Manuel d'utilisation / d'entretien du produit Liqui-tect MC68HC16Z1 du fabricant Emerson
Aller à la page of 48
M ONITORING L IQUI - TECT M ONITORING S YSTEM U SER M ANUAL.
.
i T ABLE OF CONTENTS 1.0 I NTRODUCTI ON 1.1 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 1.2 Outside Enclosure Overview . . . . . . . . . . . . . . . . . . . . .
ii 6.4 Setup System - Setup ZN2 Zone 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 9 6.5 Setup System - Setup Alarm Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introd uctio n 1 1.0 I NTRODUCTION The Liebert Liqui-tect Monitoring System is the ultimate in leak detection and retr ofitting capabili- ties for computer rooms and other large areas.
Introd uctio n 2 1.2 Out side Enclosure Overview The enclosure for the Liqui-tect panel’ s controller board comes in two sizes: •T h e large enclosure is designed to accommo date the Transformer Module and future compo- nents, in addition to the controll er board.
Introd uctio n 3 1.3 T ypical Sequence Figure 3 shows a typical se quence of how the Liqui-tect Monitoring System fu nctions afte r detecting a leak, conta mination or cabl e brea k in either Zone 1 or Zone 2. Responses depend on configuration settings.
Introd uctio n 4 1.4 Controller Board Overview The Liqui-tect panel’s co ntroller board, as shown be low, has connectors for two digital outputs for leak detection alarms, two digital out p uts for cable break alarms, two inputs for l e ak detection cables and two analog outputs for co nnecting to a building management sy stem.
Introd uctio n 5 H-S t a t u s L E D s Indicates the operation al status of the panel. 1.5: LED Indicators I - 4/20mA ou tput (Zone 2) Provides the distance liquid is detected, normal status and cable fault. Used to provide status to a building managemen t system or remote monitoring system.
Introd uctio n 6 1.5 LED Indicators The Liqui-tect pan el’s controller bo ard has LED in dicators that s how the status of inputs, ou tputs and other board components.
Installation 7 2.0 I NST ALLATION 2.1 Inst allation Considerations The Liqui-tect panel must be instal led indoors and may be mounted on the surf ace of a wall or flush- mounted, depending on the user’s appli cation and th e type of wall the unit will be mounted on.
Installation 8 2.2 Surface-Mounting th e Liqui-tect Panel After dete rmining where t o place the unit, check to ensure that yo u have all the hard ware required to install the panel on the surface of a wall.
Installation 9 2.3 Flush-Mounting the Liqui-tect Panel The Liqui-tect panel may be fl ush mounted accord ing to company practices—either with screws through the sides of the pa nel into wall supports or with hangin g hardware that attaches to the back of the pan el.
Installation 10 2.4 Connect Power to the Liqui-tect Panel The Liqui-tect panel requires 24VAC for proper op eration. Liebert recomme nds using the optional Transformer Module manufa ctured by Liebert or another UL-approve d Class 2 power uni t to obtain proper voltage.
Installation 11 2.4.2 Input and Output Power Connections - Large Enclosure Input Power Connections To connect el ectrical power to the Transformer Module: 1. Install electrical wi ring from util ity power to the Transformer Modu le. 2. Use copper wires only; prope r wiring to use fo r power is 14/2 A WG copper wire with ground.
Connection s and Configuration 12 3.0 C ONNECTIONS AND C ONFIGURATION Input and output connect ion s to the Liqui-tect panel may be made in any order—it is not n ecessary, for example, to ma ke all inpu t connections be fore making any output connections.
Connection s and Configuration 13 3.1 Connecting Leak Detection Cable Inputs The leak detection cable inputs are found on the lowe r right side of the Liqui- tect panel’s printed wir- ing assembly board.
Connection s and Configuration 14 3.1.2 Connecting Leak Detection Cable to the Connecti on Cable The connection cable has a black fitt ing on one end that will fasten se curely to the fitting on one end of the leak detection cable—see Figure 8 .
Connection s and Configuration 15 3. Once the cable passes the test, la y it in the pattern desired. Pay special attention to the following cable placement precautions. 4. Install the hold-down clips in pairs, as shown i n Figure 10 , with the following considerations: a.
Connection s and Configuration 16 3.2 Connecting Alarm Output s The Zone 1 and Zone 2 alarm outputs, found in the top right corner of the Liqui-tect panel, provide a contact outpu t for a leak and a cable break for each zone. As an example, the outputs may provide alarms to an auxili ary alarm panel or building ma nagement sys- tem.
Connection s and Configuration 17 3.4 RS422 SiteScan Web Connector The Liqui-tect panel will interfa ce wi th Liebert’s SiteSc an Web enterprise monitoring system. SiteScan can be used to monit o r the Liqui-tect panel from a host computer an d silence the a udible alarm.
Overview of Menus 18 4.0 O VERVIEW OF M ENUS The Liqui-tect panel displa ys the Opening Screen at startup, as shown in Figure 14 . If any alarms are active, the Current Alarm screen appears. (Pressi ng any key on the LCD keypad will silence the audib le alarm.
V iew Status Options 19 5.0 V IEW S TAT U S O PTIONS The View Status menu allows any user to view the st atus of cables in both zones, an alarm history log and a trend log for both zones. The arrows ↑↓ are used to scroll through the menu. The Enter ↵ key is used to select the menu item.
V iew Status Options 20 5.1 View Cable S tatus The Cable Status screens display th e overall status of the cable con- nected to each of the two zones moni tored by the Liqui-tect panel, as well as the length of the cable be ing monitored and the amount of cur- rent present in each cable.
V iew Status Options 21 5.2 View Alarm History The Alarm History Log contains up to 100 records of al arms that have occurred. Records are added to this log as alarms occur. To view t he Alarm Histor y Log: • From the Main Menu, use the arrows ↑↓ to choose View Status , then press Enter ↵.
V iew Status Options 22 5.3 View Zone T rend The Zone Trend Log contains up to 288 records that are recorded at regular intervals (every 24 hours) to assist us ers with verifying opera- tional and troubleshoot ing problems. Records are added the b eginning of the log as they occur.
System and Control Options 23 6.0 S YSTEM AND C ONTROL O PTIONS The System and Control menu allows you to config ure the Liqui-te ct panel—s etting up inputs and outputs and system featu res such as date and time.
System and Control Options 24 Figure 16 shows the main options availabl e from the System & Control menu. Figure 16 Menu ov erview - System and Control menu Opening Screen LIQUI-TECT PANEL DD-MON-YY HR:MM:SS VERSION X.
System and Control Options 25 6.2 Setup System - Overview The Setup System screen displays six options that allow you to config ure zones with cable, alarm outputs, the re-alarm delay time, lo g point.
System and Control Options 26 6.3.1 Identify the Zone as Connected To make use of the zone ZN1, you mu st specify it as Connected (Y). By default, ZN1 is Not connected (N). See 3.1 - Connecting Leak Detec- tion Cable Inputs for instructions on connecting the cable to this zone.
System and Control Options 27 6.3.4 Auto Calibration The auto calibration feature is desi gned to allow compensation for the resistance tolerances in the two legs of the sensing w ires. As soon as cable is conn ected, th e panel begins calcula ting the cable length.
System and Control Options 28 6.3.6 Set Up Sensitivity for Cont amination Detection Each zone may be set up with a se nsitiv ity level a t which cont amina- tion on the cable is detected. Examples are construction debris and dust. • The most sensit ive setting is 2 0 µA—light conta mination wi ll trig- ger an alarm.
System and Control Options 29 6.4 Setup System - Setup ZN2 Zone 2 The Liqui-tect p a nel has two inde pendent zones—ZN1 and ZN2—that may be con figured ind ividually . Each zone ca n monitor up to 5,000 ft. (1524m) of le ak detection cable. To configure the second zone: • In the Setup System Menu, choose Setup ZN2 Zone 2 (see above right).
System and Control Options 30 6.5 Setup System - Setup Alarm Output s The Liqui-tect panel has six alarm outputs—three types for eac h zone: • Digital alarm output for cabl e break detection - a c.
System and Control Options 31 6.5.1 Specify Long est Cable Length You may specify the lengt h of the longest cable connected to either of the 4-20 mA alarm outpu ts. The default value is 0-1000 f t. (0-304.8m). Valid entri es range from 0-500 ft. (0-152.
System and Control Options 32 Following are some similarities an d differ ences between Latched and Unlatched alarms. Liqui-tect System’ s Response to Alarms - Both Latched and Unlatched When a leak.
System and Control Options 33 6.7 Setup System - Setup Mapmode Mapping involves measuring the exac t location of various points along the leak detection cable. This greatly simplifies the use of the Liqui-tect Monitoring System to quickly pinpoint the location of a leak.
System and Control Options 34 6.7.1 Vie w Last Map The View Last Map option allows you to review the mapped points from the last mapping of a zone. This feature is the data logger for the mapmode process d escribed in the p revious sectio n, 6.7 - Setup Sys- tem - Setup Mapmode .
System and Control Options 35 6.8 Setup System - Setup System Info The Setup System Info options allow users to: • Change Passw ord —used for access to system setup functions • Change Date &.
System and Control Options 36 6.8.2 Change Date & Tim e/Automatic Daylight Saving Time The Liqui-tect panel has a built -in, real-time clock that is backed up by an encapsulated l i thium bat- tery and set up to adjust automati cally for daylight saving time tw ice a year.
System and Control Options 37 6.9 Reset Latched Alarms The Reset Latched Alarms menu allows you to clear an y leak o r fault alarms that have been defined as latched. To clear latched alarms: Log In and Choose Reset Latched Alarm • From the Main Menu, use the arrows ↑↓ to choose System and Control , then press Enter ↵ (see 6.
System and Control Options 38 6.10 Clear Alarm History The Clear Alarm History menu allows you to delete all records from the Alarm History Log, which contai ns up to 100 records of alarms that have occurred.
System and Control Options 39 6.1 1 Clear Zone T rend The Clear Zone Trend menu allows yo u to delete all records from the Zone Trend Log, which contains up to 288 records.
Specifications 40 7.0 S PECIFICATIONS 7.1 Liqui-tect Panel Specifications Power Requirements Small Enclosure Large Enclosure NOTE LPS0240 115VAC LPL1150 230VAC LPL2300 If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
Specifications 41 NOTES.
Specifications 42.
.
The Comp any Behind the Products With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a co.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Emerson Liqui-tect MC68HC16Z1 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Emerson Liqui-tect MC68HC16Z1 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Emerson Liqui-tect MC68HC16Z1, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Emerson Liqui-tect MC68HC16Z1 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Emerson Liqui-tect MC68HC16Z1, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Emerson Liqui-tect MC68HC16Z1.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Emerson Liqui-tect MC68HC16Z1. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Emerson Liqui-tect MC68HC16Z1 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.