ITT Manufacturing Enterprises, Inc.

Copyright © 2009 ITT Corporation BPHV September, 2009 Printed in U.S.A. SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

Sources

Références et liens

Pages mentionnées dans ce manuel — fabricant, assistance et téléchargements.

Poser une question sur : ITT Whirlpool Bath Pump (BPHV)

Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Aucune question pour l'instant sur le ITT Whirlpool Bath Pump (BPHV)

Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.

Document d'origine

ITT Whirlpool Bath Pump (BPHV) manuel PDF

52 pages·2.1 MB·Pompe à eau·PDF
Cliquez sur une page ci-dessus pour l'ouvrir ici
Page 1 / …
100%
Chargement des pages…