High Density Pulse Input Module
Cat. No. A8911






This product is not intended for life safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.

The A8911-23 is designed for pulse counting applications where large number of pulse output devices need to be connected to a Modbus network. The A8911-23 will count contact closures on 23 separate inputs and store the totalized pulse count internally using non-volatile memory. The pulse count totals are then read using the RS485/Modbus protocol. Applications include reading gas/water/electric meters in common building areas for energy information and reporting purposes.
Processor Arm7, field upgradeable firmware. LED 23 input status LEDs (red), 2 Modbus TX/RX (yellow), 1 power/alive status. (green) Protocols Modbus/RTU Power Supply 9VDC to 30VDC, 200mA, Required (not included) The unit is to be sourced by a NEC Class 2 power supply, or Listed ITE power supply marked LPS and rated from 9 to 30Vdc, 200 mA minimum but not to exceed 8A Serial Port1 RS-485 two wire, 19200 or 9600 baud. N81 Pulse Inputs1 23 independent pulse count inputs. Intended for use with isolated dry contact outputs. Pulse rate/width user selectable to 10hz, 50hz or 100hz. Pulse rate option: 10hz minimum pulse width 50ms Pulse rate option: 50hz, minimum pulse width 10ms Pulse rate option: 100hz, minimum pulse width 5ms Contact closure threshold 100 to 2.5k user selectable Pulse count values are stored in non-volatile memory. Isolation2: Pulse inputs, power input and RS485 are non-isolated. Environmental Pollution Degree 2, Altitude up to 2000M. For indoor and outdoor use when used in an appropriate enclosure. The A8911-23 must be mounted inside a NEMA rated electrical enclosure for safety and isolation requirements. North America: Indoor, temperature -30º - +70ºc, 0 - 95% humidity, non-condensing3
Safety UL61010 Recognized3
File: E320540 (Model A8911-23) EMC FCC CFR 47 Part 15, Class A EN 61000, EN 61326 Size 4.13” x 3.39” x 1.18” (105mm x 86mm x 30mm) Mass 3.7 oz (105 g)
1 inputs are intended for low voltage NEC Class 2 or equivalent outputs.
2 if the product is used in a manner not specified by the manufacture, the protection provided by the equipment may be impaired.
3 Devices manufactured before Nov 1, 2011 are rated to 0 ~ 50c, and are not UL recognized.

1 Wire connected to pulse meters inside high voltage panels should have an insulation rating in excess of the service voltage. Consult a licensed electrician and local building codes for further requirements that may apply.

3.1 Hardware Installation
1. Mount the A8911-23 on a DIN-Rail or appropriate mounting enclosure. 2. Attach the power supply to the input terminals on the A8911-23 module. 3. Turn on the power supply. Confirm the green Alive LED starts blinking. Turn off the power to the module. 4. Attach the RS485 +, - and shield wires to the A8911-23 module. Attach the other end of the RS485 line to the Modbus master device, such as an AcquiSuite. Be careful to observer polarity on both ends of the RS485 connection. RS485 wiring runs should be limited to 4000 ft.

+9 to +30VDC GND
A9811-23
NC RS485 Shield RS485 - RS485 + P23
Twisted Pair Shielded
GND

Wiring runs to pulse input terminals should be kept as short as possible. Wiring runs longer than 200 ft should be avoided. Wiring should avoid proximity to sources of electrical noise such as running in parallel to electrical cable, and VFD systems. 8. Power up the A8911-23. The Input LEDs for each connected input should now blink. The input LED will be on when the contacts are closed.

Modbus Address: Before the A8911-23 can be used, you must set the Modbus address of the A8911-23. This address must be unique among all Modbus devices in the system. The A8911-23 supports address 1 through 127.
Modbus
Address
Select an address and set the DIP switches to match.
The sum of the value of the switches is the address. In the example to the right, address 52 is set by placing switch 4, 16 and 32 to the on position.
Baud Rate: This option sets the serial port speed for the RS485 port. Set this option to [OFF] for 19200. Set the switch to [ON] for 9600 baud.
on

The device should power up and be ready in a few seconds. The LEDs should blink in the following manner.

Pulse count not incrementing:
Check the input LED for the specific input that is not working. The LED should blink when the pulse meter closes the contact output. If it is not blinking, try bridging the input terminals with a short piece of wire to confirm the LED comes on.
Try bridging the terminals at the other end of the pulse wiring run. This will confirm there are no breaks in the wire.
Verify the pulse output device is operating.
Disconnect the A8911-23 input and use a hand held digital meter and measure resistance of the pulse output device. Verify that the pulse output device is operational and the contact closure reads less than 1000 ohms when closed. For high resistance pulse devices such as intrinsic barriers, the “contact closure threshold” register may need to be configured to a larger value. The default is 1k however up to 2.5k is allowed. If using the AcquiSuite data acquisition server, use the advanced configuration page of the A8911-23 in the Modbus/device list to set this option.

The A8911-23 responds to the following Modbus/RTU functions: 0x11 Report slave id. 0x03 read holding registers (multiple) 0x06 preset single register
All Modbus registers are read-only unless otherwise noted. Registers listed as “NV” are options that are stored in non-volatile memory and will be preserved when power is removed from the device.
Modbus 40xxx registers (read registers) Data points: offset point type desc 0 40001 UINT32 pulse count 1 MSW (NV Mem, all pulse counts) 1 40002 UINT32 pulse count 1 LSW 2 40003 UINT32 pulse count 2 MSW 3 40004 UINT32 pulse count 2 LSW 4 40005 UINT32 pulse count 3 MSW 5 40006 UINT32 pulse count 3 LSW 6 40007 UINT32 pulse count 4 MSW 7 40008 UINT32 pulse count 4 LSW 8 40009 UINT32 pulse count 5 MSW 9 40010 UINT32 pulse count 5 LSW 10 40011 UINT32 pulse count 6 MSW 11 40012 UINT32 pulse count 6 LSW 12 40013 UINT32 pulse count 7 MSW 13 40014 UINT32 pulse count 7 LSW 14 40015 UINT32 pulse count 8 MSW 15 40016 UINT32 pulse count 8 LSW 16 40017 UINT32 pulse count 9 MSW 17 40018 UINT32 pulse count 9 LSW 18 40019 UINT32 pulse count 10 MSW 19 40020 UINT32 pulse count 10 LSW 20 40021 UINT32 pulse count 11 MSW 21 40022 UINT32 pulse count 11 LSW 22 40023 UINT32 pulse count 12 MSW 23 40024 UINT32 pulse count 12 LSW 24 40025 UINT32 pulse count 13 MSW 25 40026 UINT32 pulse count 13 LSW 26 40027 UINT32 pulse count 14 MSW 27 40028 UINT32 pulse count 14 LSW 28 40029 UINT32 pulse count 15 MSW 29 40030 UINT32 pulse count 15 LSW 30 40031 UINT32 pulse count 16 MSW 31 40032 UINT32 pulse count 16 LSW 32 40033 UINT32 pulse count 17 MSW 33 40034 UINT32 pulse count 17 LSW 34 40035 UINT32 pulse count 18 MSW 35 40036 UINT32 pulse count 18 LSW 36 40037 UINT32 pulse count 19 MSW 37 40038 UINT32 pulse count 19 LSW 38 40039 UINT32 pulse count 20 MSW 39 40040 UINT32 pulse count 20 LSW 40 40041 UINT32 pulse count 21 MSW 41 40042 UINT32 pulse count 21 LSW 42 40043 UINT32 pulse count 22 MSW 43 40044 UINT32 pulse count 22 LSW 44 40045 UINT32 pulse count 23 MSW 45 40046 UINT32 pulse count 23 LSW

System information points: offset point type description 1000 41001 UINT16 Serial Number (bytes 1,2) (our serial number) 1001 41002 UINT16 Serial Number (bytes 3,4) 1002 41003 UINT16 Serial Number (bytes 5,6) 1003 41004 UINT16 firmware version major 1004 41005 UINT16 firmware version minor 1005 41006 UINT32 mfg date MSW 1006 41007 UINT32 mfg date LSW 1007 41008 UINT32 up time (seconds) MSW. 1008 41009 UINT32 up time (seconds) LSW. 1009 41010 UINT16 Our modbus address 1010 41011 UINT16 Hardware Version major (8911) 1011 41012 UINT16 Hardware Version minor. HighByte=pcb-rev(0=rev A, etc), lowbyte = part- rev (0=rev A, etc) 1012 41013 UINT16 (NV/r/w) contact closure threshold in ohms, default 1000 = 1kohm. 100- 2550 ohms allowed. 1013 41014 UINT16 (NV/r/w) contact closure speed, pulse speed: 0=10hz/default, 1=50hz, 2=100hz 1014 41015 UINT16 (NV/r/w) Pulse KYZ flag bitmap. channels 1-16 0x01 = pulse1 kyz mode, 0x02 = p2, etc. 1015 41016 UINT16 (NV/r/w) Pulse KYZ flag bitmap. channels 17-23 1016 41017 UINT16 power supply voltage monitor. scale: x100 1017 41018 UINT16 pcb temperature monitor. scale: x100 1018 41019 UINT16 5V internal power supply voltage monitor. scale: x100 1019 41020 UINT16 RS485 baud rate. 2=9600, 3=19200. 1020 41021 UINT16 reason for reboot. 0x01=POR, 0x02=EXTR 0x04=WDTR 0x08=BODR, 0x8000=WDTOF
Modbus function 0x11 Slave ID response will report the following:
“Leviton, A8911-23, pulse counter, 23 channel”, id=47

Pulse Count: The pulse count is stored as an unsigned 32bit integer. This allows for 2^32 pulses (4.2billion) to be counted before rollover. On Modbus systems that do not allow you to read 32bit values, you can calculate the pulse count as follows:
count = (MSW * 65536) + LSW
count = (MSW
Pulse count registers accumulate a total number of pulses received on each pulse input. The pulse count totals always increment and can not be cleared or set to an arbitrary value to prevent tampering. All pulse count totals are stored in non- volatile memory to preserve counts during power failure. The unsigned 32 bit counter values can accumulate up to 4.29 billion (2^32) pulses before rollover.
All 32 bit data point values are encoded in 2 Modbus registers (16bits each). Modbus master systems should always query the A8911-23 using a single query to read an entire block of registers. Never use two queries to read one register and then combine the two results into a single 32 bit value. Doing so will allow the pulse count to increment in the middle of the two Modbus queries, and will cause intermittent data readings that are incorrect.
EXAMPLE: A pulse input has a count of 65534. This is represented as a 32 bit hex number 0x0000FFFE. The first 4 digits are the MSW register, the second 4 digits are the LSW register. The Modbus Master reads the first (MSW) register and gets 0x0000. In between the two readings, the pulse input counts 2 more pulses, making the total 65536 or 0x00010000 in hex. Next the Master reads the second (LSW) register and gets 0x0000. When the two registers are combined, the result is 0x00000000. The proper way to handle this situation is to simply read both registers in a single Modbus query.
or

From time to time, Leviton may release firmware updates with additional features and system changes. To find out what firmware your A8911-23 has installed, read the firmware version register with a Modbus utility, or use the “Advanced configuration” page in the AcquiSuite setup menu. Firmware update files may be obtained from Leviton technical support.
The firmware update process requires an RS232 serial port and a windows computer to run the firmware update utility. Before starting this process, verify your computer has a serial port available. You may need to deactivate other software such as the palm pilot utility or ups monitor software. USB connected serial ports may be used, however these are not as fast or reliable as standard computer serial ports and may fail to upgrade the firmware correctly.
To update the firmware, use the following procedure.



3.39in 86mm
P1
485 TX
485 RX
+24V
GND
GND P2
P2 P3 P4 P5 P6 P7 P8 P9 P10 P11 P12
P23 P22 P21 P20 P19 P18 P17 P16 P15
P23
GND P5
GND
P22
3.250in Mounting holes
GND
P21
4.13 in 105mm 1.69in 43mm
GND
P20
GND P8
GND
P19
GND P9
GND
P18
GND P10
GND
P17
GND P11
GND
P16
GND P12
GND
P15
GND P13
P13
P14
GND
P14
3.875 in Mounting holes
Alive · NC Shield

FCC STATEMENT:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by Leviton Manufacturing Co., could void the user’s authority to operate the equipment.
Model A8911 manufactured by Leviton Manufacturing Co., Inc., 201 North Service Road, Melville, NY 11747, www. leviton.com. This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Use herein of third party trademarks, service marks, trade names, brand names and/or product names are for informational purposes only, are/may be the trademarks of their respective owners; such use is not meant to imply affiliation, sponsorship, or endorsement. Modbus is a U.S. registered trademark of Schneider Electric USA, Inc.
Leviton Manufacturing Co., Inc.
201 North Service Road, Melville, NY 11747
Visit Leviton’s Web site at http://www.leviton.com
© 2021 Leviton Manufacturing Co., Inc. All rights reserved.
Specifications and price subject to change at any time without notice.
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Leviton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824- 3005. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.

No de cat. A8911


Pages mentionnées dans ce manuel — fabricant, assistance et téléchargements.
Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.
Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.