Manuel d'utilisation / d'entretien du produit 380976 du fabricant HP (Hewlett-Packard)
Aller à la page of 20
User Guide 1 Φ /3 Φ 1000 Amp True RMS Power Clamp-On Model 380976.
380976 V3.1 6/ 08 2 Introduction Congratulations on your purchase of the Ex tech 380976 Po wer Clamp-On Meter. Th is device measures 1 Φ /3 Φ Power (True, Apparent, a nd Reactive), Horsepower, Phase Angle, True RMS Current/Voltage, Resistance, Capacitance, Frequency, & Temperature.
380976 V3.1 6/ 08 3 Warranty EXTECH INSTRUMENTS CORP ORATION warrants this instrument to be f ree of defects in parts and workmanship for one year from date of shipment (a six month limited warranty applies to sensors and cables).
380976 V3.1 6/ 08 4 Meter Description 1. Transformer Jaws 2. Jaw opening trigger 3. Data Hold & MX/MN button 4. Function Selector 5. Range button 6.
380976 V3.1 6/ 08 5 Measurements AC + DC Voltage Measuremen ts WA RN ING The maximum input is 600V. Do no attemp t voltage measurements above this limit. Exceeding this limit coul d cause electrical shoc k and damage to the meter. 1. Set the rotary switch to the ‘ V’ position.
380976 V3.1 6/ 08 6 AC Power Measurements 1 Φ KW, KVA, KVAR, Power Factor & Phase Angle Measurement 1. Set the rotary switch to the ‘KW/KVA’ position. 2. Insert the test leads to the meter as follows: Black to ‘COM’ and Red to ‘V’. 3.
380976 V3.1 6/ 08 7 3 Φ 3-Wire KW, HP, KVA, KVAR, Power Factor & Phase Angle Measurement 1. First, measure W RS(L1L2) (r efer to the diagram below). a. Set the rotary switch to the “ V ”. b. Press and hold the “ HOLD ” key wh ile setting the rotary switch to “KW/KVA”, the 3 φ 3W and W L12 symbols will appear.
380976 V3.1 6/ 08 8 3. The power clamp will process these tw o sets of data (W L12 , W L23 ), and show the result on the LCD. The W L123 symbol will be shown to indicate 3 φ 3W power.
380976 V3.1 6/ 08 9 NOTE Once a phase is selected as COM, user s can not change this selection in the subsequent measurement. For example, if S (or L2) phase is selected, S (or L2) phase is always connected to t he COM during measurement of W RS (or W L1L2 ) and W TS (or W L3L2 ) in 3 φ 3W unbalanced power.
380976 V3.1 6/ 08 10 3 Φ 4-Wire KW, HP, KVA, KVAR, Power Factor & Phase Angle Measurement 1. First, measure W R(L1) (refer to t he diagram below).
380976 V3.1 6/ 08 11 3. Third, measure W T(L3) (refer to the diagram th at follows the steps below) a. Disconnect the test probe from the phase where the jaws were clamped in the previous measurement. b. Connect the test probe of the V (red) terminal to the third phase (e.
380976 V3.1 6/ 08 12 4. The power clamp will proce ss these three sets of dat a (W L1, W L2 W L3 ) and show t he result o n the LCD. Th e WL 123 symbol will be shown t o indicate the 3 φ 4W pow er (refer t o diagr am). The 3 φ 4W power value in watts is now stored in the meter’s memory.
380976 V3.1 6/ 08 13 6. W 3 φ 4W = W R(L1) + W S( L2) W T(L3) KVA K W KVAR WW W 34 2 34 2 34 φφ φ =+ PF K W KVA W W W 34 34 34 φ φ φ = 7. Set the rotary switch to another position to exit this mode and clear the stored dat a. NOTE 1. The "+" sign printed on meter must face the power source for accurate measurement.
380976 V3.1 6/ 08 14 Capacitance Measureme nts 1. Fully discharge the capacitor under test before proceeding. 2. Insert the test leads into the input jacks. (Black to ‘COM’ and Red to ‘ ’). 3. Set the rotary switch to the ‘ ’ position. 4. Connect the red and black test leads to the capacitor.
380976 V3.1 6/ 08 15 Meter Control Keys HOLD - MX/MN Ke y Data Hold Function Press this key momentarily to put the meter into Data Hold mode ( HOLD will appear on the LCD). In this mode, the meter freezes the displayed reading. To exit the Data Hold mode, press the key again (the HOLD icon will switch off).
380976 V3.1 6/ 08 16 Automatic Sleep Mode and Battery Replacement The Meter is powered by a 9V battery. An AUTO SLEEP feature is included to prese rve battery life. Note: The Auto Power OFF feature is disabled when the meter is in the MIN/MAX mode Note: In the sleep mode the meter continues to dr aw a small amount of battery current.
380976 V3.1 6/ 08 17 Specifications General Specifications Display Dual Display; 4-digit, 10,000 count (0 to 9999) LCD Jaw Opening 1.6” (42mm) Max. Input limit Max. voltage between any terminal and ground: 6 00Vrms Sampling rate 2.5 times per second (Digital Display); Once every 6 seconds (KW, KVA, and KVAR) Auto Sleep After approx.
380976 V3.1 6/ 08 18 Measurement Specificatio ns Accuracy: ± ( % of rdg + number of digits) from 18 o C to 28 o C (64 o F to 82 o F) R.H. < 80% AC Current (50Hz to 400 Hz) True RMS Range Resolution Accuracy (% reading) Sensitivity Overload Protection 99.
380976 V3.1 6/ 08 19 M Ω (Resistance) Range Resolution Accuracy Overload Protection 9.999M Ω 1K Ω 99.99M Ω 10K Ω ±(5% + 10 d) 600V Capacitance Range Resolution Accuracy Overload Protection 10.000 μ F 1nF 100.00 μ F 10nF 1000.0 μ F 100nF ±(1.
380976 V3.1 6/ 08 20 Support line (781) 890-7440 Technical support: Extension 200; E-m ail: support@extech.com Repair & Returns: Ex tension 21 0; E-mail: repair@ex tech.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté HP (Hewlett-Packard) 380976 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du HP (Hewlett-Packard) 380976 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation HP (Hewlett-Packard) 380976, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le HP (Hewlett-Packard) 380976 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le HP (Hewlett-Packard) 380976, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du HP (Hewlett-Packard) 380976.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le HP (Hewlett-Packard) 380976. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei HP (Hewlett-Packard) 380976 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.