Dear Customer, We are delighted that you have decided to choose a quality product from our company.
With each push of the button, the gate is started against the previous direction of travel, or the motion of the gate is stopped.
These instructions are original operating instructions as outlined in the EC Directive 2006 / 42 / EC. Read through all of the instructions carefully, as they contain important information about the product. Pay attention to and follow the instructions provided, particularly the safety instructions and warnings.
The forces necessary for gate travel are taught in during this learning run.
Gate travel with the taught-in travel distances and forces.
Keep these instructions in a safe place for later reference!
Gate travel towards the CLOSE end-of-travel position in order to set the home position.
Reversing cycle / safety reversal
Gate travel in the opposite direction when the safety device or force limit is activated.
If a safety device is activated, gate travel is triggered in the opposite direction (reverse cycle) up to the reversal limit shortly before the CLOSE end-of-travel position. If this limit is passed, no reversal occurs to ensure that the gate reaches the end-of-travel position without disrupting travel.
The general warning symbol indicates a danger that can lead to injury or death. In the text, the general warning symbol will be used in connection with the caution levels described below. In the illustrated section, an additional instruction refers back to the explanation in the text.
The area in which the gate moves very slowly, in order to gently move to the end-of-travel position.
After an impulse is sent, the operator independently moves into the end-of-travel position.
Indicates a danger that leads directly to death or serious injuries.
The distance the gate is opened for pedestrian traffic.
Indicates a danger that can lead to death or serious injuries.
The gate travels only as long as the respective buttons are pressed.
Indicates a danger that can lead to minor or moderate injuries.
The travel to completely open the gate.
Indicates a danger that can lead to damage or destruction of the product.
The time between the travel command (impulse) and the start of travel.
Resetting the taught-in values to the delivery status / ex factory setting.
Waiting phase at the OPEN end-of-travel position or partial opening before the gate closes during automatic timed closing.
Automatic timed closing of the gate after a set time has elapsed and after reaching the OPEN end-of-travel position or partial opening.
In this example, 2. 2 means: see text section, section 2.2
Switches on the control circuit board for setting the control.
When the gate is passed through, the photocell shortens the hold-open phase and the gate closes a short time thereafter.

Check for smooth running
The illustrated section shows the operator fitting of an operator without a base plate to the inside right of the closed sliding gate. Where fitting or programming differs for an operator with base plate or for a sliding gate with the operator attached to the inside left of the closed sliding gate, this is shown in addition.
If necessary, see the separate fitting instructions for the emergency battery
All dimensions in the illustrated section are in [mm].
Standard sliding gate operator
FOR THE SAFETY OF PERSONS, IT IS IMPORTANT TO COMPLY WITH THE FOLLOWING INSTRUCTIONS. THESE INSTRUCTIONS MUST BE KEPT.
Reinforced sliding gate operator
Depending on the type of operator, the operator can be used in private / non-commercial areas or in commercial areas.
The sliding door operator is exclusively intended for the operation of smooth-running sliding doors. The maximum permissible door size and maximum weight must not be exceeded. The door must be easy to open and close manually.
Continuous operation and use on gates with a gradient or slope is not permitted.
Only correct fitting and maintenance in compliance with the instructions by a competent / specialist company or a competent / qualified person ensures safe and flawless operation of the system. According to EN 12635, a specialist is a person with suitable training, specialist knowledge and practical experience sufficient to correctly and safely fit, test, and maintain a gate system.
DIL switch factory setting

Colour code for cables, single conductors and components
The abbreviations of the colours for identifying the cables, conductors and components comply with the international colour code according to IEC 757:
Fitting, maintenance, repairs, and disassembly of the gate system and sliding gate operator must be performed by a specialist.
▶ In the event of a gate system or gate operator failure (sluggish operation or other malfunctions), a specialist must be commissioned immediately for the inspection / repair work.

The specialist carrying out the work must ensure that installation is conducted in compliance with the prevailing national job safety rules and regulations and those governing the operation of electrical equipment. The relevant national directives must be observed. Potential hazards as outlined in DIN EN 13241-1 are avoided by construction and fitting according to our guidelines.
Safety relevant functions or components of the control, such as the force limit, external photocells and closing edge safety device, have been designed and approved in accordance with category 2, PL "c" of EN ISO 13849-1:2008.
After fitting has been completed, the installer of the gate system must declare conformity with DIN EN 13241-1 in accordance with the scope of application.
▶ See warning in section 4.6


OBSERVE ALL INSTRUCTIONS, INCORRECT FITTING COULD RESULT IN SERIOUS INJURY.

▶ Do not use the gate system if repair or adjustment work must be conducted.
▶ Check the entire gate system (joints, gate bearings and fastenings) for wear and possible damage.
▶ Check for signs of rust, corrosion or fractures.

The sliding gate operator is not designed for operation with sluggish gates, that is, gates that can no longer be opened or closed manually, or can only be opened / closed manually with difficulty.
The operator is only designed for use with gates that do not have any gradient or slope.
The gate must be in a flawless mechanical condition, so that it can be easily operated by hand (EN 12604).

▶ Check whether the gate can be opened and closed correctly.
Toothed track Dimension A (mm)
Min. Max.
▶ Immobilize any mechanical locks not needed for power operation of the sliding gate. This includes in particular any locking mechanisms connected with the gate lock.
▶ Mechanically secure the gate to prevent it from running out of its guides.
▶ Change to the illustrated section for the fitting and initial operation. Observe the respective text section when you are prompted to by the symbol for the text reference.
▶ See Figures 2a. 1 / 2b. 1
Unsuitable fixing material Use of unsuitable fixing material may mean that the operator is insecurely attached and could come loose.
▶ Only use the provided fixing material in concrete ≥ B25 / C25 (see Figures 1. 1 / 2. 1).
▶ Follow all the instructions provided in this manual.
Damage caused by dirt Drilling dust and chippings can lead to malfunctions.
▶ Cover the operator during drilling work.
▶ After drilling, check the depth of the hole.
Malfunctions in the connection cables Malfunctions may occur if connection cables and supply lines are ducted together.
Ø 12 mm for stock screws 80 mm
Ø 10 mm for heavy-duty anchors 105 mm
▶ Duct the operator's connection cables (24 V DC) in an installation system that is separate from supply lines (230 / 240 V AC).
▶ Use the socket wrench included in the scope of delivery to install the stock screws.
1. A foundation must be laid (see Figure 1a / 1b). The * mark represents the frost-free depth (in Germany = 80 cm). A larger foundation must be laid if using a closing edge safety device (see Figure 1c / 1d). 2. Concrete ≥ B25 / C25 (compacted) must be used with the operator type with base plate. 3. A base foundation may be required for gates with inside rollers. 4. The 230 / 240 V AC mains lead must be routed through a tube in the foundation. The lead to connect 24 V accessories must be installed in a tube that is separated from the mains lead (see Figure 1. 1).
▶ See Figures 3 – 3. 5
▶ Open the operator housing, release the operator and remove the circuit board bracket. The motor and toothed wheel are lowered in the housing when the operator is released.
▶ If necessary, cut the tube seals to fit the tubes.
▶ When the housing is placed on the stock screws or base plate, pull the mains lead and, if necessary, the 24 V connecting lead from below through the tube seals and into the housing without any distortion.
The foundation must have set and dried sufficiently before the following work is carried out.
▶ When tightening, pay attention that it is horizontal, stable and securely fastened.
Prior to fitting:
▶ Check that required hole depths are available.
▶ To fit the toothed tracks, use the connectors (bolts and nuts, etc.) from the fitting accessories (see Figure C1 or Figure C4). These must be ordered separately.

The operator is engaged once locked.
▶ Turn the mechanism back to the lock position while slightly raising the motor.
▶ See the control print overview in Figure 6
Fitting:
▶ See Figures 4 – 4. 3
The sliding gate operator must be released (see Figure 3. 2).
▶ When fitting the toothed tracks, make sure that the transitions between the individual toothed tracks are properly aligned to ensure smooth gate movement.
▶ After fitting, the toothed tracks and the toothed wheel of the operator must be aligned to each other. Both the toothed tracks and the operator housing can be adjusted to do this. Incorrectly fitted or poorly aligned toothed tracks may lead to unintentional reversing. It is essential that the specified dimensions are adhered to!
▶ Install control devices at a height of at least 1.5 m (out of the reach of children).
▶ Fit permanently installed control devices (such as buttons, etc.) within sight of the gate, but away from moving parts. Persons or objects may be trapped if the installed safety equipment fails.
▶ Seal the housing to protect it from humidity and vermin (see Figure 4. 4).
▶ In accordance with BGR 232, install at least one clearly visible and easily accessible emergency command unit (emergency OFF) near the gate so the gate can be brought to a standstill in the case of danger (see section 3.8.3)
Contact with the mains voltage presents the danger of a deadly electric shock. For that reason, observe the following warnings under all circumstances:
▶ Electrical connections may only be made by a qualified electrician.
Damage to the electronics caused by external voltage External voltage on the connecting terminals of the control will destroy the electronics.
▶ The on-site electrical installation must conform to the applicable protective regulations (230 / 240 V AC, 50 / 60 Hz)!
▶ Do not apply any mains voltage (230 / 240 V AC) to the connecting terminals of the control.
▶ The mains plug must be disconnected before any work is performed on the operator.
The total consumed current may be max. 500 mA when connecting accessories at the following terminals:
▶ Connect the mains voltage directly at the transformer plug terminal using the NYY underground cable.
▶ Connect the wires of the external radio receiver as follows: – GN to terminal 20 (0 V) – WH to terminal 21 (channel 1 signal) – BN to terminal 5 (+24 V) – YE to terminal 23 (channel 2 signal for partial opening). Only with a 2-channel receiver.
The aerial wire of external radio receivers should not come into contact with metal objects (nails, bracing, etc.). The best orientation to achieve an optimum range must be established by trial and error.
Mains voltage

Terminal assignment:
Terminal 20 0 V (power supply)
One or more buttons with normally open contacts (volt-free), e.g. key switches, can be connected in parallel, max. lead length 10 m.
Terminal 18 Test signal
Terminals 71 / 72 / 73 Safety device signal
Terminal 5 +24 V (power supply)
Impulse control:
▶ First contact to terminal 21
▶ Second contact to terminal 20
Safety devices without a testing unit (e.g. static photocells) must be tested twice a year. They may only be used to protect property!
Partial opening:
▶ First contact to terminal 23
▶ Second contact to terminal 20
Connection option for the universal adapter print UAP 1.
If auxiliary voltage is needed for an external button, then a voltage of +24 V DC is available for this at terminal 5 (to terminal 20 = 0 V).
To enable gate movement in the event of a mains failure, an optional emergency battery can be connected. In the case of a mains failure, the system automatically switches to battery operation.
A cut-out with normally closed contacts (switching to 0 V or volt-free) is connected as follows (see Figure 6. 3):

▶ Pull out the mains plug and the plug of the emergency battery when performing all work on the gate system.
By opening the contact, any travel cycles in progress are immediately halted and permanently prevented.
A warning lamp or CLOSE limit switch reporting can be connected via the volt-free contacts on the Option connector.
The voltage at the 24 V DC connector can be used for operation (e.g. warning signals prior to and during gate travel) with a 24 V lamp (max. 7 W).
▶ Make sure that children are not playing near the gate system.
A 230 V warning lamp must be directly supplied with power.
▶ Make sure that no persons or objects are in the gate's travel range.
▶ If the gate system only has one safety feature, only operate the sliding gate operator if you are within sight of the gate's travel range.
▶ See Figures 6. 5 – 6. 7
Safety devices such as photocells / closing edge safety devices (SKS) or 8k2 resistance contact strips can be connected:
SE1 in the opening direction, monitored safety device or 8k2 resistance contact strip
▶ Monitor the gate travel until the gate has reached the end-of-travel position.
SE2 in the closing direction, monitored safety device or 8k2 resistance contact strip
▶ Only drive or pass through remote- control gate systems when the gate is at a standstill!
SE3 in the closing direction, photocell without testing or dynamic 2-wire photocell, e.g. as a through-traffic photocell
The functions selected for the 3 safety circuits are set via the DIL switches (see section 5).
* Accessory, not included as standard equipment!

▶ See Figure 8. 1b
Teaching in the OPEN end-of-travel position: 4. Press circuit board button T and keep it pressed. The gate now travels in OPEN direction at slow speed. 5. Release circuit board button T, once the desired OPEN end-of-travel position is reached. 6. Press circuit board button P to confirm this position. The green LED flashes rapidly for 2 seconds to indicate that the OPEN end-of-travel position has been recorded and then goes out.
▶ Whenever the gate is moving, never touch the toothed track, toothed wheel, and the main or secondary closing edges.
▶ Before initial start-up, check that all the connecting leads are correctly installed at the connecting terminals.
▶ See Figure 8. 1c
▶ Make sure that all DIL switches are set to the factory setting (OFF) (see Figure 7), the gate is half open and the operator engaged.
If press-and-hold operation has been set, it is not possible to record the partial opening end-of-travel position.
Change the following DIL switches:
▶ DIL switch 1: Installation direction (see Figure 7. 1) – To ON, if the gate closes towards the right. – To OFF, if the gate closes towards the left.
Teaching in the partial opening end-of-travel position:
▶ DIL switches 3-7: Safety devices (see Figures 9. 6 / 9. 7 / 9. 8) – Set according to the connected safety and protective devices (see section 5.3 – 5.5). These are, however, not active during set-up mode.
▶ See Figure 8. 1a
▶ After you have finished the teach-in procedure, set DIL switch 2 back to OFF. The green LED signals that forces must be taught in by flashing quickly.
The limit switch (reed contact) must be connected before teaching in the end-of-travel positions. The limit switch wires must be connected at the REED terminal.
The option relay has the same function as the red LED during set-up. The limit switch position can be viewed from afar with a connected lamp (see Figure 6. 4).
The safety equipment is active again.
Teaching in the CLOSE end-of-travel position:
After teaching in the end-of-travel positions, the first cycle is always a reference run. During this reference run the option relay clocks and a connected warning lamp flashes.
Reference run to CLOSE end-of-travel position:
▶ Press circuit board button T once. The operator automatically moves into the CLOSE end‑of-travel position.
▶ If press-and-hold operation has been set (DIL switch 16 to ON), press and hold circuit board button T until the gate is in the close end-of-travel position.
The gate is now in the CLOSE end of travel position.
If the gate travels in the opening direction, DIL switch 1 is in the wrong position and must be reset. Then repeat steps 1 to 4.
Initial start-up is now finished if press-and-hold operation has been set (DIL switch 16 to ON).
If the position of the gate does not correspond to the desired CLOSE position, a readjustment must be made.
Readjusting the CLOSE end-of-travel position:
Once the end-of-travel positions have been taught in and the reference run performed, force learning runs must also be performed. For this, three successive gate cycles must take place, during which none of the safety devices may be activated. Recording the forces takes place automatically by press-and-release operation in both directions and the option relay clocks. The green LED flashes throughout. This LED is steadily illuminated once the force learning runs have been completed (see Figure 9. 1).

▶ Both of the following procedures must be conducted three times.
Deactivating the force limit:
Force learning runs:
▶ Press circuit board button T once. The operator automatically moves into the OPEN end‑of‑travel position.
If the wire jumper is snipped through during set-up or during gate travel, this will not have any effect on the function.
▶ Press circuit board button T once. The operator automatically moves into the CLOSE end‑of-travel position.
Once you have completed the teach-in procedure, the door system can only be operated using an external button.
Reactivating the force limit:
▶ Do not set a force value that is too high.
Due to special fitting situations, it can, however, happen that the previously taught-in forces prove inadequate, which can lead to undesired reversing. Readjust the forces in such cases.
The slow speed length is automatically set to a basic value of approx. 500 mm before the end-of-travel positions after the end-of-travel positions have been taught in. The starting points can be reprogrammed from a minimum length of approx. 300 mm up to the entire gate length (see Figure 9. 3).
The force limit of the gate system is set via a potentiometer that is labelled "Kraft F" on the control print (see Figure 9. 1).
Changing the starting points for slow speed deletes the already taught-in forces and they must be taught in again after the changes have been made.
Full left + 0 % force
Changing the starting points:
Centred +15 % force
1. The end-of-travel positions must be set and the gate is in the CLOSE end-of-travel position and DIL switch 2 must be set to OFF. 2. Set DIL switch 12 to ON. 3. Press print button T. The gate will travel normally in press-and-release operation in the OPEN direction. 4. When the gate passes the desired position for the start of slow speed, briefly press print button P. The operator will move at slow speed for the remaining distance until in the OPEN end-of-travel position. 5. Press print button T again. The gate will again travel normally in press-and-release operation in the CLOSE direction. 6. When the gate passes the desired position for the start of slow speed, briefly press print button P. The operator will move at slow speed for the remaining distance until in the CLOSE end-of-travel position. 7. Set DIL switch 12 to OFF.
Full right +75 % force
If the force measured with the force measuring device is still too high when the potentiometer is turned to full left, this can be changed by reducing the travel speed (see Figure 9. 2).
Adjusting the speed:
The slow speed starting point settings have now been completed. The green LED flashes to signal that the forces must be taught in again.
Not for use in countries with EU directives!
The force limit can be switched off by snipping through the BR1 wire jumper on the control print.
The starting points for slow speed can also be set to "overlap"; in this case, the entire gate movement is in slow speed.
If no safety devices are connected (DIL switches 3 – 6 to OFF), the operator will only work in press-and-hold operation.
If 8k2 resistance contact strips are connected (DIL switch 3 – 6 to ON) the operator will work in‑press‑and‑release operation without force limit.

During operation of the gate in the CLOSE direction, the system must distinguish between two possibilities: whether the gate contacts the end stop (gate system stops) or an obstruction (gate reverses direction). The limit range can be adjusted as follows (see Figure 9. 4).
Setting the reversal limit:
The DIL switches must be set as described below in accordance with the national regulations, the desired safety equipment and the on-site circumstances.
1× flashing up to
Minimum reversal limit, the green LED flashes once
Installation direction:
10× flashing Maximum reversal limit, the green LED flashes 10 times
1 ON Gate closes to the right (as viewed from the operator)
1 OFF Gate closes to the left (as viewed from the operator)
Automatic timed closing can only be activated if at least one safety device has been connected. This is required according to DIN EN 13241-1.
Set-up mode:
▶ See Figures 8. 1a – c
The safety and protective devices are not active during set-up mode.
The hold-open phase can be set for operation with automatic timed closing (see Figure 9. 5).
Setting the hold-open phase:
SE1 safety device (opening):

The functions of the SE1 are set with DIL switch 3 in combination with DIL switch 4.

3 ON Activation kit for closing edge safety device or photocell with testing
4 ON Brief, immediate reversing in the CLOSE direction (for SKS)

4 OFF Brief, delayed reversing in the CLOSE direction (for photocell)
▶ After the learning runs, the person commissioning the system must check the function(s) of the safety equipment.
The system is ready for operation only after this.

▶ See Figure 9. 9d
SE2 safety device (closing):
8 OFF 9 OFF Operator No special function
Option relay Relay picks up in the CLOSE end-of- travel position.
The functions of the SE2 are set with DIL switch 5 in combination with DIL switch 6.

5 ON Activation kit for closing edge safety device or photocell with testing
Automatic timed closing is only possible from the determined end-of-travel positions (full or partial opening). Automatic timed closing is deactivated if it fails three times. The operator must be restarted with an impulse.
6 ON Brief, immediate reversing in the OPEN direction (for SKS)
6 OFF Brief, delayed reversing in the OPEN direction (for photocell)
Effect of the SE3 protective device as a through-traffic photocell with automatic timed closing

10 ON The photocell is activated as a through-traffic photocell, after the photocell has been passed, the hold-open phase is reduced.
SE3 protective device (closing):
10 OFF The photocell is not activated as a through-traffic photocell. If, however, automatic timed closing is activated and the photocell interrupted after the hold-open phase has elapsed, the hold-open phase will be reset to the preset time.
Delayed reversing to OPEN end-of-travel position.
7 ON Dynamic 2-wire photocell
Setting the reversal limits:
The functions of the operator (automatic timed closing / pre- warning phase) and the function of the option relay are set with DIL switch 8 in combination with DIL switch 9.
▶ See Figure 9. 4 and section 4.5
11 ON Reversal limit set step-by-step
▶ See Figure 9. 9a

8 ON 9 ON Operator Automatic timed closing, pre-warning phase for each gate movement
Option relay Relay clocks rapidly during the pre- warning phase, normally during the travel phase and is OFF during the hold-open phase.
Starting point for slow speed when opening and closing:
▶ See Figure 9. 3 and section 4.4
12 ON Starting points are set for slow speed when opening and closing
▶ See Figure 9. 9b

8 OFF 9 ON Operator Automatic timed closing, pre-warning time only for automatic timed closing
Option relay Relay clocks rapidly during the pre- warning phase, normally during the travel phase and is OFF during the hold-open phase.
Setting the hold-open phase:
▶ See Figure 9. 5 and section 4.6
13 ON Hold-open phase is set in increments
▶ See Figure 9. 9c

8 ON 9 OFF Operator Pre-warning phase for each gate movement without automatic timed closing
Option relay Relay clocks rapidly during the pre- warning phase, normally during the travel phase.

Impulse behaviour during the hold-open phase:
The impulse behaviour during the hold-open phase can be set for operation with automatic timed closing.
14 ON An impulse cancels the hold-open phase. The operator closes the gate after the pre‑warning phase has elapsed.
14 OFF An impulse increases the hold-open phase by the pre-set time.
▶ Make sure that the hand transmitters are kept away from children and can only be used by people who have been instructed on how the remote-control gate functions!
Setting the speed:
▶ See Figure 9. 2 and section 4.3.2
▶ If the gate has only one safety feature, only operate the hand transmitter if you are within sight of the gate!
15 ON Slow mode (slow speed); (no SKS required)
15 OFF Normal mode (normal speed)
▶ Only drive or pass through remote- control gate systems when the gate is at a standstill!
▶ Please note that unwanted gate cycles may occur if a hand transmitter button is accidentally pressed (e.g. if stored in a pocket / handbag).
Setting the operating mode:
Press-and-hold operation can be set with DIL switch 16. The force limit is set to the maximum value.
Special functions are possible during press-and-hold operation in conjunction with a universal adapter print UAP 1.
1 LED 2 Hand transmitter buttons 3 Battery compartment cover 4 Battery

▶ Use only the battery type AAA (LR03) 1,5 V.
▶ Pay attention that no persons or objects are in the gate's travel range when teaching in the radio system.
The original declaration of conformity can be requested from the manufacturer.

Plug-in the external radio receiver on the respective connector (see Figure 6. 1). The function “impulse” (Open – Stop – Close – Stop) and the function “partial opening” for at max. 60 different hand transmitters can be programmed on the external radio receiver. If more than 60 different hand transmitters are programmed the receiver deletes those that have been registred in the beginning.
▶ Make sure that children are not playing near the gate system.
▶ Make sure that no persons or objects are in the gate's travel range.
▶ If the gate system only has one safety feature, only operate the sliding gate operator if you are within sight of the gate's travel range.
▶ Monitor the gate travel until the gate has reached the end-of-travel position.
The function of this hand transmitter button is now programmed on the receiver (see Figure 11a).
▶ Only drive or pass through remote- control gate systems when the gate is at a standstill!
The function of this hand transmitter button is now programmed on the receiver (see Figure 11b).
▶ Whenever the gate is moving, never touch the toothed track, toothed wheel, and the main or secondary closing edges.
At least one hand transmitter button must be taught in on the radio receiver to operate the sliding gate operator via radio.
During radio transmission, the hand transmitter and receiver must be at least 1 m apart.
▶ All persons using the gate system must be shown how to operate it properly and safely.
▶ Demonstrate and test the mechanical release as well as the safety return.

It is not possible to delete individual hand transmitters.
▶ Replace the transparent cover (see Figure 12) and close the housing cover after completing all of the steps required for initial start-up.
▶ In the event of a failure of the safety reversal, a specialist must be commissioned immediately for the inspection and repair work.
▶ Fix the sign warning about getting trapped in a noticeable, cleaned and degreased place, for example, near to the permanently installed button for moving the operator.

During normal mode, the sliding gate operator only works according to the impulse sequence control (OPEN-STOP- CLOSE-STOP). It does not matter whether an external button, hand transmitter button or circuit board button T has been actuated:
▶ See LED GN and LED RT in Figure 6
The green LED indicates the operating condition of the control:
▶ To open and close fully, press the appropriate impulse generator for channel 1.
Steady illumination Normal state, all end-of-travel positions and forces taught-in.
▶ To open and close partially, press the appropriate impulse generator for channel 2.
Fast flashing Force learning runs must be performed.
To be able to open or close the sliding gate by hand during a power failure, it must be disengaged from the operator.
Slow flashing Set-up mode – end-of-travel position setting
Once the power supply has been restored, the gate must be reengaged with the operator upstream from the limit switch.
▶ Slightly lift the motor while locking it (see Figure 14. 2).
The red LED indicates:
The sliding gate operator is maintenance-free.
In the interest of your own safety, we recommend having the gate system inspected and maintained by a qualified person in accordance with the manufacturer's specifications.
In normal mode Flashing code as an error / diagnosis display
The red LED RT helps to easily identify causes when operation does not go according to plan.
▶ Disconnect the mains plug and, if applicable, the plug of the emergency battery when performing all work on the gate system.
If normal operation of the sliding gate operator with the circuit board button T is otherwise possible, a short circuit in the external button's connecting lead or in the button itself can be recognised through the behaviour described here.
▶ Safeguard the gate system against being switched on again without authorisation.
Inspection and repairs may only be carried out by a qualified person. Contact your supplier for this purpose.
Error / warning Safety / protective device has responded
A visual inspection may be carried out by the operator.
▶ Check all safety and protective functions monthly.
▶ Check the function of the resistance contact strips 8k2 every six months.
▶ Malfunctions and / or defects at hand must be rectified immediately.
Display flashes 2×

Error / warning Force limit in CLOSE direction
To reset the control (taught-in end-of-travel positions, forces):
Possible cause Obstruction in gate area
Remedy Remove the obstruction; check forces, increase if necessary
Error / warning Hold or static current circuit is open, operator at a standstill
The control system has now been reset to the factory setting.
When disassembling, observe the applicable regulations regarding occupational safety.
Have a specialist dismantle the sliding gate operator in the reverse order of these fitting instructions and dispose of it properly.
Error / warning Force limit in OPEN direction
Possible cause Obstruction in gate area
Optional accessories are not included in the scope of delivery.
Remedy Remove the obstruction; check forces, increase if necessary
Loading of the operator by all electrical accessories: max. 500 mA.
Error / warning System error
Possible cause Internal error
Remedy Perform a factory reset (see section 10) and teach in the control again (see section 4.2), or exchange it if necessary
Error / warning Peak force
Remedy Check the motor for seizure
If an error occurs, this can be acknowledged, provided the error is no longer present.
▶ Actuate an internal or external impulse generator. The error is deleted and the gate travels in the corresponding direction.

15 Excerpt from the Declaration of Incorporation
We shall be exempt from our warranty obligations and product liability in the event that the customer carries out his own structural alterations or undertakes improper installation work or arranges for same to be carried out by others without our prior approval and contrary to the fitting guidelines we have provided. Furthermore, the manufacturer assumes no responsibility for the accidental or careless operation of the operator and accessories, as well as for improper maintenance of the gate or for a non-authorised method of fitting the gate. Batteries are also not covered by the warranty.
(as defined in EC Machinery Directive 2006 / 42 / EC for incorporation of partly completed machinery according to annex II, part B)
There is no warranty on consumables (e.g. fuses, batteries, lamps). Claims made under the warranty do not extend the warranty period. For replacement parts and repairs the warranty period is six months or at least the remainder of the warranty period.
Partly completed machinery as defined in the EC Directive 2006 / 42 / EC is only intended to be incorporated into or assembled with other machinery or other partly completed machinery or equipment, thereby forming machinery to which this directive applies.
A claim under this warranty is only valid for the country in which the equipment was bought. The product must have been purchased through our authorised distribution channels. A claim under this warranty exists only for damage to the object of the contract itself. Reimbursement of expenditure for dismantling and fitting, testing of corresponding parts, as well as demands for lost profits and compensation for damages, are excluded from the warranty.
This is why this product must only be put into operation after it has been determined that the entire machine / system in which it will be installed corresponds with the guidelines of the EC Directive mentioned above.
Any modification made to this product without our express permission and approval shall render this declaration null and void.
The receipt of purchase substantiates your right to claim under the warranty.
For the duration of the warranty we shall eliminate any product defects that are proven to be attributable to a material or manufacturing fault. We pledge to replace free of charge and at our discretion the defective goods with non- defective goods, to carry out repairs, or to grant a price reduction.
Replaced parts become our property.

Max. gate width Depending on operator type: 6,000 mm / 8,000 mm / 10,000 mm
Max. gate height Depending on operator type: 2,000 mm / 3,000 mm
Max. gate weight Depending on operator type: Floor-guided 300 kg / 500 kg / 800 kg Self-supporting 250 kg / 400 kg / 600 kg
Rated load See data label
Max. pull and push force See data label
Operator housing Diecast zinc and weather- resistant plastic
Mains voltage Rated voltage 230 V / 50 Hz
Control Microprocessor control system, programmable via 16 DIL switches, control voltage 24 V DC
Operating mode S2, short-time duty 4 minutes
Temperature range -20°C to +60°C
Travel / force limit Electronic
Force limit for both operational directions, self-programming and testing
Motor 24 V DC motor and worm gear
Protection category IP 44
Automatic safety cut-out

DIL 1 Installation direction
ON Gate closes to the right (as viewed from the operator)
OFF Gate closes to the left (as viewed from the operator)
DIL 2 Set-up mode
ON Set-up mode (limit switch and OPEN end-of-travel position) / delete gate data (reset)
OFF Normal mode in press-and-release operation
DIL 3 Type of SE1 safety device (connection at terminal 72) when opening
ON Safety device with testing (SKS activating kit or photocell)
OFF 8k2 resistance contact strip, photocell from another manufacturer or none (8k2 resistance between terminal 72 and 20)
DIL 4 Effect of SE1 safety device (connection at terminal 72) when opening
ON SE1 activation triggers brief, immediate reversing (for SKS)
OFF SE1 activation triggers brief, delayed reversing (for photocell)
DIL 5 Type of SE2 safety device (connection at terminal 73) when closing
ON Safety device with testing (SKS activating kit or photocell)
OFF 8k2 resistance contact strip, photocell from another manufacturer or none (8k2 resistance between terminal 73 and 20)
DIL 6 Effect of SE2 safety device (connection at terminal 73) when closing
ON SE2 activation triggers brief, immediate reversing (for SKS)
OFF SE2 activation triggers brief, delayed reversing (for photocell)
DIL 7 Type and effect of SE3 protective device (connection tml. 71) when closing
ON SE3 protective device is a dynamic 2-wire photocell
OFF SE3 protective device is a non-tested, static photocell
DIL 8 DIL 9 Operator function (automatic timed closing) Option relay function
ON ON Automatic timed closing, pre-warning time for each gate movement
Clocks rapidly during pre-warning phase, normally during travel phase, is OFF during hold- open phase
OFF ON Automatic timed closing, pre-warning time only for automatic timed closing
Clocks rapidly during pre-warning phase, normally during travel phase, is OFF during hold- open phase
ON OFF Pre-warning phase for each gate movement without automatic timed closing
Clocks rapidly during pre-warning phase, normally during travel phase
OFF OFF No special function Picks up in the CLOSE end-of-travel position
DIL 10 Through-traffic photocell with automatic timed closing
ON SE3 protective device activated as through-traffic photocell
OFF SE3 protective device not activated as through-traffic photocell
DIL 11 Set reversal limit
ON Reversal limit set step-by-step
DIL 12 Setting the slow speed starting point for opening and closing
ON Starting points for slow speed when opening and closing


OFF Impulse extends the hold-open phase by the pre-set value
La signification des codes d'erreur affichés à l'écran et la façon de les effacer.
| Code | Signification | Solution | |
|---|---|---|---|
| C300 | C800 / Rev. 1.1 RE / 07.2014 | p.3 |