Safety Instructions 2
Operating Instructions Batteries 3 Care and Cleaning 6, 7 Remote Control Features 4, 5
Cool Only Models AE1CD10AM / AE0CD10AM AE1CD14DM / AE0CD14DM AE1CD20DM / AE0CD20DM
Installation Instructions Air Purging and Leakage Test 15 Before You Begin 8 Connection Tubing 11 Dimensions 9 Drainage Hose 11 Electrical Requirements 8 Electrical Wiring 12–14 Indoor Unit 12, 13 Location 10 Outdoor Unit 14, 15 Tubing Hole 11 Power Line 14 Mounting Plate 11 Test Operation 16 Wiring Indoor Unit 12 Wiring Outdoor Unit 14
Heat/Cool Models AE1RD10AM / AE0RD10AM AE1RD14DM / AE0RD14DM AE1RD20DM / AE0RD20DM
Minibloc
La section française commence à la page 19
Troubleshooting Tips 17 Normal Operating Sounds 17
Consumer Support Consumer Support Back Cover Warranty 18
e instrucciones de
instalación
La sección en español empieza en la página 37
Write the model and serial numbers here for the indoor and outdoor units:
Indoor Serial # ____________________
Outdoor Model # ____________________
Outdoor Serial # ____________________
Find these numbers on a label on the side of each unit.


Operating the air conditioner. GEAppliances.com
Press the FAN pad to set the desired fan speed (AUTO/Low/Medium/High).
Make sure power is connected and press the ON/OFF pad to start the system.
Press the TEMP +/– pads to set the desired temperature.
Press the MODE pad to select the desired operation mode.
Press the SWING pad for automatic rotation of the louvers. Press again to stop the rotation.
The remote control uses two AAA batteries.
Remove the cover from the back of the remote control and insert two new batteries (pay attention to the polarity).
Reattach the cover.
I Do not mix new and used batteries or different
types of batteries.
I Remove batteries when the remote control is not
in use for an extended time.
I The remote control signal can only be received
within a range of 20 ft.
I The remote control should be placed about
3 feet or more away from TV sets or any other electrical appliances.
Battery cover

About the remote control.
The remote control transmits the signals to the system.
Features and appearance may vary.
AUTO—In this mode, the unit automatically controls the room temperature within the range of 77ºF and 68ºF. The fan will run continuously while the unit is in AUTO mode. When the room temperature exceeds 77ºF, the unit will go into COOL Mode. When the room temperature drops to 73ºF, the fan will continue to run but COOL Mode will turn off. When the temperature drops below 68ºF, the unit will go into HEAT Mode. When the temperature reaches 73ºF, the fan will continue to run but HEAT Mode turns off. NOTE: This temperature range setting cannot be adjusted and will not be displayed.
Swing on Clock and timer
Timer set ON and OFF
COOL—Use to cool the room to the desired temperature set between 61ºF and 86ºF. NOTE: The unit will not provide optimum cooling if the outside temperature is below 60ºF. Under certain conditions, the unit may activate the antifreeze protection cycle for approximately 5 minutes to remove ice from the indoor coil.
DRY—Use to dehumidify the room. The fan will run at a fixed low speed to provide maximum dehumidification. The temperature can be set between 61ºF and 86ºF.
FAN—Use to turn ON and OFF the fan-only operation. COOL, HEAT or DRY mode will not be provided.
HEAT (on models so equipped)—Use to warm the room to the desired temperature set between 61ºF and 86ºF. NOTE: The unit will not provide optimum heating if the outside temperature is below 14ºF. Under certain conditions, the unit may activate the antifreeze protection cycle for approximately 8 minutes to remove ice from the outdoor coil. During this cycle, it is normal to hear operating sounds such as refrigerant flowing inside the system.

About the remote control . (cont.) GEAppliances.com
The remote control transmits the signals to the system.
Display Displays all set contents when turned on. Displays only the set temperature and time when turned off. ON/OFF Pad Press to turn the system on and off. MODE Pad Press to change the operation mode to AUTO, (COOL), (DRY), (FAN ONLY) or (HEAT). TEMP Pads Press + to increase the set temperature in 1ºF increments. Press – to decrease the set temperature in 1ºF increments. In the COOL and HEAT modes, the set temperature can be selected from 61ºF to 86ºF. The set temperature will not be displayed in the AUTO mode. FAN Pad Press to change the fan speed to AUTO FAN, (Low Fan), (Medium Fan) or
T-ON (Timer ON) Pad When the air conditioner is off, press T-ON (timer on) to set it to turn on automatically (using its previous settings) at the time you set.
Press TIME- or TIME+ pads to set the start time in 1-minute increments.
Press and hold the TIME- or TIME+ pads to set the start time in 10-minute increments.
To cancel ON (T-ON), press the CANCEL pad.
T-OFF (Timer OFF) Pad When the air conditioner is on, press T-OFF (timer off) to set it to automatically turn off at the time you set.
Press TIME- or TIME+ pads to set the turn- off time in 1-minute increments.
Press and hold the TIME- or TIME+ pads to set the turn-off time in 10-minute increments.
(High Fan). SWING Pad Press for automatic rotation of the louvers. Press again to stop them from rotating. SLEEP Pad Press to turn the sleep mode on and off. When in the cooling mode and the sleep timer is set, the set temperature will automatically increase 2ºF after the first hour and 2°F after the second hour. SLEEP Mode is compatible with COOL, HEAT and DRY. CLOCK Pad Press to set the time of day. Press TIME- or TIME+ pads to set the time in 1-minute increments. Press and hold the TIME- or TIME+ pads to set the time in 10-minute increments.
To cancel OFF (T-OFF), press the CANCEL pad.
TIME Pads Use when setting the CLOCK and timers (T-ON and T-OFF). Press to set in 1-minute increments. Press and hold to set in 10-minute increments.
CANCEL Pad Press to cancel the timer(s).

Care and cleaning of the air conditioner.
Grille, Case and Remote Control
Air Filters The two air filters behind the front grille should be checked and cleaned at least every 30 days or more often, if necessary.
Turn the system off before cleaning. To clean, wipe with a soft, dry cloth. Do not use bleach or abrasives.
Open the front access panel.
Pull the filter tab slightly forward to remove the filter. Clean the filter with a vacuum or warm, soapy water. Rinse and allow the filter to dry before replacing it.
Reinsert the filters and close the front access panel.
Air intake vent · Air outlet vent


The heat exchanger coils and panel vents of the outdoor unit should be checked regularly. If clogged with dirt or debris, the heat exchanger and panel vents should be professionally cleaned.
I Dirty or clogged coils will reduce the operating
efficiency of the system and cause higher operating costs.
Operate the system in the fan mode for 2 hours. This will dry out the system.

ELECTRICAL REQUIREMENTS
Read these instructions completely and carefully.

6” or more space to the ceiling
6” or more space to the wall
6” or more space to the wall
valve x 5/16″ female (1/2″-20UN)
118” or more air outlet side
79” or more space to the floor
To aid installation, the following tubing kits may be ordered:
12” or more space to the wall
79” or more air outlet side
111⁄4”–10K and 14K BTU models 117⁄8”–20K BTU models
211⁄4”–10K and 14K BTU models 227⁄16”–20K BTU models

Read these instructions completely and carefully; then follow step by step.
The platform must support a minimum of 200 lbs. See Installation Dimensions for mounting hole spacing.

INSTALL THE CONNECTION TUBING • Connect the copper tubing with the relevant union tubes of the indoor unit and tighten the flare nut of the connection tubes. NOTE: Be careful when bending the connection tubes to avoid damaging them. 1. Align the center of the tube flare with the relevant valve. 2. Screw in the flare nut by hand and then tighten the nut with spanner and torque wrench. See the table below for the correct torque. 3. Connecting tube specifications are shown below:
INSTALL THE TUBING HOLE • Make the tubing hole in the wall at a slight downward slant to the outdoor side.
3” from right edge to center of right tubing hole
Hole is 2” diameter for 10K and 14K BTU
11⁄2” from bottom edge to center of right tubing hole
models and 21⁄2” diameter for
20K BTU models.

WIRE THE INDOOR UNIT (cont.) NOTE: Wiring must be done by a qualified electrician according to the local codes and regulations and this manual. The connecting wire should be correctly connected to the circuit interface.
WIRE THE INDOOR UNIT NOTE: Use UL-approved electrical branch circuit disconnect for providing supply voltage to split system indoor and outdoor units. Locate disconnect within sight and readily accessible per NEC and local codes. 1. Open the front access panel. 2. Remove the cover plate of the electrical box.
Electrical wires must be secured with attached strain reliefs.
*L1 will be used for neutral in 115V models.
Indoor unit Outdoor unit

INSTALL THE INDOOR UNIT • Route the tubes and wiring from the right side of the indoor unit. Cut off the tailings from the chassis as necessary.
7 INSTALL THE INDOOR UNIT (cont.) • Wrap the tubes and wiring and pull them through the cut-off-tailings hole.
Control cord (for cooling/heating type only)
2 Right rear tube

WIRE THE OUTDOOR UNIT 1. Open the cover of the outdoor unit. 2. The connecting wire lead from the terminal board of the indoor unit must be connected correctly. 3. The connecting wire should be a little longer so that it can be maintained easily.
INSTALL THE POWER LINE 1. Open the wiring cover and remove the knockouts. 2. The connector should be secured by the nut, and the wiring cover should be replaced and secured with the included screw. 3. All wiring should be protected by liquid-tight tubing, and connections to the wiring cover should be with liquid-tight connectors.
Wrap electrical cords with attached metal tie to provide strain relief.
10,000 and 14,000 BTU Models
*L1 will be used for neutral in 115V models.
Indoor unit Outdoor unit

INSTALL THE OUTDOOR UNIT • Install the connection tube 1. Align the center of the tubing flare with the relevant valve. 2. Screw in the flare nut by hand and then tighten the nut with spanner and torque wrench. See the table below for the correct torque. 3. Connecting tube specifications are shown below:
10 PURGE THE AIR AND TEST FOR LEAKAGE 1. Install the connecting tubes of the indoor/outdoor unit. 2. DO NOT OPEN THE GAS VALVES UNTIL THE EVACUATION PROCESS IS COMPLETE. 3. Remove the gas line service port cap and connect the gas valves of the vacuum gauge, vacuum pump and outdoor unit. NOTE: Connect by using a 1/4″ Female x 1/2″ Male Adapter Access Fitting (obtain locally). 4. Start the vacuum pump. (Running time should be more than 15 minutes.) 5. Check the vacuum with the vacuum gauge. The gauge should read -30 in. Hg. After evacuation, fully close the handle on the manifold valve (on the vacuum pump device). Then stop the vacuum pump and disconnect it. 6. The pressure should be kept for 1–2 minutes to confirm that the reading of the vacuum gauge does not change. The pressure should be -30 in. Hg. 7. Remove the vacuum line and replace the service port cap. 8. Remove both the liquid and gas valve caps. 9. Open the gas and liquid valve entirely, using the 5 mm Allen wrench. If this is not done, the performance will be reduced, or an error will occur. 10. Replace the caps and tighten securely.
10,000/14,000 20,000 Specifications BTU Units BTU Units
Design Length 20 ft. 26.2 ft.
Extra Refrigerant Charge 0.16 oz./ft. 0.54 oz./ft. Per Ft. Above Design Length
Outer Diameter Liquid Pipe 1/4″ 3/8″
Outer Diameter Gas Pipe 1/2″ 5/8″
Max. Distance Height 33 ft. 33 ft.
Max. Distance Length 68 ft. 98 ft.
Tubing OD Tightening torque (in./lb.)

10,000 and 14,000 BTU models only: • If the remote control is lost, the emergency run operation can be performed with a ballpoint pen or similar object. a. When the unit is off, set the handling switch to the AUTO mode.
10,000 and 14,000 BTU Models
The unit will then automatically run in the mode selected by the microcomputer system according to the surrounding temperature. If you want to turn the unit off, press the handling switch again. b. When the unit is on, set the handling switch to the STOP mode to
turn off the unit.
20,000 BTU models only: • If the remote control is lost, open the front access panel and perform the following: a. Set the handling switch to the AUTO position to operate in the
AUTO mode. Once there is a remote control signal, the unit will again be controlled by that signal. b. Set the handling switch to the STOP position to turn off the unit.
K Has the unit been securely installed? If not, the unit may fall, shake or make noises. K Has the refrigerant leak test been performed? Leakage may cause insufficient cooling capacity. K Does the unit drain well? Poor drainage can cause condensation and dripping. K Is the voltage correct according to the nameplate? Incorrect voltage may cause electrical malfunction. Diagnostic
information is available for this unit. Contact your service technician. K Is the unit properly grounded? A nonsecure ground connection can cause damage. K Are the air inlet and outlet completely free of cover? Covering the air inlet or outlet may cause insufficient cooling
capacity. K Have the length of the connection tubing and refrigerant capacity been recorded? It is important to know these
things for future reference.
Handling switch · 20,000 BTU Models · Handling switch

Before you call for service… GEAppliances.com
Troubleshooting Tips: Save time and money! Review the chart below first and you may not need to call for service.
The system The fuse is blown/circuit •Check the house fuse/circuit breaker box and does not start breaker is tripped. replace the fuse or reset the breaker.
The Timer operation is not set •Check the Timer functions and make sure they are correctly. set to the desired settings.
The unit does not operate when •This is normal. Wait about 3 minutes and the unit restarted. will restart.
The system does not Airflow is restricted. •Make sure there are no curtains, blinds or furniture cool as it should blocking the front of the system.
The temperature control may •Turn to a lower or higher setting. The lowest setting not be set high or low enough. provides maximum cooling.
The air filter is dirty. •Clean the filter at least every 30 days. See the Operating Instructions section.
The room may have been hot. •When the system is first turned on, you need to allow time for the room to cool down.
Cold air is escaping. •Check for open furnace floor registers and cold air returns.
I These sounds are common during the
I A noise that sounds like air being released is a
antifreeze cooling or heating modes.
design feature of dehumidifying water being processed inside the system.
I You may hear a sound like water flowing. This
is the sound of refrigerant flowing inside the system.
I You may hear a clicking noise when you start
or stop the unit. This sound is the expansion or contraction of the unit due to changes in the temperature.

Split System Warranty.
All warranty service provided by our designated service network. To schedule service, call 866.404.5245. For service in Canada, contact Gordon Williams Corp. at 1.888.209.0999. Please have serial number and model number availa ble when calling for service.
Staple your receipt here. Proof of the original purchase date is needed to obtain service
under the warranty.
One Year Any part of the air conditioner which fails due to a defect in materials or workmanship. From the date of the During this limited one-year warranty, GE will also provide, free of charge, all labor original purchase and related service to replace the defective part.
Five Years Any part of the sealed refrigerating system (the compressor, condenser, evaporator From the date of the and all connecting tubing) which fails due to a defect in materials or workmanship. original purchase During this four-year limited additional warranty, GE will also provide, free of charge, all labor and related service to replace the defective part.
IService trips to your home to teach you how to use
IReplacement of house fuses or resetting of circuit
the product.
breakers.
IImproper installation, delivery or maintenance. If you
IFailure due to corrosion on models not corrosion-
have an installation problem, or if the air conditioner is of improper cooling capacity for the intended use, contact your dealer or installer. You are responsible for providing adequate electrical connecting facilities.
protected.
IDamage to the product caused by improper power
supply voltage, accident, fire, floods or acts of God.
IIncidental or consequential damage caused by possible
IFailure of the product resulting from modifications to
defects with this air conditioner.
the product or due to unreasonable use including failure to provide reasonable and necessary maintenance.
IDamage caused after delivery.
IProduct not accessible to provide required service.
IIn commercial locations labor necessary to move the
unit to a location where it is accessible for service by an individual technician.
EXCLUSION OF IMPLIED WARRANTIES—Your sole and exclusive remedy is product repair as provided in this Limited Warranty. Any implied warranties, including the implied warranties of merchantability or fitness for a particular purpose, are limited to one year or the shortest period allowed by law.
This warranty is extended to the original purchaser and any succeeding owner for products purchased for home use within the USA and Canada. If the product is located in an area where service by a GE Authorized Servicer is not available, you may be responsible for a trip charge or you may be required to bring the product to an Authorized GE Service location for service. In Alaska, the warranty excludes the cost of shipping or service calls to your home.
Some states do not allow the exclusion or limitation of incidental or consequential damages. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. To know what your legal rights are, consult your local or state consumer affairs office or your state’s Attorney General.
Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.
Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.