PRODUCT DATA 63-2689-05 Sp yder ® BA C n e t ® Pr ogrammab le Contr oller s PR ODUCT DESCRIPTION The PUB and PVB controllers are par t of the Sp yder f amily .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 2 OR DERING INFORMATION When purchasing replacement and moder nizat ion products from your TRADELINE® wholesaler or distributor , refer to the TRADELINE® Catalog or price sheets for complete ordering number .
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 3 63-2689—0 5 BEF ORE INSTALLATION The controller is av ailable in three models (see T able 1). Revie w the power , input, and output specifications on page 2 before installing the controller .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 4 Fig. 2. Damper with 90 de gree CW rotation to open. IMPORTANT Mount actuator flush with damper housing or add a spacer between the actuator mounting surface and damper box housing.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 5 63-2689—0 5 IMPORTANT Special prec autions must be taken for dampers that open in a CCW directi on. The actuator is shipped with its rotation direction set to CW to Op en, which applies to the damper direction in ste ps 1 and 2 above .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 6 P anel Mounting The controller enclosure is cons tructed of a plastic base plate and a plastic factor y-snap-on cover . NO TE: The controller is design ed so that the cover does not need to be removed from the base plate for either mounting or wiring.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 7 63-2689—0 5 The application en gineer must re view the control job requirements. This includes the seq uences of operation for the controller , and f or the system as a whole.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 8 required and thereby affect tr ansformer sizi ng. The f ollowing ex ample is an I x R line-loss calcula tion f or a 200 ft. (61m) run from the transf or mer to a controller drawing 37 V A and using two 18 A WG (1.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 9 63-2689—0 5 on page 6. The ear th ground ter minal (ter minal 3) must be connected to a verif ied ear th ground for each controller in the group (see Fig. 12 on page 9). — All loads on the co ntrolle r must be powered by the same transf or mer that powers the controller itself .
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 10 Cabling should be selected that meets or e xceeds the BA Cnet Standard which specifies the f ollowing: An MS/TP EIA-485 network shall use sh ielded, twisted-pair cable with characteristic i mpedance between 100 and 130 ohms.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 11 63-2689—0 5 Fig. 13. T ermination modules. Wiring Method WARNING Electrical Shock Hazar d. Can cause severe inju ry , death o r property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 12 T able 7. Description of wiring ter minal connections for PUB6438S, PVB6436AS, and PVB6438NS.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 13 63-2689—0 5 • T ypical controller wiri ng f or 4 to 20 mA heating, cooling, and model ML6161 floati ng motor control (see Fig . 21 on page 18). • T ypical controller wir ing for a pneumatic transducer , model RP7517B (see Fig.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 14 Fig. 17. Controller wiring dia gram (model PVB6436AS shown) for typical V A V application with staged reheat.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 15 63-2689—0 5 Fig. 18. Contr oller wiring di agram (mod el PUB6438S shown) f or typica l PWM re heat and PWM peripheral heat v alve actuator . (For note 2, ref er to Fig. 14.) NO TE: Make sure to set the Co nfiguration DIP Switch as shown in Fig.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 16 Fig. 19. Controller wiring diag ram (model PUB6438S s hown) f or typical AHU application.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 17 63-2689—0 5 Fig. 20. Contr oller wiring di agram (model PUB6438S shown) with 4 to 20 mA enthalpy senso rs and digital inputs.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 18 Fig. 21. Co ntroller wiring diagram (model PUB6438S shown) with 4 to 20 mA he at ing, cool ing, and model ML6161 damper actuator .
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 19 63-2689—0 5 Fig. 22. Controller wiring diagram (model PUB6438S shown) f or RP7517B pneumatic transducer . CH E CKO U T Step 1. Check Instal lation and Wiring Inspect all wiring conn ections at the controller ter minals, and verify compliance with i nstallation wiring diagrams.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 20 T able 8. Status LED St ates. B ACNET STATUS LED: The LED on the front of the contro ller , between the BACnet MS/TP terminal s and MA C Address DIP Switches, provides a visual indication of the BA C net MS/TP communication status.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 21 63-2689—0 5 2. Once the ter minal bloc k is raised 1/4 in. (6.35 mm) from its alignment pins, grasp the ter minal bloc k at its center (f or long ter minal blocks g rasp it at each end) and pull it straight up.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS 63-2689—0 5 22.
SPYDER® BA CNET® PROGR AMMABLE CONTROLLERS 23 63-2689—0 5.
SP YDER® BACNET® PROGR AMMABLE CONTROLLERS Automation and Control Solu tions Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 customer.honeywell.com ® U .S. Registere d T rademark © 2012 Hone ywell International Inc. 63-2689—05 M.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Honeywell PVB4024S c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Honeywell PVB4024S - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Honeywell PVB4024S, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Honeywell PVB4024S va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Honeywell PVB4024S, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Honeywell PVB4024S.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Honeywell PVB4024S. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Honeywell PVB4024S ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.