ADAM 4000 Data Acquisition Modules User's Manual.
ADAM 4000 Series Data Acquisition Modules User’s Manual Copyright Notice This document is copyrighted, 1997, by Advantech Co., Ltd. All rights are reserved. Advantech Co., Ltd., reserves the right to m ake improvements to the products described in this manual at any time witho ut notice.
Table of Con te nts Chapter 1 Introduction ..….....……... ...............… .......... ........…….. 1-1 1.1 Overview .......... ........... ..….......... .......... .......... ..….........….…… 1-2 1.2 Applications .............. ..
3.17 ADAM-4056SO 12-ch. Source Type Isolated Digital Output Module ………….……………………………………… …..……... 3-63 3.18 ADAM-4060/4068 Relay Output Module ............... .….......... . 3-65 3.19 ADAM-4069 8-channel Relay Output Module ………… …….
Chapter 8 Calibration ............ .......... ........ .... .........…. ........... ......... 8-1 8.1 Analog Input Module Calibration ............... ............ .….......... . 8-2 8.2 Analog Input Resistance Calibration ........ ............ ...
B.1.1 Engineering Units ........................................... ..................…….......... B-2 B.1.2 Percent of FSR .................................... .............................…............. B-3 B.1.3 Twos complement hexade cimal .
Introduction 1.
Introduction 1- 2 ADAM 4000 Series User’s Manual 1.1 Overview The ADAM Ser ies is a set of inte lligent sensor-to-computer interface modules containing built-in m icroprocessor. They are remotely controlled through a simple set of commands issued in ASCII format and transm itted in RS-485 p rotocol.
Chapter 1 Chapter 1 Introduction 1 - 3 The command set fo r input modules is larg er because it incorp orates alarm functions. All communication s to and from the module a re performed in ASCII, which means that ADAM modules can be virtually programmed in any high-level language.
Introduction 1- 4 ADAM 4000 Series User’s Manual ADAM modules can be m ounted on any panels, brackets, or DIN rails. They can also be stacked together . The RS-485 n etwork, together with screw-terminal plug connectors, allows for system expansion, recon figuration, and repair without disturbing field wiring.
Installation Guideline 2.
Inst alla tion Gu ide line 2- 2 ADAM 4000 Series User’s Manual This chapter provides gu idelines to what is needed to set up and install an ADAM network. A quick hook up scheme is provided that le ts you configure modules before th ey are installed in a network.
Chapter 2 Chapter 2 installation Guideline 2 - 3 Power supply For the ease of use in industrial en vironments, the ADAM m odules are designed to accept industry stand ard +24 V DC , unregulated power. Operation is guaranteed when using any power su pply between +10 and +30 V DC .
Inst alla tion Gu ide line 2- 4 ADAM 4000 Series User’s Manual Figure 2-1 Power Supply Connections We advise the following standard color s (as indicated on the modu les) for each powe r li ne: +Vs .
Chapter 2 Chapter 2 installation Guideline 2 - 5 Notice: User can refer our help file to see m ore details for explanation of Utility operation. ADAM Communication Speed In ADAM series, the baud rate ca n be configur ed from 1200 bp s to 38.4 K bps. Ho wever, th e ba ud rate of all modules i n an R S-485 network must be the same.
Inst alla tion Gu ide line 2- 6 ADAM 4000 Series User’s Manual 2.2 Basic configuration and ho ok-up Before placing a m odule in an existing network, the module should be configured. Though all modules are initially configured at th e factory, it is recommend ed to check if th e baud rate is set correctly beforehand.
Chapter 2 Chapter 2 installation Guideline 2 - 7 The following items are required to configure a m odule: an ADAM converter module, a personal computer with RS-232 por t (baud rate set to 9600) and the ADAM utility software.
Inst alla tion Gu ide line 2- 8 ADAM 4000 Series User’s Manual Module at address 01 responds that it is configured for an input range of + /-2.5 V, ba ud rate of 9600, integratio n time of 50 ms (60 Hz). The code also shows engineer ing units and no checksum checking or generation.
Chapter 2 Chapter 2 installation Guideline 2 - 9 2.3 Baud rate and Checksum ADAM modules contain EEPROMs to stor e configuration information and c alibration constants. The EEPROM rep laces the conventional array of switches and pots that ar e originally used for specif ying ba ud rate, input an d outp ut range … et c.
Inst alla tion Gu ide line 2- 10 ADAM 4000 Series User’s Manual • Power on all com ponents except the ADAM Module. • Power the ADAM module on while shorting the INIT* and GND terminals (See Figu.
Chapter 2 Chapter 2 installation Guideline 2 - 11 2.4 Multiple Module Hookup The Figure below is a n example of how ADAM modules ar e connected in a multiple module network: Figure 2-5 Multi-module Co.
Inst alla tion Gu ide line 2- 12 ADAM 4000 Series User’s Manual 2.5 Progra mming Example The following example is a simple program written in Visual Basic 6. 0 that demonstrates how to ge t temperature reading which is stored in the address of 01H from ADAM-40 11 mod ule.
Chapter 2 Chapter 2 installation Guideline 2 - 13 Step 3. Select “Microsoft C omm Control” Step 4. Add the C omm Cont rol on the for m..
Inst alla tion Gu ide line 2- 14 ADAM 4000 Series User’s Manual Step 5. Add three Comman d Buttons on the form as shown be low Step 6. Add one Label and one Text on the form as sh own below.
Chapter 2 Chapter 2 installation Guideline 2 - 15 Step 7. Click OPEN Button and type in the following codes. The source codes ar e listed at the end o f this section. Step 8. Click SEND Button and type in the following codes. The source codes ar e listed at the end o f this section.
Inst alla tion Gu ide line 2- 16 ADAM 4000 Series User’s Manual Step 9. Click CLOSE Button and type in the followin g codes. The source codes ar e listed at the end o f this section. Step 10. Run the Project → Click OPEN to open COM1 → Click SEND to send the Get Tem perature Reading Command.
Chapter 2 Chapter 2 installation Guideline 2 - 17 Program Source Codes: OPEN Comman d Button: Private Sub Command1_Click() ' Buffer to hol d input string Dim Instring As String ' Use COM1. MSComm1.C ommPort = 1 ' 9600 baud, no p arity, 8 data, and 1 stop bit.
I/O Modules 3.
I/O Mo dules 3- 2 ADAM 4000 Series User’s Manual 3.0 The common specif ication of ADAM-4000 I/O Series Communication: z RS-485 (2-wire) to host z Speeds: 1200, 2400 , 4800, 9600, 19200, 38400, 57600, 11 5200 bps (ADAM-4080 , ADAM-4080D o nly suppor t up to 3 8400 bps) z Max.
Chapter 3 Chapter 3 I/O Modules 3-3 3.1 ADAM-4011/4011 D Thermocouple Input Modules The ADAM-4011/4011D Th ermocouple Input Modules use a microprocessor-contro lled integrating A/D converter to convert sensor voltage, curre nt or thermocouple signa l into digi tal data.
I/O Mo dules 3- 4 ADAM 4000 Series User’s Manual Event counting The event counter is connected to the Digital Input ch annel and can be used to keep track of the to tal amount of external low-speed pulses. Its accumulated maximal count is 65535. The count will maintain at 65535 even if the actual number of events exceeds 6 5535.
Chapter 3 Chapter 3 I/O Modules 3-5 Function Descript ion for the ADAM-4011 Thermocouple Input Module To provid e a better und erstanding of the ADAM modu le functions, the following is a d escription of the module ADAM-401 1 with the most extensive set of functions.
I/O Mo dules 3- 6 ADAM 4000 Series User’s Manual ADAM-4 011 Thermocouple Input Module Figure 3-1 ADAM-4011 Thermocouple Inp ut Module Accepts: - J, K, T, E, R, S and B thermocouples - Millivolt inputs : ± 15 mV, ± 50 m V, ± 100 mV and ± 500 mV - Volt inputs: ± 1 V and ± 2.
Chapter 3 Chapter 3 I/O Modules 3-7 ADAM-4011D Thermocouple Input Mo dule Figure 3-2 ADAM-4011D The rmocouple Input Module with LED Display Accepts: - J, K, T, E, R, S and B thermocouples - Millivolt inputs : ± 15 mV, ± 50 m V, ± 100 mV and ± 500 mV - Volt inputs: ± 1 V and ± 2.
I/O Mo dules 3- 8 ADAM 4000 Series User’s Manual Application Wiring Figure 3-3 ADAM-4011/4011D Thermocouple Inp ut Wiring Diagram Figure 3-4 ADAM-4011/4011D Millivolt and Vol t Input Wiring Diagram .
Chapter 3 Chapter 3 I/O Modules 3-9 Figure 3-6 ADAM-4011/4011D Digital Output Wiring Diagram Used with SSR (HI-LO alarm) Figure 3-7 ADAM-4011/4011D Digital Input Wi ring Diagram Used with TTL Figure 3.
I/O Mo dules 3- 10 ADAM 4000 Series User’s Manual 3.2 ADAM-4012 Anal og Input Module The ADAM-4012 Analog Input Modules use a m icroprocessor- control led int egrati ng A/D conve rter t o conver t sens or voltage or current signals into digital data.
Chapter 3 Chapter 3 I/O Modules 3-11 Alarm s ignaling Analog input modules include High and Low alarm functions. High and Low alarm limits m ay be downlo aded into the module’s EEPROM by the host computer. The alarm function s can be enabled or d isabled remotely.
I/O Mo dules 3- 12 ADAM 4000 Series User’s Manual ADA M- 40 12 Analog Input Module Figure 3-9 ADAM-4012 Analog Input Module Accepts: - Millivolt inputs ± 150 mV and ±500 m V - Volt inputs: ±1 V, ±5 V and ±10 V - Current input: ±20 mA (r equires a 125 resistor) Two digital output channels and one digital input channel are provided.
Chapter 3 Chapter 3 I/O Modules 3-13 Application Wiring Figure 3-10 ADAM-4012 Millivolt and Volt Input Wiring Diagram Figure 3-11 ADAM-4012 Process Current Inp ut Wiring Diag ram Figure 3-12 ADAM-4012.
I/O Mo dules 3- 14 ADAM 4000 Series User’s Manual Figure 3-13 ADAM-4012 Digital Input Wiring Diagram Used wit h TTL Figure 3-14 ADAM-4012 Digital Input Wiring Diagram Used with Dry contact.
Chapter 3 Chapter 3 I/O Modules 3-15 3.3 ADAM-4013 RTD Module The ADAM-401 3 RTD Input Module supports one Pt or Ni RTD input channel for temperature m easurement. This modu le can accept RTD sensors with two, three, or four wires. The module offers signal conditioning, A/D conversion, ranging, and RS-485 digital communication functions.
I/O Mo dules 3- 16 ADAM 4000 Series User’s Manual Application Wiring Figure 3-16 ADAM-4013 RTD Inputs Wiring Diagram.
Chapter 3 Chapter 3 I/O Modules 3-17 3.4 ADAM-4015 6- channel RTD Input Module A RTD m odul e is po pul arly use d for tem per ature measu rem ent. Unlike the traditional design, the ADAM-4015 RTD I nput Module provides six RTD input channels for different types of RTD signal like as Pt, Ni, Balco.
I/O Mo dules 3- 18 ADAM 4000 Series User’s Manual Application Wiring Figure 3-18 ADAM-4015 RTD Input Mod ule Wiring Di agram.
Chapter 3 Chapter 3 I/O Modules 3-19 Technical specification of ADAM- 4015 Channel Number 6 differential Support Protocol ADAM ASCII and MO DBUS/RTU Input Type Pt100, Pt1000, BALCO500, Ni Input Connec.
I/O Mo dules 3- 20 ADAM 4000 Series User’s Manual 3.5 ADAM-4015T 6-cha nnel Thermistor Input Module A Thermistor Module is popu larly used for temperature measurement. Unlike the traditional design, the ADAM-4015T provides six therm istor input channels for thermistor sig nal.
Chapter 3 Chapter 3 I/O Modules 3-21 Technical specification of ADAM- 4015T Channel Number 6 differential Support Protocol ADAM ASCII and MO DBUS/RTU Input Type Thermistor Input Connections 2 or 3 wir.
I/O Mo dules 3- 22 ADAM 4000 Series User’s Manual 3.6 ADAM-4016 Analog Input/Output Module A strain gauge input mo dule uses a microprocessor-contro lled integrating A/D converte r to convert sensor voltage or current signals into digital data f or load cell and st ress measu rem ent.
Chapter 3 Chapter 3 I/O Modules 3-23 Every A/D conversion will be follo wed by a comparison with the High and Low limits. When the input value exceeds on e of these limits, the High or Low alarm state is set to ON. There are two alarm mode options, Momentary and Latch ing.
I/O Mo dules 3- 24 ADAM 4000 Series User’s Manual ADA M- 40 16 Analog Input/Out put Module Figure 3-21 ADAM-4016 Analog Input/Output Module Accepts: - Millivolt inputs : ± 15 mV, ± 50 m V, ± 100 mV, ± 500 mV - Current input: ± 20 mA Excitation voltage output: 0 ~ 1 0 V Four digital output channels are provided.
Chapter 3 Chapter 3 I/O Modules 3-25 Application Wiring Figure 3-22 ADAM-4016 Strain G auge Voltage Input Wiring Diagram Figure 3-23 ADAM-4016 Strain Gauge Current Input Wiring Diagram.
I/O Mo dules 3- 26 ADAM 4000 Series User’s Manual Figure 3-24 ADAM-4016 Digital Output Wiring Diagram Used with SSR.
Chapter 3 Chapter 3 I/O Modules 3-27 3.7 ADAM-4017/40 17+/4018/4018M/4018+ 8-c hannel Analog Input Modules ADAM-4 017/4 018 8-channel Analog Input Module The ADAM-4017/4018 is a 16-bit, 8-channel analog input module that provides programmable input ranges on all channels.
I/O Mo dules 3- 28 ADAM 4000 Series User’s Manual ADAM-4 017+ 8-channel Differential Analog Input Mod ule Here comes a solutio n to the demand for m ore analog input channels. Similar to its counterpart, the AD AM-4017+ enables eight d ifferential channels with multiple input ranges.
Chapter 3 Chapter 3 I/O Modules 3-29 ADA M- 40 17 8-channel Analog Input Module Figure 3-25 ADAM-4017 8-channel Analog Input Module Channels: - Six differential, two single-ended Accepts: - Millivolt .
I/O Mo dules 3- 30 ADAM 4000 Series User’s Manual ADAM-4 017+ 8-channel Differential Analog Input Mod ule Figure 3-26 ADAM-4017+ 8-ch. differential ana log input module Jumper se tting (ADAM-4017+) 1. JP0~J P7 JP0~ JP7 20 mA In put R an ge Voltage Input rang e Mapping to Channel Ch.
Chapter 3 Chapter 3 I/O Modules 3-31 Technical specification of ADAM-4017+ Channel 8 Input Type mV, V, mA Input Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 4 ~ 20 mA Isolation Voltage 300.
I/O Mo dules 3- 32 ADAM 4000 Series User’s Manual ADA M- 40 18 8-channel Analog Input Module ADAM-4018 CODE INPUT RANGE 00 01 02 03 04 DATA ACQUISITION MODULE Vin 0+ Vin 0- Vin 1+ Vin 5+ Vin 5- Vin 6+ INIT* (Y) DATA+ (G) DATA- (R) +Vs (B) GND Vin 1- Vin 4+ Vin 4- AGND INPUT: Thermocouple mV, V, mA OUPUT: RS-485 05 ?5 mV ?0 mV ?00 mV ?00 mV ? V ?.
Chapter 3 Chapter 3 I/O Modules 3-33 ADAM-4018M 8-channel Analog Input Data logger ADAM-4018M CODE INPUT RANGE 00 01 02 03 04 DATA ACQUISITION MODULE Vin 0+ Vin 0- Vin 1+ Vin 5+ Vin 5- Vin 6+ INIT* (Y) DATA+ (G) DATA- (R) +Vs (B) GND Vin 1- Vin 4+ Vin 4- AGND INPUT: Thermocouple mV, V, mA OUPUT: RS-485 05 ?5 mV ?0 mV ?00 mV ?00 mV ? V ?.
I/O Mo dules 3- 34 ADAM 4000 Series User’s Manual ADAM-4 018+ 8-channel Thermocouple Input Module Figure 3-29 ADAM-4018+ 8-ch. t hermocouple input module JP0~ JP7 4~20 mA I npu t R ang e Voltage Input rang e Mapping to Channel Ch. 1 Ch. 2 Ch. 3 Ch. 4 Ch.
Chapter 3 Chapter 3 I/O Modules 3-35 Isolation Voltage 3000 V DC Fault and over-vol tage protection Withstands ov er voltage up to ±35 V Sampling Rate 10 sample/sec (total) Input Impedance Voltage: 20 M , Current: 120 Accuracy ±0.1% or better Power Consumpti on 0.
I/O Mo dules 3- 36 ADAM 4000 Series User’s Manual Vin5- Vin5+ 1 Vin6+ mV/V - + AGND Vin7+ Figure 3-31(b) ADAM-4017 Singl e-ended Input Wi ring Diagra m (Ch6 and Ch7) 11 Vi n 0 + Vi n 0 - Vi n 1 + Vi.
Chapter 3 Chapter 3 I/O Modules 3-37 11 Vi n 0 + Vi n 0 - Vi n 1 + Vi n 1 - T/C or 4~20m A + - Figure 3-33 ADAM-4018+ Thermocouple Input Wiring Diagram 3.8 ADAM-4019+ 8 -channel Universal Ana log Input Module The ADAM-4019+ is universal analog input module to integrat e with various AI modules into one.
I/O Mo dules 3- 38 ADAM 4000 Series User’s Manual Figure 3-34 ADAM-4019+ 8-channel Universal Analog Input The jumper setting of ADAM-4019+ for inpu t type selection: JP0~JP7 20mA Input Range Voltage Input range Mapping to Channel Ch.0 Ch.1 Ch.2 Ch.3 Ch.
Chapter 3 Chapter 3 I/O Modules 3-39 Application Wiring Figure 3-35 ADAM-4019+ Universal Analog In put Wiring Diagram 120.
I/O Mo dules 3- 40 ADAM 4000 Series User’s Manual Technical specification of ADAM-4019+ Channel 8 Resolution 16 bits Input Type V, mV, mA, T/C Input type and temperature range V: ± 1 V , ± 2.
Chapter 3 Chapter 3 I/O Modules 3-41 3.9 ADAM-4021 Anal og Output Module Analog output mod ule receives its digital input through an RS-485 interface from the host computer. The form at of the data is either two’s complement hexadecim al format or percentage o f full-scale range (FSR), depending on the mo dule’s configuration.
I/O Mo dules 3- 42 ADAM 4000 Series User’s Manual ADA M- 40 21 Analog Output Module Figure 3-36 ADAM -4021 Analog Output Module Depending on its configuration setting s the module accepts the follow.
Chapter 3 Chapter 3 I/O Modules 3-43 Application Wiring Figure 3-37 ADAM-4021 Analog Output Wiring Diagram.
I/O Mo dules 3- 44 ADAM 4000 Series User’s Manual 3.10 ADA M-4024 4-chan nel An alog Output Module ADAM-4024 is a 4-channel analog output module with m ixed type I/O. Currently, there is not any ADAM-4000 series mod ule that provides more than on e analog output ch annel.
Chapter 3 Chapter 3 I/O Modules 3-45 Technical specification of ADAM-402 4 • Resolution: 12-bit • Output Ty pe: mA, V • Output R ange : 0~20 mA , 4~20 mA, and ±10V • Isolation Voltag e: 3000 V DC • Output Impedance: 0.5 Ω • Accuracy: ±0.
I/O Mo dules 3- 46 ADAM 4000 Series User’s Manual Application Wiring Figure 3-39 ADAM-4024 Pin Define and Wiring Diagram.
Chapter 3 Chapter 3 I/O Modules 3-47 3.11 ADAM-4050 Dig ital I/O Module The ADAM-4050 features seven digital input and eight digital output channels. The outp uts are open-collector transistor switches that you can control from the host comp uter.
I/O Mo dules 3- 48 ADAM 4000 Series User’s Manual Application Wiring Figure 3-41 ADAM-4050 TTL Input Wiring D iagram Figure 3-42 ADAM-4050 Conta ct Closure Inp ut Wiring Diagram Figure 3-43 ADAM-405.
Chapter 3 Chapter 3 I/O Modules 3-49 3.12 ADAM-4051 16-channel Iso lated Digital Input Module The ADAM-4051 is a 16 channel Digital Inpu t Module. It is built with 2500 V DC optica l isolation, and it is suitable for critical applicatio ns.
I/O Mo dules 3- 50 ADAM 4000 Series User’s Manual Application Wiring Figure 3-45 ADAM-4051 Dry Contact Wiring Diagram Figure 3-46 ADAM-4051 Wet Cont act Wiring Diagram.
Chapter 3 Chapter 3 I/O Modules 3-51 3.13 ADAM-405 2 Isolated Dig ital Input M odule The ADAM-4052 provides eight digital input ch annels. Among these eight channels, six of them are fully ind ependent isolated channels and the other two are isolated channels with a c ommon ground.
I/O Mo dules 3- 52 ADAM 4000 Series User’s Manual Application Wiring Figure 3-48 ADAM-4052 Isolation Digital Input Wiri ng Ground External Internal.
Chapter 3 Chapter 3 I/O Modules 3-53 3.14 ADAM-40 53 16-chann el Digital Input Mod ule The ADAM-4053 provides 16 dig ital input channels fo r dry contact or wet contact signals. For d ry contact, the effective distance from DI to contact point is up to 500 m.
I/O Mo dules 3- 54 ADAM 4000 Series User’s Manual Note: There is one pin showin g “INIT*/DI15” on the connector of the ADAM-4053 module. You can configure the p in define by the jumper on PCB (r.
Chapter 3 Chapter 3 I/O Modules 3-55 Application Wiring Figure 3-50 ADAM-4053 Wet C ontact Input Wiring Diagram Figure 3-51 ADAM-4053 Conta ct Closure Inp ut Wiring Diagram External Internal External .
I/O Mo dules 3- 56 ADAM 4000 Series User’s Manual 3.15 ADAM-4055 1 6-channel Isolated Digital I/O Module The ADAM-4055 o ffers 8 channel isolated digital input and 8 channel isolated digita l output for critical applications. The inputs accept 10~50 V voltag e, and the outputs can sup ply 5~40 V DC at the open collector.
Chapter 3 Chapter 3 I/O Modules 3-57 Application Wiring: Figure 3-53 ADAM-4055 Digital Output Wiring Diagram Figure 3-54a ADAM-4055 Digi tal Input Dry Cont act Wiring Diag ram.
I/O Mo dules 3- 58 ADAM 4000 Series User’s Manual Figure 3-54b ADAM-4055 Digital Input Dry Contact Diagram ( Internal) Figure 3-55a ADAM-4055 Digital Input Wet Contact Wiring Diagram.
Chapter 3 Chapter 3 I/O Modules 3-59 Figure 3-55b ADAM-4055 Digi tal Input Wet Contact Diagram (Internal) Figure 3-56a ADAM-4055 Default Jum per Setting for the Digital Input Wiring (Support dry and w.
I/O Mo dules 3- 60 ADAM 4000 Series User’s Manual Figure 3-56b ADAM-4055 Default Jumper Setting for the Digi tal Input Wiring.
Chapter 3 Chapter 3 I/O Modules 3-61 3.16 ADAM- 4056S 1 2-channel Sink Type Isolated Digital Output Module ADAM-4056S is a 12-channe l sink ty pe is olated di gital ou tput module. The isolated cha nnels are designed for d igital outpu t for critical applications.
I/O Mo dules 3- 62 ADAM 4000 Series User’s Manual Application Wiring +5V ~ +40V LOAD + - Figure 3-58 ADAM-4056S Digital Out put Wirin g Diagram.
Chapter 3 Chapter 3 I/O Modules 3-63 3.17 ADAM-405 6SO 12- channel Source Typ e Isolat ed Digital Output Module ADAM-4056SO is a 12-channel source type isolated digital output module. The 12 isolated digital output channels are designed for critical applications.
I/O Mo dules 3- 64 ADAM 4000 Series User’s Manual Application Wiring Figure 3-60 ADAM-4056SO Digital Output Wiring Diagram.
Chapter 3 Chapter 3 I/O Modules 3-65 3.18 ADAM-4060/4 068 Relay Output Module The ADAM Relay Outp ut Module is a low-cost a lternative to SSR modules. The ADAM-40 60 Relay Output Module provides four relay channels; two of them are Form A, and two are Form C.
I/O Mo dules 3- 66 ADAM 4000 Series User’s Manual ADA M- 40 68 8-channel Relay Output Module TYPE SIGNAL RE LA Y 0,1,2, 3 RE LA Y 4,5,6, 7 FORM A FORM C R L 4 N O R L 4 C O M R L 3 N O R L 3 C O M R.
Chapter 3 Chapter 3 I/O Modules 3-67 Application Wiring The following diagr ams are examples of h ow to connect Form A and Form C relay output ap plications to your ADAM modules.
I/O Mo dules 3- 68 ADAM 4000 Series User’s Manual Figure 3-65 ADAM-4068 Form C Relay Output Wiring Diagram RL 4 N O RL4 C OM RL 3 N O RL3 C OM Figure 3-66 ADAM-4068 Form A relay output Wiring Diagra.
Chapter 3 Chapter 3 I/O Modules 3-69 3.19 ADAM -4069 8-channel Relay Output M odule The ADAM-4069 Relay Output Module provides eig ht channels; four are Form A and the rest are Form C. This mo dule is excellent for ON/OFF control or low-power switching applicat ions.
I/O Mo dules 3- 70 ADAM 4000 Series User’s Manual Specific atio n: z Number of Re lay Output Channel: 8 z Digital Output: (Source) 4 Form A , 4 Form C AC 5A@240V DC 5A@30V ON/OFF : 5m s/ 5.
Chapter 3 Chapter 3 I/O Modules 3-71 Figur e 3-69 ADAM-4069 Form A Relay Output.
I/O Mo dules 3- 72 ADAM 4000 Series User’s Manual 3.20 ADAM-408 0/4080D Counte r/Frequency Input Mo dules ADAM-4080/4080D Counter/frequ ency input module has two 32- bit counter input channels (counter 0 and cou nter 1) with built-in programmable timer for fr equency measurement.
Chapter 3 Chapter 3 I/O Modules 3-73 External Control ( Gate mode) Aside from the GND and co unter terminal, each chan nel has a gate terminal to connect to an external gate signal. The gate signal (high or low) can trigger the counter from start or stop counting.
I/O Mo dules 3- 74 ADAM 4000 Series User’s Manual ADAM-4080 Counter/Frequency Inp ut Mo dules ADAM-4080 CODE INPUT RANGE 50 51 DATA ACQUISITION MODULE GATE 1- GATE 1+ IN 1- IN 0 GATE 0 D.
Chapter 3 Chapter 3 I/O Modules 3-75 ADAM-4080D Counter/Frequency Input Modules with LED Display ADAM-4080D CODE INPUT RANGE 50 51 DATA ACQUISITION MODULE GATE 1- GATE 1+ IN 1- IN 0 GATE 0 D.
I/O Mo dules 3- 76 ADAM 4000 Series User’s Manual Application Wiring Counter Input GATE0 IN0 1 D.GND Gate Control GND Figure 3-72 ADAM-4080/4080D Non-isolated Input GATE1+ GATE1- 11 IN1- IN1+ + - + .
C o m m a n d S e t 4.
Command Set 4- 2 ADAM 4000 Series User’s Manual 4.1 Introduction In order to avoid communication conflicts among devices trying to send data simultaneously, all the traffics are coordinated by the host computer. This action is initia ted by the host computer using a command/respon se protocol.
Chapter 4 Chapter 4 Command Set 4-3 Before the command set is given, we provid e an I/O module commands search table to help you find the com mands that you wish to use.
Command Set 4- 4 ADAM 4000 Series User’s Manual 4.3 I/O Module Commands Search Table ADAM-401 1 Command T able Command Synta x Command Name Command Descrip tion Page N o.
Chapter 4 Chapter 4 Command Set 4-5 ADAM-401 1 Command T able (Continued) Command Synta x Command Name Command Descrip tion Page N o. @AADI Re ad Dig ital I/O an d Alarm Status The addressed m odule r.
Command Set 4- 6 ADAM 4000 Series User’s Manual ADAM- 401 1D Comma nd T able Command S y ntax Command Name Command Descrip tion Pa g e No. %AANNTTCCFF Configuratio n Sets the addre ss, input range,b.
Chapter 4 Chapter 4 Command Set 4-7 ADAM- 401 1D Comma nd T able (C on tin ued) Command Syntax Command Name Command Descrip tion Page N o. @AAD I Read Digita l I/O and Alarm Status The addressed m odu.
Command Set 4- 8 ADAM 4000 Series User’s Manual ADAM-4012 Command T able Command S y ntax Command Name Command Descrip tion Pa g e No. %AANNTTCCFF Configuratio n Sets the addre ss, input range,ba ud.
Chapter 4 Chapter 4 Command Set 4-9 ADAM-4012 Command T able (Continued) Command S y ntax Command Name Command Des cription Pa g e No . @AADI Read Digita l I/O and Alarm Status The addressed module re.
Command Set 4- 10 ADAM 4000 Series User’s Manual ADAM-4013 Command T able Command Synta x Command Name Command Description Page No. %AANNTTCCFF Configuration Sets the address, baud rate, dat a forma.
Chapter 4 Chapter 4 Command Set 4-1 1 ADAM-4015/ADAM-4015T Command Table Command Syntax Comm an d Nam e Command Description Page No. %AANNTTCC FF Conf igur ati on Sets the address, baud rate, d ata fo.
Command Set 4- 12 ADAM 4000 Series User’s Manual ADAM-4016 Command T able Command Synta x Command Name C ommand Descrip tion Page No. %AANNTTCCFF Configuratio n Set the address, input range, baud ra.
Chapter 4 Chapter 4 Command Set 4-13 ADAM-4016 Command T able (Continued) Command S y ntax Command Name Command Descrip tion Pa g e No . @AA DI Read Digi tal I/O And Alarm Status Ask the addre ssed mo.
Command Set 4- 14 ADAM 4000 Series User’s Manual ADAM-4017 Command T able Command Synta x Command Name C ommand Description Page N o. %AANNTTCCFF Configuratio n Set the address, input range, baud ra.
Chapter 4 Chapter 4 Command Set 4-15 ADAM-4017+ Command T able Command S y ntax Command Name Command Description Page No. %AANNTTCCFF Configuration Set the addr ess, input range, baud r ate, data form.
Command Set 4- 16 ADAM 4000 Series User’s Manual ADAM-4017+ Input range and external calibrating input source for each input type Rang e bcode ( Hex ) Input Range Max. Si gnal Min Signal Displayed Reso lutio n 07 +/-4~20 mA +20.000 -20.000 1uA 08 +/-10 V +10.
Chapter 4 Chapter 4 Command Set 4-17 ADAM-4018 Command T able Command S y ntax Command Name Command Descrip tion Pa g e No. %AANNTTCCFF Configuration Set the addres s, input range, ba ud rate, data fo.
Command Set 4- 18 ADAM 4000 Series User’s Manual ADAM-4018+ Command T able Command Synta x Comm and Name Command Des cription Page No. %AANNTTCCFF Configuration Set the addres s, input range, ba ud .
Chapter 4 Chapter 4 Command Set 4-19 ADAM-4018+ Command T able (Continued) Command S y ntax Command Name Command Descrip tion Pa g e No. $AA1Ci Offset C alibration Offset error calibrate of ass ignmen.
Command Set 4- 20 ADAM 4000 Series User’s Manual ADAM-4018M Command T able Command Synta x Command Name Command D escription Page No. %AANNTTCCFF C onfiguration Set the a ddress, input range, baud r.
Chapter 4 Chapter 4 Command Set 4-21 (Continued on following page) ADAM-4018M Command T able (Continued) @AA T Read Memory Operation Mode Read the recordi ng status o f the memo ry mod ule . 5-41 @AAL Event Record Count Read the number of stored eve nt records in the memory module.
Command Set 4- 22 ADAM 4000 Series User’s Manual ADAM-4019+ Command T able Command Synta x Command Name Command Descrip tion P age No. %AANNTTCCFF Configurat ion Sets the address, baud rate, data fo.
Chapter 4 Chapter 4 Command Set 4-23 ADAM-4019+ Command T able (Continued) Command S y ntax Command Name Command Descrip tion Pa g e No. $AA0Ci Singl e Ch annel Span Cali bration Gain error cali brate.
Command Set 4- 24 ADAM 4000 Series User’s Manual ADAM-4021 Command T able Command Synta x Command Name Command Descript ion Page No. %AANNTTCCFF C onfiguration Set the address, outpu t range, baud r.
Chapter 4 Chapter 4 Command Set 4-25 ADAM-4024 Command T able Command Synta x Command Name Command Des cription Page No. %AANNTTCCFF Configurat ion Set the a ddress, output range , baud rate, data for.
Command Set 4- 26 ADAM 4000 Series User’s Manual ADAM-4024 Command T able (Continued) Command Synta x Command Name Command Des cription Page No. $AAACnZ EMS Flag setting Enable/Disable (Z=1/0) CHn E.
Chapter 4 Chapter 4 Command Set 4-27 ADAM-4050 Command T able Command Synta x Command Name Command Description Page No. %AANNTTCCFF Configuration Sets address, baud rate, and/or checksum status, to a .
Command Set 4- 28 ADAM 4000 Series User’s Manual ADAM-4051 Command Table Command Synta x C ommand Name Command D escription Page No. %AANNTTCCFF C onfigurat io n S ets the address, bau d rate, and/o.
Chapter 4 Chapter 4 Command Set 4-29 ADAM-4052 Command Table Command Synta x Command Name Command Des cription Page No. %AANNTTCCFF Configuration Sets address, bau d rate, and/or checksum stat us, to .
Command Set 4- 30 ADAM 4000 Series User’s Manual ADAM-4053 Command Table Command Synta x Command Name C ommand Description Page No. %AANNTTCCFF C onfigurat ion Sets address, baud rate, and/or checks.
Chapter 4 Chapter 4 Command Set 4-31 ADAM-4055 Command Table Command Synta x Command N ame Command Descrip tion Page No. %AANNTTCCFF Configuration Sets the address, baud rat e, and/or checks um status.
Command Set 4- 32 ADAM 4000 Series User’s Manual ADAM-4056S Command Table Command Syntax Command N ame Command Description Page No. %AANNTTCCFF Configuration Sets the address, baud rate, and/or chec.
Chapter 4 Chapter 4 Command Set 4-33 ADAM- 4056 SO Co mmand Tabl e Command Syntax Command N ame Command Description Page No. %AANNTTCCFF Configuration Sets the address, baud rate, and/or checks um sta.
Command Set 4- 34 ADAM 4000 Series User’s Manual ADAM-4060/4068 Command Table Command Syntax Command N ame Command Description Page No. %AANNTTCCFF Configuration Sets ad dress, baud rat e, and/or ch.
Chapter 4 Chapter 4 Command Set 4-35 ADAM-4069 Command Table Command Synta x Command Name Comm and Description Page No. %AANNTTCCFF Configurat ion Sets address, bau d rate, and/or checks um status , t.
Command Set 4- 36 ADAM 4000 Series User’s Manual ADAM-4080 Command Table Command Synta x Command Name Command Descrip tion Page No. %AANNTTCCFF Configuratio n Sets the address, i nput mode, baud rat.
Chapter 4 Chapter 4 Command Set 4-37 ADAM-4080 Command Table (Continued) Command Synta x Command Name Command Description Page No. $AAAG Set Gate Mode Request s the spec ified counter/frequency module.
Command Set 4- 38 ADAM 4000 Series User’s Manual ADAM-4080 Command Table (Continued) Command Synta x Command Name Command Description Page No. $AA4S Enable/Di sable Digital Filter Enables or disable.
Chapter 4 Chapter 4 Command Set 4-39 ADAM-4080 Command Table (Continued) Command Synta x Command Name Comm and Description Page No. @AAPN(data) Set Initial Count V alue of Cou nter N Sets the initial .
Command Set 4- 40 ADAM 4000 Series User’s Manual ADAM-4080D Command Table Command Synta x Command Name Command Description Page No. %AANNTTCCFF Configuration Sets the address, input mode , baud rate.
Chapter 4 Chapter 4 Command Set 4-41 ADAM-4080D Command Table (Contin ued) Command Synta x Command Name Command Description Page No. $AAAG Set Gate Mode Requests the specified counter/ frequency modul.
Command Set 4- 42 ADAM 4000 Series User’s Manual ADAM-4080D Command Table (Contin ued) Command Synta x Command Nam e Command Description P age No. $AA4S Enable/D isable Digital Filter Enables or dis.
Chapter 4 Chapter 4 Command Set 4-43 ADAM-4080D Command Table (Contin ued) Command Synta x Command Name C ommand Description Page No. @AAEA T Enable Alarm Enable the alarm in either momentary or latch.
Analog Input Module Command Set 5.
5-2 ADA M 40 00 S eri es Use r’s M anu al 5.1 Analog Input Common Command Set Command S y ntax Description I/O Module %AANNTTCCF F Sets the address, i nput range, baud rate, data format, checksum st.
Chapter 5 5-3 ADAM 4000 Series Use r’s Manual Command S y ntax Command Descrip tion I/O Module $AA4 Returns the value that was stored in the sp ecified module's register after the # ** command .
5-4 ADA M 40 00 S eri es Use r’s M anu al 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ %AANNTTC CFF Name Configuration command Description Sets address, input range, baud rate, data format, checksum status, and/or integration time for an analog input module.
Chapter 5 5-5 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ %AANNTTC CFF Response !AA(cr) if the comm and is valid. ?AA(cr) if an invalid par ameter was entered or if the INIT* terminal was not groun ded when attempting to change baud rate or checksum settings.
5-6 ADA M 40 00 S eri es Use r’s M anu al 401 1, 401 1D, 4012, 4013, 401 5, 40 15T , 4016 , 4017, 4017+, 4018, 4018+, 4018M, 4019+ Table 5-1 Input Range Cod es (Type Codes) Input Range Code (Hex) Input R ange for 401 1, 401 1D, 4018, 4018+ (Thermocouple and ± 20 mA only), 4018M 00 ± 15 mV 01 ± 50 mV 02 ± 100 mV 03 ± 500 mV 04 ± 1 V 05 ± 2.
Chapter 5 5-7 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ Input Range Code (Hex) Input Range for 40 13 20 Platinum, -100 ~ 100 ℃ , a=0.00385 21 Platinum, 0 ~ 100 ℃ , a=0.
5-8 ADA M 40 00 S eri es Use r’s M anu al 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ Input Range Code (Hex) Input Ran ge for 4019+ 02 ± 100 mV 03 ± 500 mV 04 ± 1 V 05 ± 2.
Chapter 5 5-9 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ $AA2 Name Configuration Status comm and Description The command requests the retur n of the configuration data from the analog input module at addr ess AA.
5-10 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ $AA2 Example command: $452(cr) response: !45050600(cr) The command asks the an alog input module at addr ess 45h to send its configuration data.
Chapter 5 5-1 1 ADAM 40 00 Seri es User’ s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ $AAF Name Read Firmware Version command Description The command requests the analog input module at address AA to return the version co de of its firmware.
5-12 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4018M, 4019+ $AAM Name Read Module Name comm and Description The command requests the analog input module at address AA to return its name.
Chapter 5 5-13 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4019+ #AA Name Analog Data In command Description The command will return th e input value from a specifie d (AA) module in th e currently configured data fo rmat.
5-14 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4 016, 4017, 4017+, 4018, 4018+, 4019+ #AA Example command: #DE(cr ) response: >FF5D(cr) The analog input module at address DEh has an in put value of FF5D.
Chapter 5 5-15 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017, 4017+, 4018, 4018+, 4018 M, 4019+ #AAN Name Read Analog Input from Channel N com mand Description The command will retur n the input value from one of the eight channels of a sp ecified (AA) mo dule in the currently configured data form at.
5-16 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017, 4017+, 4018, 4018+, 4018 M, 4019+ $AA5VV Name Enable/disable Channels for Multiplexing command Description Enables/d isables multiplexing simultaneously for separate channels of a specified input module.
Chapter 5 5-17 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017, 4017+, 4018, 4018+, 4018 M, 4019+ $AA6 Name Read Channel Status command Description Asks a specified inpu t module to return the status of al l channels.
5-18 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4016, 4017, 4018, 4018M $AA0 Name Span Calibration command Description C alibrates an analog input module to correct for gain errors.
Chapter 5 5-19 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4016, 4017, 4018, 4018M $AA1 Name Offset Calibration command Description Calibrates an analog input module to c orrect for offset errors. Syntax $AA1(cr) $ is a delimiter character.
5-20 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4016 #** Name Synchronized Sampling command Description Orders all analog input modules to sample their in put values and store the valu es in special registers. Syntax #** # is a delimiter character.
Chapter 5 5-21 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4016 $AA4 Name Read Synchronized Data comm and Description R eturns the input value that was stored in the addressed module’s register, after a Synchronized Sampling comm and #** was issued.
5-22 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4013, 4015, 4015T , 4016 $AA4 Example command: $074( cr) response: >071+ 5.8222(c r) The command asks the an alog input module at addr ess 07h to send its analog input data.
Chapter 5 5-23 ADAM 4000 Series Use r’s Manual 401 1D, 4015, 4015T , 4018+, 4019+ $AAB Name Channel Diagnose command Description Diagnose channel status in over range, under range, and wire opening.
5-24 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4018, 4018+, 4018M, 4019+ $AA3 Name CJC Status command Description Instructs the addressed analog input module to read its CJC (Cold Junc tion C ompensa tion) s ensors and re turn the acquired data.
Chapter 5 5-25 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4018, 4018+, 4018M, 4019+ $AA9SNNNN Name CJC Offset Calibr ation command Description Calibrates an analog in put module to adjust for offse t errors of its CJC (Cold Jun ction Compensation) se nsors.
5-26 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017+, 4018+, 4019 + $AA0Ci Name Single Channel Span Calibration command Description The command calibrates a sp ecified channel to correct fo r gain errors. Syntax $AA0Ci(cr) $ is a delimiter character.
Chapter 5 5-27 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017+, 4018+, 4019 + $AA1Ci Name Single Channel Offset Calibration command Description The command calibrat es a specified channel to cor rect for offset erro rs. Syntax $AA1Ci(cr) $ is a delimiter character.
5-28 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017+, 4018+, 4019 + $AA7CiRrr Name Single Channel Range Configuration command Description This command configures the input type and range of the specified channel in an analog input module. Syntax $AA7CiRrr(cr) $ is a delimiter character.
Chapter 5 5-29 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017+, 4018+, 4019 + $AA8Ci Name Read Single Channel Range Con figuration comma nd Description This command read the input type and range configuration of the specified channe l in an analog input module.
5-30 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017+, 4018+, 4019 + $AAXnnnn Name Watchdog Timer Setting command Description This co mmand se t the communication watchdog timer (WDT) cycle time.
Chapter 5 5-31 ADAM 4000 Series Use r’s Manual 4015, 4015T , 4017+, 4018+, 4019 + $AAY Name Read C ommunication Watc hdog Ti mer Cycle Setting command Description This comman d read the setting of communication watchdog timer (WDT) cycle tim e. Syntax $AAY(cr) $ is a delimiter character.
5-32 ADAM 4000 Series Use r’s Manual 4015, 4015T $AAS0 Name Internal Calibration command Description This comm and executes internal self- calibration for offset and gain errors. Syntax $AAS0(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of the analog input module which is to be calibrated.
Chapter 5 5-33 ADAM 4000 Series Use r’s Manual 4015, 4015T $AAS1 Name Reload Default C alibrating Pa rameter command Description Reload factory default calibrating parameter to overwrite current calibrating parameter. Syntax $AAS1(cr) $ is a delimiter character.
5-34 ADAM 4000 Series Use r’s Manual 5.2 Analog Input Data Logger Command Set Command Syntax Command Nam e Description I/O Module @AACCCSDMTT TT Set Memory Configuration Set the channel storage status, standalone mod e, data logger mode, storage ty pe and sampling int erval for the specified analog input data lo gg er .
Chapter 5 5-35 ADAM 4000 Series Use r’s Manual 4018M @AACCCSDMTTTT Name Set Memory Configuration command Description Sets the channel storage status, standalone m ode, data logger mode storage type and sampling interv al for the specified analog input d ata logger.
5-36 ADAM 4000 Series Use r’s Manual 4018M @AACCCSDMTTTT Response !AA(cr) if the co nfig uration is successful. ?AA(cr) if the co nfiguration fails. ! and ? are delimiter characters. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
Chapter 5 5-37 ADAM 4000 Series Use r’s Manual 4018M @AAD Name Read Memory Configuration command Description The command requests the config uration data from the analog inpu t data logger at addr ess AA. Syntax @AAD (cr) @ is a delimiter character.
5-38 ADAM 4000 Series Use r’s Manual 4018M @AASO Name Set Memory Operatio n Mode comman d Description Sets the operation mode of the analog input data logger at address AA to Start or Stop. Syntax @AASO(cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
Chapter 5 5-39 ADAM 4000 Series Use r’s Manual 4018M @AAT Name Read Memory Operation Mode command Description R equest the mem ory operation status o f the analog input data logger at address AA. Syntax @AAT (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
5-40 ADAM 4000 Series Use r’s Manual 4018M @AAL Name Event Record Count command Description R equest the n umber of event recor ds stored in the analo g input data logger at address AA. Syntax @AAL (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
Chapter 5 5-41 ADAM 4000 Series Use r’s Manual 4018M @AAN Name Standard Record Cou nt command Description R equest the number of standard records stored in the analog input data logger at address AA. Syntax @AAN (cr) @ is a delimiter character AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
5-42 ADAM 4000 Series Use r’s Manual 4018M @AARNNNN Name Re ad Reco rd Cont ent co mmand Description R equest the content of record NNNN stored in the analog input data logger at address AA. Syntax @AARNNN N (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
Chapter 5 5-43 ADAM 4000 Series Use r’s Manual 4018M @AARNNNN HHHH represents the 4-character h exadecimal number o f returned record stored in the analog input data logger at address AA. TTTTTTTT r epresents elap sed time. (cr) is the terminating character, carriag e return (0Dh).
5-44 ADAM 4000 Series Use r’s Manual 4018M @AAACSDHHHHTEIIII Name Set Alarm Limit command Description Set high/low alarm limits for the channel C in the analog input data logger at address AA. Syntax @AAAC SDHHHHTE IIII(cr) @ is a delimiter character AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
Chapter 5 5-45 ADAM 4000 Series Use r’s Manual 4018M @AAACSDHHHHTEIIII Example command: @EF A 0+20400+201 00(cr) response: !EF(cr) The command sets ch annel 0 of the analog input data logger at address EF as such: high alarm limit = 10.24 low alarm limit = 2.
5-46 ADAM 4000 Series Use r’s Manual 4018M @AABC Name Read Alarm Limit command Description R equest the alarm lim its for the specified chan nel in the analog inpu t data logger at addr ess AA. Syntax @AABC(cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an analog input data logger.
Chapter 5 5-47 ADAM 4000 Series Use r’s Manual 5.3 Dig ital I/O , A la rm an d Eve nt Co mmand Se t Command Synta x Command Name D escription I/O Module @AADI Read Dig ital I/O and Alarm Status The .
5-48 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AADI Name Read Digital I/O and Alarm Sta te Description The addressed analog input modu le is instructed to return the value of its digital input and output channels and the state of its alarm (Momentary or Latching) .
Chapter 5 5-49 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AADI Status Code DO0 001 002 003 OO OFF OFF OFF OFF O1 OFF O FF OFF ON O2 OFF O FF ON OFF O3 OFF O FF ON ON O4 OFF O N OFF O.
5-50 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AADO Name Set Digital Output command Description Sets the values of the module’ s digital output s (ON or OFF). Syntax @AADO(data)(cr) @ is a delim iter character. AA (ra nge 00-FF) represents the 2-char acter hexadecimal address of an analog input module.
Chapter 5 5-51 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AADO Example command: @05DO01(cr) response: !05(cr) The analog input module at add ress 05h is instructed to set digital output channel 1 to ON and digital o utput channel 2 to OFF.
5-52 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AAEAT Name Enable Ala rm co mmand Description The addressed analog input module is instructed to enable its alarm in either Latchi ng or Momentary mode. Syntax @AAEAT(cr) @ is a delimiter character.
Chapter 5 5-53 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AAHI Name Set High Alarm Limit command Description Downloads high alarm limit value into the addressed module. Syntax @AAHI(data)(cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
5-54 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AALO Name Set Low Alarm Limit command Description Download s Low alarm limit valu e into the addressed module. Syntax @AALO(data)(cr) @ is a delimiter character. AA (range 00-FF) represents the 2 -character hexad ecimal address of an an alog input modu le.
Chapter 5 5-55 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AADA Name Disable Alarm command Description Disables all alarm functions of the addressed analog input module. Syntax @AADA(cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
5-56 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AACA Name Clear Latch Alarm comm and Description B oth alarm states (High and Low) of the add ressed analog input module are set to OFF, no alarm. Syntax @AACA(cr) @ is a delimiter character.
Chapter 5 5-57 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AARH Name Read High Alarm Limit c ommand Description The addre ssed module is asked to return its High alarm limit value. Syntax @AARH(cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
5-58 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012, 4016 @AARL Name Read Low Alarm Lim it command Description The addressed modu le is asked to r eturn its Low ala rm limit value. Syntax @AARL (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
Chapter 5 5-59 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012 @AARE Name Read Event Counter command Description The addressed module is instructed to r eturn its even t counter value. Syntax @AARE (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
5-60 ADAM 4000 Series Use r’s Manual 401 1, 401 1D, 4012 @AACE Name Clear Event Counter command Description The addresse d module is instructed to reset its even t counter to zero. Syntax @AACE (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of an an alog input modu le.
Chapter 5 5-61 ADAM 4000 Series Use r’s Manual 5.4 Excitation Voltag e Output Command S et Command S y ntax Command Name Description I/O module $AA6 Get Excitatio n V oltage Output V alue Returns either la st value se nt to specified modul e by $AA7 command, or start-up output voltage.
5-62 ADAM 4000 Series Use r’s Manual 4016 $AA6 Name Get Excitation Voltage Output Value command Description The addressed strain g auge input module is instructed to return the latest output value it received from Excitation Voltage Output command.
Chapter 5 5-63 ADAM 4000 Series Use r’s Manual 4016 $AA7 Name Excitation Voltage Output comm and Description Send a v alue to the analog ou tput channel o f the addresse d strain gauge input module. Upon receipt, the analog output channel will output this value.
5-64 ADAM 4000 Series Use r’s Manual 4016 $AAS Name Start-up Voltage Output C onfiguration co mmand Description Stores the present analog output value of the strain gauge input module with addres s AA in the module’s non-vola tile register. The output value w ill take effect upon start -up or after a bro wnout.
Chapter 5 5-65 ADAM 4000 Series Use r’s Manual 4016 $AAS Example command: $0AS(cr) response: !0A(cr ) Presume the present output valu e of the output channel of the strain gauge input module with address 0A is +05 .000V. The command tells the module store th e present output value, in its non-volatile me mory.
5-66 ADAM 4000 Series Use r’s Manual 4016 $AAE Name Trim Calibration command Description Trims the output voltage of the strain gauge input module a specified number of u nits up or down. Syntax $AAE(number of co unts)(cr) $ is a delimiter characte r.
Chapter 5 5-67 ADAM 4000 Series Use r’s Manual 4016 $AAA Name Zero Calibration command Description Stores the voltage output value of the addressed str ain gauge input module as zero voltage reference.
5-68 ADAM 4000 Series Use r’s Manual 4016 $AAB Name Span Calibration command Description Stores the voltage output value of the addressed str ain gauge input module as 10V reference.
Analog Output Module C ommand Set 6.
Analog Outp ut M odule Com mand Se t 6- 2 ADAM 4000 Series User’s Manual 6.1 Analog Output Module Command for ADAM-40 21 Command S y ntax Command Name Descripti on I/O Module %AANNTTCCFF Configurat .
Chapter 6 6- 3 ADAM 4000 Series User’s Manual %AANNTTC CFF Name Configuratio n command Description Sets address, input range, baud rate, data format, checksum status, and/or integration time for an analog output module. Syntax %AANNTT CCFF(cr) % is a delimiter char acter.
Analog Outp ut M odule Com mand Se t 6- 4 ADAM 4000 Series User’s Manual %AANNTTC CFF Response !AA(cr) if the comm and is valid. ?AA(cr) if an invalid parameter was entered or the INI T* terminal was not grou nded when changing baud rate or checksum settings was attempted.
Chapter 6 6- 5 ADAM 4000 Series User’s Manual %AANNTTC CFF Example command: %310A310610(cr) response: !24(cr) The analog input module is configured from addresses 31h to a new add res s 0Ah, output range 4 to 20 mA , baud rat e 9600, engineering u nits data format, a slew ra te of 1.
Analog Outp ut M odule Com mand Se t 6- 6 ADAM 4000 Series User’s Manual #AA Name Analog Data Out command Description Send a value to the address of a nalog outp ut module. Then, the analog output modu le will output this value. Syntax #AA(data)(cr) # is a delimiter character.
Chapter 6 6- 7 ADAM 4000 Series User’s Manual #AA Example command: #3315.000(cr) response: >(cr) The command sends the va lue 15 mA, which is conve rted to engineering units, to the address 33h of the an alog output module. The analog output module responds with an output value of 15 mA which rep resents a valid command.
Analog Outp ut M odule Com mand Se t 6- 8 ADAM 4000 Series User’s Manual $AA4 Name Start-up Voltage/Curren t Output Configura tion command Description Stores the present output value of an analog output module at address AA in the m odule’s non-volatile r egister.
Chapter 6 6- 9 ADAM 4000 Series User’s Manual $AA3 Name Trim Calibration command Description Trim the address of analog output modu le for a specific number of un i t s up or dow n . Syntax $AA3(number of counts)(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address which is to be calibrat ed.
Analog Outp ut M odule Com mand Se t 6- 10 ADAM 4000 Series User’s Manual $AA3 Example co mmand : $073 14(c r) response: !07(cr) The command tells the analog output module at address 07h to increase its output value by 20 (14h) counts which are approximately 30 μ A.
Chapter 6 6- 11 ADAM 4000 Series User’s Manual $AA0 Name 4 mA Calibration command Description Stores the current output value 4 mA for refer ence in the specified address in analog output module. Syntax $AA0(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address whose data are to be sent.
Analog Outp ut M odule Com mand Se t 6- 12 ADAM 4000 Series User’s Manual $AA1 Name 20 mA Calibra tion command Description Stores the current output value of the addressed analog output module as 20 mA reference . Syntax $AA1(cr) $ is a delimiter character.
Chapter 6 6- 13 ADAM 4000 Series User’s Manual $AA2 Name Read Configuration Status command Description Instruct the analog output module to ret urn it s configu ratio n data. Syntax $AA2(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address for status reading.
Analog Outp ut M odule Com mand Se t 6- 14 ADAM 4000 Series User’s Manual $AA6 Name Last Value Re adback command Description The analog output module is in structed to return the la test output value that it has received from the Analog Data Ou t command.
Chapter 6 6- 15 ADAM 4000 Series User’s Manual $AA8 Name Current Readback command Description The addressed analog o utput module is instructed to measure the c urrent fl owing throug h its current/ volta ge loop and re turn the measure d data in the module’ s configured data form at.
Analog Outp ut M odule Com mand Se t 6- 16 ADAM 4000 Series User’s Manual $AA5 Name Reset Status command Description C hecks the Re set Status of th e analog o utput module to see whether it has been reset since the last Re set Status command was issued.
Chapter 6 6- 17 ADAM 4000 Series User’s Manual $AAF Name Read Firmware Version command Description The comma nd requests the analog ou tput module at address AA to return the version co de of its firmware. Syntax $AAF (cr) $ is a delimiter character.
Analog Outp ut M odule Com mand Se t 6- 18 ADAM 4000 Series User’s Manual $AAM Name Read Module Name Description The comma nd requests the analog ou tput module at address AA to return its name Syntax $AAM (cr) $ is a delimiter character. AA (range 00-FF) represents the 2 -character hexad ecimal address that you want to access.
Chapter 6 6- 19 ADAM 4000 Series User’s Manual 6.2 Analog Output Module Command for ADAM-40 24 ADAM-4024 Command Revie w: Command Set F unction Response E xample %AANNTT CCFF Module Configuration : .
Analog Outp ut M odule Com mand Se t 6- 20 ADAM 4000 Series User’s Manual ADAM-4024 Command Review: (Continued) Command Set Func ti on Res pons e Exam pl e #A AECn( da ta) Set data As C Hn Em erg enc y St op Dat a !AA ECn ( dat a) #02EC2 +07.456 #02EC1 -03.
Chapter 6 6- 21 ADAM 4000 Series User’s Manual ADAM-4024 Command Review: (Continued) Comm an d Set Funct io n Respon se Exa mple $AA8Cn Read B ack CHn Output R ange !AACnxx $027C2 $AAACnZ Enable/Dis.
Digital I/O, Relay ouput and Counter/Frequen cy Command Se t 7.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 2 ADAM 4000 Series User’s Manual 7.1 Digital I/ O and Relay Output Module Command Command S y ntax Descripti on I/O Module %AANNTTCCFF S.
Chapter 7 7- 3 ADAM 4000 Series User’s Manual Command Syntax Descripti on I/O Module $AAX2 Request s the Safty Fl ag of t he addressed di gital I/O modul e to see whether the safe ty value has b een executed since Wr ite Safety V alue command was set.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 4 ADAM 4000 Series User’s Manual %AANNTTC CFF Name Configuratio n command Description Configure address, baud rate and/or check sum status of the digital I/O module. Syntax %AANNTT CCFF(cr) % is a delimiter character.
Chapter 7 7- 5 ADAM 4000 Series User’s Manual %AANNTTC CFF Response !AA (cr) if the comm and is valid. ?AA(cr) if an in valid parameter was entered or the INIT* terminal was no t grounded when chan ging baud r ate or checksum settings were attempted.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 6 ADAM 4000 Series User’s Manual $AA6 Name Digital Data In command Description This command requests the specified (AA) module to return the status of its digital input channels and feedback value from its digital output channels.
Chapter 7 7- 7 ADAM 4000 Series User’s Manual $AA6 Example command: $336(cr ) response: !112200 (cr) This example is for ADAM-4050 . The first two character s, 11h (00010001), o f the response indicates that d igital output channels 0 and 4 a re ON and channels 1, 2, 3, 5 , 6, 7 are OFF.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 8 ADAM 4000 Series User’s Manual #AABB Name Digital Data Out command Description The command either sets a single digital output channel or sets all digita l output channel s simultaneous ly.
Chapter 7 7- 9 ADAM 4000 Series User’s Manual ADAM-4 05 6S and 4056SO: When writing to a single channel (bit), the first th ree characters are always 0. The value of the last character is either 0 or 1. When writing to all chan nels (byte), the first character zero is irrelevant, but the rest are significant (r ange 000h-FFFh).
Digital I/O and Relay Output Counter/Frequency Command Set 7- 10 ADAM 4000 Series User’s Manual #AABB Examples command: #140005 (cr ) response: >(cr) An output byte with value 05h (00000101) is sent to the digital I/O module at address 14h (Either ADA M-405 0 or ADAM-4060) .
Chapter 7 7- 11 ADAM 4000 Series User’s Manual #** Name Synchronized Sampling command Description Orders all (analog or dig ital) input modules to sa mple their input values and store them into a special register. Syntax #** # is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 12 ADAM 4000 Series User’s Manual $AA4 Name Read Synchronized Data comm and Description The addressed digital I/O module is in structed to return the value that was stored in its register by a Synchronized Sampling command .
Chapter 7 7- 13 ADAM 4000 Series User’s Manual $AA4 (dataOutput) two-character hexad ecimal value which is either the feedback of a digital ou tput channel or a relay. (dataInput) two-character hexadecim al value representing the input values of the digital I/O module.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 14 ADAM 4000 Series User’s Manual $AA2 Name Configuration Status comm and Description R eturns the c onfigurati on para meters of the dig ital I/ O module. Syntax $AA2(cr) $ is a delimiter character.
Chapter 7 7- 15 ADAM 4000 Series User’s Manual $AA2 Example command: $452 (cr) response: !454006 00 (cr) The command asks the dig ital I/O module at address 4 5h to send its configuratio n data. The digital I/O module at address 45h responds with baud rate 9600, no ch ecksum function and module supports fo r Advantech protocol.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 16 ADAM 4000 Series User’s Manual $AA5 Name Reset Status command Description Requests the Reset Status of the addressed digital I/O module to see whether it has been reset sin ce the last Reset Status command.
Chapter 7 7- 17 ADAM 4000 Series User’s Manual $AA5 Example command: $39 5(cr) response: !390 (cr) The command tells the digital I/O module at address 39h to return its Reset S tatus.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 18 ADAM 4000 Series User’s Manual $AAF Name Read Firmware Version command Description The comm and requests the digital I/O m odule at address AA to return the version co de of its firmware Syntax $AAF (cr) $ is a delimiter character.
Chapter 7 7- 19 ADAM 4000 Series User’s Manual $AAM Name Read Module Name comm and Description The comm and requests the digital I/O m odule at address AA to return its name Syntax $AAM (cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address that you will acces s to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 20 ADAM 4000 Series User’s Manual $AAX0TTTTDDDD Name Write Safety Value command Description Force th e DO chann els to safety status when communication is in time -out a nd over p re-de fine d peri od.
Chapter 7 7- 21 ADAM 4000 Series User’s Manual $AAX1 Name Read Safety Value comman d Description Read the time-ou t setting and pre-defined safety status of DO channels. Syntax $AAX1(cr) $ is a delimiter character. AA (ra nge 00-FF) represents the 2-char acter hexadecimal address that you will access to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 22 ADAM 4000 Series User’s Manual $AAX2 Name Read Safety Flag command Description Requests the Safety Flag of the add ressed digital I/O module to see whether the safety value has been executed since Write Safety Value command was set.
Chapter 7 7- 23 ADAM 4000 Series User’s Manual $AAE0 Name Read and Clear over Current Status Flag com mand Description Read the Over Cur rent Status Flag and Clear the Flag simultan eously. Syntax $AAE0(cr) $ is a delimiter character. AA (ra nge 00-FF) represents the 2-char acter hexadecimal address that you w ill access to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 24 ADAM 4000 Series User’s Manual $AAP Name Read the Low Power Status of Mo dule command Description The command requests the module at address AA to ret urn the low power status of module Syntax $AAP(cr) $ is a delimiter character.
Chapter 7 7- 25 ADAM 4000 Series User’s Manual $AAS Name Change and Read the Low Power Mode o f Module command Description The command requests the module at address AA to change and return the status of low power mode of mo dule Syntax $AAS(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 26 ADAM 4000 Series User’s Manual $AAXnnnn Name Watchdog Timer Setting command Description This co mmand se t the communication watchdog timer (WDT) cycle time. Syntax $AAXnnnn(cr) $ is a delimiter character.
Chapter 7 7- 27 ADAM 4000 Series User’s Manual $AAY Name Read C ommunication Watc hdog Ti mer Cycle Setting command Description This comman d read the setting of communication watchdog timer (WDT) cycle tim e. Syntax $AAY(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 28 ADAM 4000 Series User’s Manual 7.2 Counter/Frequenc y Module Co mmand 7.2.1 Configuration, Counter Input and Display Command Set Comm.
Chapter 7 7- 29 ADAM 4000 Series User’s Manual %AANNTTC CFF Name Configuratio n command Description Sets the address, input mode, baud rate, checksum status and frequency gate time for a specified coun ter/frequency module Syntax %AANNTT CC F F (cr) % is a delimiter char acter.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 30 ADAM 4000 Series User’s Manual %AANNTTC CFF Response !AA(cr) if the comm and is valid. ?AA(cr) if an invalid param eter was entered or the INIT* terminal was no t grounded when chan ging baud r ate or checksum setting were attem pted.
Chapter 7 7- 31 ADAM 4000 Series User’s Manual $AA2 Name Configuration Status comm and Description The command requests the return of the configu ration data from the co unte r/frequenc y module a t addre ss AA . Syntax $AA2(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 32 ADAM 4000 Series User’s Manual $AAF Name Read Version command Description The command requests the analog input module at address AA to return the version co de of its firmware. Syntax $AAF (cr) $ is a delimiter character.
Chapter 7 7- 33 ADAM 4000 Series User’s Manual $AAM Name Read Module Name comm and Description The command requests the coun ter/frequency module at address AA to return its na me Syntax $AAM (cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address that you will acces s to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 34 ADAM 4000 Series User’s Manual $AABS Name Set Input Mode co mmand Description Set the input signal mode of the sp ecified coun ter/ frequency modu le to either non-isolated (TTL) o r photo-isolated.
Chapter 7 7- 35 ADAM 4000 Series User’s Manual $AAB Name Read Input M ode command Description R ead the input m ode of the specified counter/frequenc y module. Syntax $AAB(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address that you will acces s to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 36 ADAM 4000 Series User’s Manual #AAN Name Read Counter or Frequency Value comm and Description Instructs the addressed counter/frequency module at address AA to re ad the counter or fr equency value of counter 0 or counter 1 and return the acquired data.
Chapter 7 7- 37 ADAM 4000 Series User’s Manual $AA8V Name Select LED Data Origin command Description Select whether LED will dis play data from either the hos t computer or the counter/frequency module directly. Syntax $AA8V(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 38 ADAM 4000 Series User’s Manual $AA8 Name Read LED Data Origin command Description R ead the LED Data Origin status which determ ines whether LED will display data from either the hos t computer or the counter/frequency module directly.
Chapter 7 7- 39 ADAM 4000 Series User’s Manual $AA9(data) Name Send Data to L ED comm and Description The host computer sends data to the addressed module to display on its LED. Syntax $AA9(data)(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address that you will acces s to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 40 ADAM 4000 Series User’s Manual 7.2.2 Counter Setup Com m and Set Command Syntax C ommand Name Description I/O Module $AAAG Set Gate M.
Chapter 7 7- 41 ADAM 4000 Series User’s Manual $AAAG Name Set Gate Mode comm and Description R equest the specified cou nter/frequency module to set its gate to one of the th ree s tates, high , low o r dis abled. Syntax $AAAG(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 42 ADAM 4000 Series User’s Manual $AAA Name Read Gate Mode command Description R equest the specified counter/frequency module to return its gate status. Syntax $AAA(cr) $ is a delimiter character.
Chapter 7 7- 43 ADAM 4000 Series User’s Manual $AA3N(data) Name Set Maxim um Counter Value com mand Description Set the maximum value for either counter 0 or counter 1 of a specified counter /frequency module. Syntax $AA3N(data)(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 44 ADAM 4000 Series User’s Manual $AA3N Name Read Maximum Counter Value command Description R ead the maximum value of counter 0 or counter 1 for a specified counter /frequency module . Syntax $AA3N(cr) $ is a delimiter character.
Chapter 7 7- 45 ADAM 4000 Series User’s Manual $AA5NS Name Start/Stop Counter command Description R equest the co unter/frequency modu le to start or stop th e counting for either counter 0 or counter 1. Syntax $AA5NS(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 46 ADAM 4000 Series User’s Manual $AA5N Name Read Counter Start/Stop Status comm and Description Requests the addressed counter/frequency mod ule to indicate whether counter 0 or counter 1 is active.
Chapter 7 7- 47 ADAM 4000 Series User’s Manual $AA6N Name Clear Counter command Description C lears the counter 0 or counter 1 of the sp ecified counter/frequency module. Syntax $AA6N(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address that you will acces s to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 48 ADAM 4000 Series User’s Manual $AA7N Name Read/Clear Overflow Flag c ommand Description The command requests the module to return the status of the overflow flag for either counter 0 or coun ter 1.
Chapter 7 7- 49 ADAM 4000 Series User’s Manual 7.2.3 Digital Filter and Programmable Threshold Command Set Command Synta x Command Name Description I/O Module $AA4S Enable/D isable Digital Filter En.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 50 ADAM 4000 Series User’s Manual $AA4S Name Enable/Disable Digital Filter command Description Enables or d isables the digita l filter of the counter / frequency m odule. Syntax $AA4S(cr) $ is a delimiter character.
Chapter 7 7- 51 ADAM 4000 Series User’s Manual $AA4 Name Read F ilter Status co mmand Description Read the digital filter sta tus of the addr essed counter/ frequency m odule. Syntax $AA4(cr) $ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address that you will acces s to.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 52 ADAM 4000 Series User’s Manual $AA0H(data) Name Set Minimum In put Signal W idth at High Lev el command Description Set the minimum input signal width at high level for a specified counter/fre quency module to filter the noise.
Chapter 7 7- 53 ADAM 4000 Series User’s Manual $AA0H Name Read Minimum Inp ut Signal Width at High Level command Description Read the minimum input signal width at high level for a specified counter /frequency module . Syntax $AA0H(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 54 ADAM 4000 Series User’s Manual $AA0L(dat a) Name Set Minimum In put Signal W idth at Low Level comm and Description Set the minimum input signal width at low level fo r a specified counter/f requency module to filter noise.
Chapter 7 7- 55 ADAM 4000 Series User’s Manual $AA0L Name Read Minimum Input Signal Width at Low Lev el command Description Read the minimum in put signal width at lo w level for a specified counter/f requency module to filter noise. Syntax $AA0L(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 56 ADAM 4000 Series User’s Manual $AA1H(data) Name Set Non-isol ated High Tr igger Level command Description Set the high trigger level for non-isolated input signals for a specified counter /frequency module .
Chapter 7 7- 57 ADAM 4000 Series User’s Manual $AA1H Name Read Non-isolated High Trigger Level command Description Read the high trigger level for non-isolated input signals of a specified counter /frequency module. Syntax $AA1H(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 58 ADAM 4000 Series User’s Manual $AA1L(data) Name Set Non-isol ated Low Trig ger Level comm and Description Set the low trigger level of non-isolated inp ut signals for a specified counter /frequency module .
Chapter 7 7- 59 ADAM 4000 Series User’s Manual $AA1L Name Read Non-isolated Low Trigg er Level command Description R ead the low trig ger level for non-isolated input signals of a specified c ounter/freque ncy module. Syntax $AA1L(cr) $ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 60 ADAM 4000 Series User’s Manual 7.2.4 Digital Output and Alarm Command Set Command Synta x Command Nam e Descripti on I/O Module @AAPN.
Chapter 7 7- 61 ADAM 4000 Series User’s Manual Command Synta x Command Name Description I/O Module @AAEA T E nable Alar m of Counte r 0 Enable t he alarm of counter 0 in either momentary or latching.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 62 ADAM 4000 Series User’s Manual @AAPN(data) Name Set Initial C ount Value of Counter 0 or 1 command Description Set the initial count value for counter 0 or 1 of the specified counter module at address AA.
Chapter 7 7- 63 ADAM 4000 Series User’s Manual @AAGN Name Read Initial Count Value of Counte r 0 or 1 command Description Read the initial count valu e of counter 0 or 1 of the specified counter module at address AA. Syntax @AAGN(data)(cr) @ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 64 ADAM 4000 Series User’s Manual @AAEAN Name Enable Ala rm co mmand Description Enable Alarm for the specified counter. Syntax @AAEAN (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of the m odule.
Chapter 7 7- 65 ADAM 4000 Series User’s Manual @AADAN Name Disable Alarm command Description Disable Alarm for the specified cou nter. Syntax @AADAN (cr ) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of the m odule.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 66 ADAM 4000 Series User’s Manual @AAPA(data) @AASA(data) Name Set Alarm Limit Value of Counter 0 or 1 command Description Set the Alarm limit value of counter 0 o r 1 of the specified counter module at address AA.
Chapter 7 7- 67 ADAM 4000 Series User’s Manual @AARP @AARA Name Read Alarm Limit Value of Counter 0 or 1 command Description Read the alarm limit value of counter 0 or 1 of the specified counter module at address AA. Syntax @AARP(data)(cr) @AARA(data)(cr) @ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 68 ADAM 4000 Series User’s Manual @AADO Name Set Digital Output co mmand Description Set the values of the module’s two digital outputs (ON or OFF). Syntax @AADO(data)(cr) @ is a delimiter character.
Chapter 7 7- 69 ADAM 4000 Series User’s Manual @AADI Name Read Digital Output and Alarm State command Description The addressed counter module is instructed to return the value of its two digital output chann els and the state of its alarm. Syntax @AADI(cr) @ is a delim iter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 70 ADAM 4000 Series User’s Manual @AADI Example command: @15DI(cr ) response: !151000 0(cr) The counter modu le at address 15h is instructed to return digital output data and a larm status.
Chapter 7 7- 71 ADAM 4000 Series User’s Manual @AAEAT Name Enable Ala rm co mmand Description The counter module is instructed to enable its alarm for counter 0 in either Latching or Momentary mod e. Syntax @AAEAT(cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of the m odule.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 72 ADAM 4000 Series User’s Manual @AADA Name Disable Alarm command Description Disable all alarm functions for counter 0 of the addressed counter m odule. Syntax @AADA (cr) @ is a delimiter character.
Chapter 7 7- 73 ADAM 4000 Series User’s Manual @AACA Name Clear Latch Alarm comm and Description Both alarm states (High and Low) of the ad dressed counter module are set to O FF, no alarm. Syntax @AACA (cr) @ is a delimiter character. AA (range 00-FF) r epresents the 2- character hexadecimal address of the m odule.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 74 ADAM 4000 Series User’s Manual @AAPA(data) Name Set Low -alarm C ount Valu e for C ounter 0 c ommand Description Set the low-alarm count value for counter 0 of the specifie d counter m odule.
Chapter 7 7- 75 ADAM 4000 Series User’s Manual @AASA(data) Name Set Hi-alarm Count Value of Counter 0 command Description Set the high-alarm count value for counter 0 of the specified counter module. Syntax @AAS A(da ta)(cr) @ is a delimiter character.
Digital I/O and Relay Output Counter/Frequency Command Set 7- 76 ADAM 4000 Series User’s Manual @AARP Name Read Low-alarm Count Value of Coun ter 0 command Description R ead the low-alarm value of counter 0 of the specified counter m odule. Syntax @AARP(cr) @ is a delimiter character.
Chapter 7 7- 77 ADAM 4000 Series User’s Manual @AARA Name Read High-alarm Count Value for Counter 0 Description R eques ts the addres sed coun ter mo dule to return i ts high-alarm count valu e of counter 0. Syntax @AARA(cr) @ is a delimiter character.
Calibration 8.
Calibration 8- 2 ADAM 4000 Series User’s Manual Analog input/output modules are calibrated when you receive them. However, calibration is sometim es required. No scr ewdriver is necessary because calibra tion is done in so ftware. Calibr ation parameters ar e stored in the ADAM modu le’s onboard EEPROM.
Chapter 8 Chapter 8 Ca libration 8- 3 4. Execute the Offset Calibration command. This is also done through the ADAM utility software. (Please see “Offset Calibration” option in the Calibration sub-menu of the ADAM utility software). Figure 8-2 Zero Calibration 5.
Calibration 8- 4 ADAM 4000 Series User’s Manual 6. This step is only for ADAM 40 11, 4011D, 4018, 4018+ , 4018M, 4019, 4019+. Execute the CJC (cold jun ction sensor) calibration command. Thi s is also done through the ADAM utility software. (Please see “CJC Calibration” optio n in the Calibration sub-menu of the ADAM utility sof tware).
Chapter 8 Chapter 8 Ca libration 8- 5 8.2 Analog Input Resi stance Calib ration Model: AD AM-4013 1. Apply power to the module and let it warm up for about 30 minutes. 2. Assure that the module is correctly installed and is pro perly configured for the inp ut range that you want to calibra te.
Calibration 8- 6 ADAM 4000 Series User’s Manual Table 8-2 Calibration Resistance Module Input Range Code (Hex) Input R ange S pan Calibration Resistance Offset Calibration Resistance 4013 2 0 Pt, -100~100 ℃ a = 0.00385 140 Ω 60 Ω 21 Pt, 0~100 ℃ a = 0.
Chapter 8 Chapter 8 Ca libration 8- 7 8.3 Analog Input Thermistor module Calibration Model: ADAM-4015T If you select the range “Thermistor 3K 0~100C”, please follow the calibration step s as below. 1. Short the INIT* pi n to GND and then power u p ADAM-4015T.
Calibration 8- 8 ADAM 4000 Series User’s Manual 3. Set the resistance to “0” and click on “Save” 4. Click on “Z ero Cal. ” 5. Apply 200.0 ohms resistor with 0.
Chapter 8 Chapter 8 Ca libration 8- 9 6. Click on “Spa n C al.” 7. Apply 10K ohm s resistor with 0.01% accurac y to CH0 and then Click on “Save” 8.
Calibration 8- 10 ADAM 4000 Series User’s Manual If you sele ct the ra nge “Th ermis tor 10K 0~100C ”, plea se f ollow the calibration steps as below.
Chapter 8 Chapter 8 Calibration 8- 11 3. Set the resistance to “0” and click on “Save” 4. Click on “Z ero Cal. ” 5. Apply 800.0 ohms resistor with 0.
Calibration 8- 12 ADAM 4000 Series User’s Manual 6. Click on “Spa n C al.” 7. Apply 30K ohm s resistor with 0.01% accurac y to CH0 and then Click on “Save” 8.
Chapter 8 Chapter 8 Calibration 8- 13 8.4 Analog Output Calibration Model: AD AM-4021/402 4 The output current of analo g output modules can be calibrated by using a low and high calibrating value. The analog outp ut modules can be configured in one of the two rang es, 0-20 mA and 4-20 m A.
Calibration 8- 14 ADAM 4000 Series User’s Manual 4. Issue the An alog Data Out comman d to the m odule with an output value of 4 mA. 5. Check the act ual output value at the termin als. If it does no t equal to 4 mA, use the “Trim” option in the “Calibrate” sub menu to change the actual output.
Chapter 8 Chapter 8 Calibration 8- 15 Module: AD AM-4016 1. Apply power to the strain gauge input m odule and let it warm up for about 30 minutes. 2. Ass ure that the module is correctly insta lled. Then, connect a voltmeter to th e screw terminals of the module.
Calibration 8- 16 ADAM 4000 Series User’s Manual 4. Execute the Span Calibration comm and. This can be don e through the ADAM utility software. (Ple ase s ee "A/O 10 V Calibra tion" option in the Calibration sub-menu of th e ADAM utility software.
Technical Specificati ons A.
Technical Specificati ons A- 2 ADAM 4000 Series User’s Manual A.1 ADAM-4011 Thermo couple Inp ut Module Table A- 1 ADAM-4011 Specifications T/C channel number 1 Input range J, K, T, E, R, S a nd B Th ermoc oupl e ±15 mV, ±50 mV, ±100 mV, ±500mV, ±1 V, ±2.
Appendix A Appendix A Technical Spec ification A - 3 Table A- 2 ADAM-4011 Rang e Accu racy for Thermocouple Input Range Code (Hex) Input Range Typical Accuracy Maximum Error Units 0E J th ermoc ouple 0 to760 ℃ ±0.5 ±0.75 ℃ 0F K thermocouple 0 to 1370 ℃ ±0.
Technical Specificati ons A- 4 ADAM 4000 Series User’s Manual Figur e A-1 ADAM-4011 Funct ion Di agram.
Appendix A Appendix A Technical Spec ification A - 5 A.2 ADAM-4011D Thermocouple I nput Module with LED Display Table A-3 ADAM-4011D Specifications T/C channel number 1 Input range J, K, T, E, R, S and B Ther mocouple ±15 mV, ±50 mV, ±100 mV, ±500mV, ±1 V, ±2.
Technical Specificati ons A- 6 ADAM 4000 Series User’s Manual Table A- 4 AD AM-4 011D Range Ac curacy for T hermocouple Input Range Code (Hex) Input Range Typical Accuracy Maximum Error Units 0E J thermocouple 0 to 760 ℃ ±0.5 ±0.75 ℃ 0F K thermocouple 0 to 1370 ℃ ±0.
Appendix A Appendix A Technical Spec ification A - 7 Figure A-2 ADAM-4011D Fun ction Diagram.
Technical Specificati ons A- 8 ADAM 4000 Series User’s Manual A.3 ADAM-4012 Analog Input Module Table A- 5 ADAM-4012 Specifications AI channel number 1 Input range ±150 mV, ±5 00mV, ±1 V, ±5 V, ±10 V and ±20mA Output speed (in bps) Maximum di stance RS-485 (2-wire) 1200, 2400, 4800, 9 600, 19.
Appendix A Appendix A Technical Spec ification A - 9 Figure A-3 ADAM-4012 Function Diagram.
Technical Specificati ons A- 10 ADAM 4000 Series User’s Manual A.4 ADAM-4013 RTD Input Module Table A- 6 ADAM-4013 Specifications RTD chann el n umber 1 Input type Pt or Ni RTD Output speed (in bps) Maximum di stance RS-485 (2-Wire) 1200, 2400, 4800, 9 600, 19.
Appendix A Appendix A Technical Spec ification A - 11 Figure A-4 ADAM-4013 Function Di agram.
Technical Specificati ons A- 12 ADAM 4000 Series User’s Manual A.5 ADAM-4016 Analog Input/Outpu t Module Table A- 7 ADAM-4016 Specifications AI channel number 1 AI range ±15 mV, ±50 mV, ±100 mV, ±500 mV and ±20 mA Output Speed (bps) Maximum distance RS-485 (2-wire) 1200, 2400, 4800, 9 600, 19.
Appendix A Appendix A Technical Spec ification A - 13 Figure A-5 ADAM-4016 Function Diagram.
Technical Specificati ons A- 14 ADAM 4000 Series User’s Manual A.6 ADAM-4017/4017+ 8-Cha nnel Analog Input Module Table A-8 ADAM-4017/4017+ Specification s AI chann el number ADAM-4017: 6 differenti.
Appendix A Appendix A Technical Spec ification A - 15 Figure A-6 ADAM-4017/4017+ F uncti on Di agram.
Technical Specificati ons A- 16 ADAM 4000 Series User’s Manual A.7 ADAM-4018/4018+ 8-channel Analog Inpu t Module Table A-9 ADAM-4018/4018+ Specification s AI chann el number ADAM-4018: 6 differenti.
Appendix A Appendix A Technical Spec ification A - 17 Table A-10 ADAM-4018/4018+ Range Accu racy for Thermocouple Input Range Code (Hex) Input Range Typical Accuracy Maximum Error Units 0E J thermocouple 0 to 760 ℃ ±1.0 ±1.5 ℃ 0F K thermo couple 0 to 1370 ℃ ±1.
Technical Specificati ons A- 18 ADAM 4000 Series User’s Manual Figure A-7 ADAM-4018/4018+ F unct ion Diag ram.
Appendix A Appendix A Technical Spec ification A - 19 A.8 ADAM-4018M 8-channel Analog Input Dat a Logger Table A- 1 1 ADAM-4018M Specifications AI channel number 6 differential and 2 single-ended Inpu.
Technical Specificati ons A- 20 ADAM 4000 Series User’s Manual Table A-12 ADAM-4018M Range Acc uracy for Ther mocouple Input Range Code (Hex ) Input Range Typical Accuracy Maximum Error Units 0E J thermocouple 0 to 760 ℃ ±1.0 ±1.5 ℃ 0F K thermocouple 0 to 1370 ℃ ±1.
Appendix A Appendix A Technical Spec ification A - 21 Figure A-8 ADAM-4018M Function D iagram.
Technical Specificati ons A- 22 ADAM 4000 Series User’s Manual A.9 ADAM-4019+ 8-Channe ls Universal Analog Inpu t Module Table A- 1 3 ADAM-4019+ Specific ation s AI channel number 8 Input type V, mV, mA and T/C Input range V: ± 1 V , ± 2.
Appendix A Appendix A Technical Spec ification A - 23 Figure A-9 ADAM-4019+ Function Diagram.
Technical Specificati ons A- 24 ADAM 4000 Series User’s Manual A.10 ADAM-4021/4024 Anal og Output Module Table A-14 ADAM-4021/4024 Spe cification s Input speed (bps) Maximum di stance RS-485 (2-wire) 1200, 2400, 4800, 9 600, 19.2K, 38.4K, 57.6K, 115.
Appendix A Appendix A Technical Spec ification A - 25 Support protoc ol ADAM-4021: ADAM ASCII ADAM-4024: ADAM ASCII and MODBUS/RTU Watchdog timer ADAM-4021: System (1.6 second) ADAM-4024: System (1.6 second) and c ommunication Power supply +10 to +30 V DC (non-regulated) Power consumption ADAM-4021: 1.
Technical Specificati ons A- 26 ADAM 4000 Series User’s Manual Figure A-10 ADAM-4021 Function Diagram.
Appendix A Appendix A Technical Spec ification A - 27 Figure A-11 ADAM-4024 Function Diagram.
Technical Specificati ons A- 28 ADAM 4000 Series User’s Manual A.11 ADAM-4050 Digital I/O Mod ule Table A-15 ADAM-4050 Specifications DI/O channel number 7 digital inputs 8 digital outputs Input/Output speed (bps) Maximum di stance RS-485 (2-wire) 1200, 2400, 4800 , 9600, 19.
Appendix A Appendix A Technical Spec ification A - 29 Figure A-12 ADAM-4050 Function D iagram.
Technical Specificati ons A- 30 ADAM 4000 Series User’s Manual A.12 ADAM-4051/4052 Isolat ed Digital In put Modu le Table A-16 ADAM-4051/4502 Specification s DI/O channel number ADAM-4501: 16 digit .
Appendix A Appendix A Technical Spec ification A - 31 Watchdog timer ADAM-4051: System (1.6 second) and communication ADAM-4052: System (1.6 second) Power supply +10 to +30 V DC (non- regul ated) Power consumption ADAM-4051: 1.0 W @ 24 V DC ADAM-4052: 0.
Technical Specificati ons A- 32 ADAM 4000 Series User’s Manual Figure A-13 ADAM-4051/ 4052 Function Diagram.
Appendix A Appendix A Technical Spec ification A - 33 A.13 ADAM-4053 16-chann el Digital Input Module Table A-17 ADAM-4053 Specifications DI/O channel number 16 digital inputs Input/Output speed (bps) Maximum di stance RS-485 (2-wire) 1200, 2400, 4800, 9600, 19.
Technical Specificati ons A- 34 ADAM 4000 Series User’s Manual Figure A-14 A DAM-4053 Function Diagram.
Appendix A Appendix A Technical Spec ification A - 35 A.14 ADAM-4055 Isola ted Di git al In put/O utput M odule Table A-18 ADA M-4055 Specifications DI/O channel number 8 digital inputs 8 digital outputs Input/Output speed (bps) Maximum di stance RS-4 85 (2-wire) 1200, 2400, 4800, 96 00, 19.
Technical Specificati ons A- 36 ADAM 4000 Series User’s Manual Figure A-15 ADAM-4055 Function D iagram.
Appendix A Appendix A Technical Spec ification A - 37 A.15 ADAM-4056S 12-channel Sink Type Isol ate d Digita l Output Module Table A-19 ADAM-4056S S pecification s DO channel number 12 digi tal outp uts (sink type ) Input/Output speed (bps) Maximum di stance RS-4 85 (2-wire) 1200, 2400, 4800, 96 00, 19.
Technical Specificati ons A- 38 ADAM 4000 Series User’s Manual Figure A -16 ADAM-4056S Function Diagram.
Appendix A Appendix A Technical Spec ification A - 39 A.16 ADAM-4056SO 12-c hannel Source Type Isolated Digita l O utpu t Modu le Table A- 20 ADAM-4056SO Specifications DO channel number 12 digi tal outp uts (sourc e type ) Input/Output speed (bps) Maximum di stance RS-4 85 (2-wire) 1200, 2400, 4800, 96 00, 19.
Technical Specificati ons A- 40 ADAM 4000 Series User’s Manual Figure A-17 ADAM-4056SO Function Diagram.
Appendix A Appendix A Technical Spec ification A - 41 A.17 ADAM-4060 Relay Output Module Table A-21 ADAM-4060 Spec ifications DO channel number 4 channel relay (2 form A, 2 fo rm C ) Input speed (bps) Maximum di stance RS-485 (2-wire) 1200, 2400, 4800, 9600, 19.
Technical Specificati ons A- 42 ADAM 4000 Series User’s Manual Figure A-18 A DAM-4060 Function Diagram.
Appendix A Appendix A Technical Spec ification A - 43 A.18 ADAM-4068/4069 8-chann e l Relay Outp ut M odu le Table A-22 ADAM-4068/4069 Specification s DO channel number 8 channel relay (4 form A, 4 fo rm C ) Contact rating (Res istive) ADAM-4068: AC: 0.
Technical Specificati ons A- 44 ADAM 4000 Series User’s Manual Figure A-19 ADAM-4068/ 4069 Function Diagram RS-4 85 Communication Microc ontrol ler 8-Channel Relay Output Power Converter Rect & .
Appendix A Appendix A Technical Spec ification A - 45 A.19 ADAM-4080 Counter/F requency Input Module Table A-23 ADAM-4080 Spec ifications Input channel number 2 independent 32-bit counters Input frequenc y 50 kHz maximum Input mode Isolated or non-isolated Isolation input level Logic leve l 0 Logic al level 1 +1 V maximum +3.
Technical Specificati ons A- 46 ADAM 4000 Series User’s Manual Figure A-20 ADAM-4080 Function Diagram.
Appendix A Appendix A Technical Spec ification A - 47 A.20 ADAM-4080D Counter/Freque ncy Input Module with LED Dis play Table A-24 ADAM-4080D S pecifications Input channels 2 independent 32-bit count ers Input fre quency 50 kHz maximum Input mode Isolated or non-isolat ed Isolation input level Logic level 0 Logical level +1 V max +3.
Technical Specificati ons A- 48 ADAM 4000 Series User’s Manual Figure A-21 ADAM-4080D Fu nct ion Di agram.
Data Formats and I/O Ranges B.
Data Formats and I/O Ranges B- 2 ADAM 4000 Series User’s Manual B.1 Analog Input Formats The ADAM analog input modules c an be configured to transm it data to the host in on e of the following data formats: -Engineering Units -Percent of FSR -Twos complement hexadecimal -Ohm s B.
Appendix B Appendix B Data Formats and I/O Ranges B - 3 B.1.2 Percent of FSR This mode is used by setting bits 0 and 1 of the data format/checksum /integration time p arameter to 01. The format used in Percent of FSR consi sts of a pl us (+) or mi nus (-) si gn fol lowe d by five de cim al digits including a decimal point.
Data Formats and I/O Ranges B- 4 ADAM 4000 Series User’s Manual The percentage is re lated to the full span of the configured range. F or instance, a nickel RTD is specified for -80 o C to +100 o C. Then, the lower v alue of -80 o C equals to 0% of span and the uppe r val ue of + 100 o C equals to 100% of sp an.
Appendix B Appendix B Data Formats and I/O Ranges B - 5 Thermocouple Type Temperature Range (Degree s) Temperature Range (Hex) J 0° C to 760° C 0000h - 7FFFh T -100° C to 400° C E000h - 7FFFh R 50.
Data Formats and I/O Ranges B- 6 ADAM 4000 Series User’s Manual B.2 Analog Input Ranges Range Code (hex) Input R ange Descri ption Data Formats +F.S. Zero -F.S. Displayed Resolution 00 ± 15 mV Enginee ring Units +15.000 ±00. 000 -15. 000 1 µv % of FSR +100.
Appendix B Appendix B Data Formats and I/O Ranges B - 7 Range Code (hex) Input Ran ge Descripti on Data For mats +F.S. Zero -F.S. Displayed 08 ± 10 mV Engineering Units +10.00 0 ±00.000 -10.00 0 R esolution % of FSR +100.00 ±000 .00 -100.0 0 1 µv Twos Co mp l e me n t 7FFF 0000 8000 0.
Data Formats and I/O Ranges B- 8 ADAM 4000 Series User’s Manual Range Code (hex) Input R ange Descri ption Data For mats Maxi mum Specif ied Signal Min i mum Specifie d Signal Displayed Resoluti on 0F Type K Therm ocouple 0°C to 1370°C Engineering Units +1370.
Appendix B Appendix B Data Formats and I/O Ranges B - 9 Range Code (hex) Input R ange Description Data Formats Max imu m Specitied Signal Min imu m Specitied Signal Displayed Resoluti on 22 100.00 Ω Platinu m RTD α = .003 85 0°C to 20 0°C Enginee ring Units +200.
Data Formats and I/O Ranges B- 10 ADAM 4000 Series User’s Manual Range Code (hex) Input Range Descripti on Data Formats Maxi mu m Specitied Signal Minimum Specitied Signal Displayed Resolution 29 100.00 Ω Nickel RTD α = .00392 0°C to 100 °C Engineer ing Units +100.
Appendix B Appendix B Data Formats and I/O Ranges B - 11 B.3 Analog Output Formats You can configure ADAM analog output modules to receive data from the host in on e of the following data formats: -Engineering Units -Percent of FSR -Twos complement hexadecimal Data for ADAM modules can be used in an y one of the fo llowing data formats : B.
Data Formats and I/O Ranges B- 12 ADAM 4000 Series User’s Manual B.4 Analog Output Ranges Range Code (hex) Input Ra nge Descri ption Data Formats Max imu m Specitied Signal Minimum Specitied Signal Output Resolution 30 0 to 2 0 mA Engineer ing Units 20.
Technical Diagrams C.
Technical Diag rams C- 2 ADAM 4000 Series User’s Manual C.1 ADAM Dimensi ons Figure C-1 ADAM Modules Dim ensions.
Appendix C Appendix C Technical Diagrams C - 3 C.2 Install at ion C.2.1 DIN-Rail Mount ing Figure C-2 DIN-Ra il Adapter.
Technical Diag rams C- 4 ADAM 4000 Series User’s Manual Figure C-3 DIN-Rail Mounting.
Appendix C Appendix C Technical Diagrams C - 5 C.2.2 Panel Mounting Figure C -4 Panel Mounting Bracket Dimensions.
Technical Diag rams C- 6 ADAM 4000 Series User’s Manual Figu re C -5 Panel Mounting.
Appendix C Appendix C Technical Diagrams C - 7 C.2.3 Piggyback Stack Figure C-6 Piggyback Stack.
Utility Software D.
Utili ty So ftware D- 2 ADAM 4000 Series User’s Manual D.1 ADAM-4000 Utility Sof tware Together with the ADAM modu les you will find a utility d isk containing utility software with the following ca.
Appendix D Appendix D U t ility Soft ware D - 3 NOTICE: When changing confi gurat ion, ca libration or alarm parameters, you should always make sure that a window appears notifying you th at the target module ha s confirmed the changes.
Utili ty So ftware D- 4 ADAM 4000 Series User’s Manual After you have made all necessary changes to the module c onfiguration, the utility will d isplay th e process data automatically. Calibration Please note only analog input and output m odules can be ca librated.
Appendix D Appendix D U t ility Soft ware D - 5 You can type the ADAM ASCII command in the text box and click Send bu tton for testing the command s which ar e listed in Chapter 4 Comm and Set. Figure D-4 Terminal Function Notice: User can ref er our help f ile to see more details f or explanation of Utility operation.
Utili ty So ftware D- 6 ADAM 4000 Series User’s Manual D.2 The p roc edure f or AD AM-40 0 0 ser ies in stalla t ion gu i de When user fi rst tim e gets AD AM-4 000 m odul es, he c an re fer fol lowin g procedure to c onfigure and operate.
Appendix D Appendix D U t ility Soft ware D - 7 INIT* state defaults: Baud rate: 960 0 Address : 00h Checksum: disabled Forcing the module in INIT* state does not change any pa rameters in the module’s EEPROM.
Utili ty So ftware D- 8 ADAM 4000 Series User’s Manual 6. Use software to configure settings According to user’s application to set parameter like as address, baudrate, data format, checksum, protocol…and so on. Changing Baud rate and Checksum Refer to C hapt er 2 sect ion 2.
RS-485 Network E.
RS-485 Network E- 2 ADAM 4000 Series User’s Manual EIA RS -485 is industry ’s most w idely used bid irecti onal, balanced transmission line standard. It is sp ecifically developed f or industrial multi-drop systems that should be able to transmit and receive data at high rates or over long distances.
Appendix E Appendix E RS-485 Network E - 3 E.1 Basi c Net wor k Lay out Multi-drop RS-485 implies that there are two m ain wires in an segment. The connected mo dules tap from these two lines with so called drop cables. Thus all connections are p arallel and connecting or disconnecting of a node doesn ’t affect the network as a wh ole.
RS-485 Network E- 4 ADAM 4000 Series User’s Manual Sta r L ay o ut In this scheme the repeaters are connected to drop-down cables from the main wires of the first se gment.
Appendix E Appendix E RS-485 Network E - 5 E. 2 Line Termination Each discon tinuity in impedance cau ses reflections and distortion. When an imp edance discontinuity occurs in th e transmission line the immediate effect is signal reflection. This will lead to signa l distortion.
RS-485 Network E- 6 ADAM 4000 Series User’s Manual Figure E-5 Termination resistor locations Because each input is biased to 2.4 V, the nomin al common mode voltage of balanced RS-485 s ystems, the 18 k Ω on the input can be taken as being in series across the inp ut of each individual receiver.
Appendix E Appendix E RS-485 Network E - 7 E.3 RS-485 Data Flow Contr ol The RS-485 standar d uses a sing le pair of wires to send and receiv e data. This line sharing requires som e method to con trol the direction of the data flow. RTS (Request To Sent) and CTS (Clear To Sen t) are the most commonly used m ethod.
How to us e the C heck sum fe at ur e F.
How to use the Checksum feature F- 2 ADA M 40 00 S eri es Use r’s M anu al A checksum helps you de tect communication errors between the host and module. This feature adds two extra checksum characters to the command or response str ing; therefore, it reduces the throughput .
Appendix F Appendix F How to use the Checksum f eature F - 3 Example 2 This example explains how to calculate the checksum value of a Read High alarm l imit co mmand st ring : Case 1. (If the Checksum featur e is disa ble d ) Command: $07R H(cr ) Respo nse : !07+2.
How to use the Checksum feature F- 4 ADA M 40 00 S eri es Use r’s M anu al Table F-1 Printa ble ASCII Characters HEX AS CII HE X ASCII HEX ASCII HEX ASCII 21 ! 40 @ 5F _ 7E ~ 22 "" 41 A 60.
ADAM-4000 I/O Modbus Mapp ing Table G.
ADAM-4000 I/O Modbus Mapping Table G- 2 ADAM 4000 Series User’s Manual The model list of AD AM-4000 I/O series support Modbus protocol Model Description 1 ADAM-4015 6-channel RTD Input Module ADAM-4.
Appendix G Appendix G ADAM-4000 I/ O Mo dbus Mapping Table G - 3 1. ADAM-4015 6-channel RTD Input Module and ADAM-4015T 6-channel Thermistor Input Module ADDR 0X Channel Item Attribute Mem o 00201 0 B.
ADAM-4000 I/O Modbus Mapping Table G- 4 ADAM 4000 Series User’s Manual 2. ADAM-4018+ 8-channel Th ermocouple Input Module ADDR 0X Channel Item Attrib ute Mem o 00201 0 Bur n-out Signal R 1:Burn-out .
Appendix G Appendix G ADAM-4000 I/ O Mo dbus Mapping Table G - 5 3. ADAM-4017+ 8-channel Analog Inpu t Module ADDR 4X Channel Item Attribute Memo 40001 0 Current Value R 40002 1 Current Value R 40003 .
ADAM-4000 I/O Modbus Mapping Table G- 6 ADAM 4000 Series User’s Manual 4. ADAM-4019+ 8-Channels Universal Analog Input Module ADDR 0X Channel Item Attrib ute Mem o 00201 0 Burn-out Signal R 0: Non 1.
Appendix G Appendix G ADAM-4000 I/ O Mo dbus Mapping Table G - 7 5. ADAM-4024 4-channel Analog Output Module ADDR 0X Channel Item Attribute Memo 00001 0 Emergency DI Input Flag R 00002 1 Emergency DI .
ADAM-4000 I/O Modbus Mapping Table G- 8 ADAM 4000 Series User’s Manual 6. ADAM-4051 16-channel Isolated Digital Input with LED Module ADDR 0X Channel Item Attribute Mem o 0000 1 0 DI I npu t Si gna .
Appendix G Appendix G ADAM-4000 I/ O Mo dbus Mapping Table G - 9 7. ADAM-4055 16-channel Isolated Digital I/O with LED Module ADDR 0X Channel Item Attr ibute Memo 00001 0 DI Input Signal R 00002 1 DI .
ADAM-4000 I/O Modbus Mapping Table G- 10 ADAM 4000 Series User’s Manual 8. ADAM-4056S 12 channel Sink-type Isolated Digital Output Module ADDR 0X Channel Item Attribute Memo 00017 0 Digital O utput .
Appendix G Appendix G ADAM-4000 I/ O Modbus Ma pping Table G- 11 9. ADAM-4056SO 12 channel Source-type Isolated Digit al Output Module ADDR 0X Channel Item Attribute Memo 00017 0 Digital Output Value .
ADAM-4000 I/O Modbus Mapping Table G- 12 ADAM 4000 Series User’s Manual 10. ADAM-4068 8 Relay Output Module ADDR 0X Channel Item Attribute Memo 00017 0 R elay O ut put Valu e R/W 00018 1 R elay O ut.
Appendix G Appendix G ADAM-4000 I/ O Modbus Ma pping Table G- 13 11. ADAM-4069 8 Power Relay Output Module ADDR 0X Channel Item Attribute Memo 00017 0 R e la y O ut put Valu e R/W 00018 1 R elay O ut .
Changing Configurat io n to Modbus P rot ocol H.
Changing Configurati o n t o Modbus Prot ocol H- 2 ADAM 4000 Series User’s Manual The ADAM-4000 Modbus version modules may come from the factory set for which ADAM ASCII pr otocol are set as the default protocol. If the m odule is connected to a Modbus network, the Mod bus network may not r ecognize the m odule.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Advantech Data Acquisition Modules ADAM 4000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Advantech Data Acquisition Modules ADAM 4000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Advantech Data Acquisition Modules ADAM 4000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Advantech Data Acquisition Modules ADAM 4000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Advantech Data Acquisition Modules ADAM 4000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Advantech Data Acquisition Modules ADAM 4000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Advantech Data Acquisition Modules ADAM 4000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Advantech Data Acquisition Modules ADAM 4000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.