FR
Acson logo
Notice d'utilisation officielle

Acson SEQ-0501

21 pages·809 KB·Climatiseur·PDF·ENNLJA
Acson SEQ-0501
Table des matières 13 sections SEQUENTIAL CONTROLLER for PACKAGED AIR CONDITIONER (PAC) · CONTRÔLEUR SÉQUENTIEL pour CLIMATISEUR · FOLGESTEUERUNG für VERPACKTE KLIMAANLAGE · REGOLATORE SEQUENZIALE per CONDIZIONATORI ASSEMBLATI (PAC) · … AfficherMasquer
Page 1 of the Acson SEQ-0501 user manual — D C
Page 1 · cliquer pour agrandir
Page 1

SEQUENTIAL CONTROLLER for PACKAGED AIR CONDITIONER (PAC)

CONTRÔLEUR SÉQUENTIEL pour CLIMATISEUR

FOLGESTEUERUNG für VERPACKTE KLIMAANLAGE

REGOLATORE SEQUENZIALE per CONDIZIONATORI ASSEMBLATI (PAC)

REGULADOR SECUENCIAL para ACONDICIONADOR DE AIRE EMBALADO (PAC)

УСТРОЙСТВО ЦИКЛОВОГО УПРАВЛЕНИЯ для КОМБИНИРОВАННОГО КОНДИЦИОНЕРА (КК)

Acson SEQ-0501 — SEQUENTIAL CONTROLLER for PACKAGED AIR CONDITIONER (PAC) diagram (page 1)
Fig. 1 · SEQUENTIAL CONTROLLER for PACKAGED AIR CONDITIONER (…

DISPLAY / AFFICHAGE / ANZEIGE / DISPLAY / INDICACIÓN / ДИСПЛЕЙ

Acson SEQ-0501 — DISPLAY / AFFICHAGE / ANZEIGE / DISPLAY / INDICACIÓN / ДИСПЛЕЙ diagram (page 1)
Fig. 2

D C

H I

B

A

Part No.: A08019013037 OM-SEQ-0501

Page 2 of the Acson SEQ-0501 user manual — SEQUENTIAL CONTROLLER for PACKAGED AIR CONDITIONER (PAC)
Page 2 · cliquer pour agrandir
Page 2

A : Time display B : Error indication C : Compressor running display (up to 4 compressors) D : Key lock display E : Heater display (up to 2 heaters) F : Energy saving mode display G : Compressor defrost cycle display (up to 4 compressors) H : Operation mode display I : Temperature set display

2. Operating Guide 2.1 ON/OFF key Press once to start the air conditioning unit. Press again to stop the unit. The operation lamp next to the key lights up and goes off respectively when the unit is running or not running. Caution : In the case when the ON/OFF key is pressed immediately after the operation is stopped, the unit will not restart until 3 minutes later to protect the compressor.

2.2 Selecting Operation Mode Press the MODE key to select the type of operating mode. Consecutive press of the key switches the operation over “COOL”, “HEAT”, “AUTO” and “FAN”. 2.3 SAVE Mode Press the SAVE key to select the energy saving function. This option is only available for “COOL”, “HEAT” and “AUTO” modes.

2.4 Auxiliary Electric Heater If the “HEAT” mode provides insufficient heating to a room even at the highest temperature setting (30°C), press the HEATER key to activate the auxiliary electric heater. For models with two heaters, consecutive press of the key allows the selection of one or both heaters active.

2.5 Temperature Setting To set the desired room temperature, press or to increase or decrease the set temperature in the range of 16°C to 30°C. Press both and simultaneously to toggle between °C and °F setting.

2.6 Time Setting Real time Clock Press the CLOCK key once to activate set clock mode. Press again to disable set clock mode. Under set clock mode, the time of the present day can be set by pressing the respective MINUTE, HOUR and DAY key.

7-days timer Press the ON TIMER key to activate auto-ON timer mode. Under this mode, press the respective MINUTE, HOUR and DAY key to select the time of the week when the air- conditioning unit is to automatically start running. Press the ON TIMER key again to save the setting.

Page 3 of the Acson SEQ-0501 user manual — ENGLISH
Page 3 · cliquer pour agrandir
Page 3

Press the OFF TIMER key to activate auto-OFF timer mode. Under this mode, press the respective MINUTE, HOUR and DAY key to select the time of the week when the air-conditioning unit is to automatically start running. Press the ON TIMER key again to save the setting.

ENGLISH

Then to activate the 7-days timer, press and hold the TIMER ACTIVE key until the word “TIMER ACTIVE” appears on the LCD screen. Repeat the same step to disable the 7-days timer.

2.7 Other Function Key Lock Press the MINUTE key 3 times consecutively to activate the key lock. A “KEY LOCK” symbol will appear on the LCD screen. At this point, only the ON/OFF key is valid. To disable the key lock, again press the MINUTE key 3 times consecutively.

Test run Press the TEST key 2 times consecutively to test run the unit.

3. Error Code When the system is on and an error occurs, the ON/OFF LED on the LCD panel will blink and an error code is shown. When the system is off and there is a thermistor error, the ON/OFF LED is off but the error code is still displayed. Each error code represents different message as below:
E01Require manual resetE19Indoor coil sensor 4 short E02Compressor 1 high temperature (overload)E20Indoor coil sensor 1 open E03Compressor 2 high temperature (overload)E21Indoor coil sensor 2 open E04Compressor 3 high temperature (overload)E22Indoor coil sensor 3 open E05Compressor 4 high temperature (overload)E23Indoor coil sensor 4 open E06Compressor 1 high pressure trip / contact openE24Outdoor coil sensor 1 short E07Compressor 2 high pressure trip / contact openE25Outdoor coil sensor 2 short E08Compressor 3 high pressure trip / contact openE26Outdoor coil sensor 3 short E09Compressor 4 high pressure trip / contact openE27Outdoor coil sensor 4 short E10Compressor 1 trip / low R-22 / outdoor abnormalE28Outdoor coil sensor 1 open E11Compressor 2 trip / low R-22 / outdoor abnormalE29Outdoor coil sensor 2 open E12Compressor 3 trip / low R-22 / outdoor abnormalE30Outdoor coil sensor 3 open E13Compressor 4 trip / low R-22 / outdoor abnormalE31Outdoor coil sensor 4 open E14Room sensor shortE32Compressor 1 de-ice E15Room sensor openE33Compressor 2 de-ice E16Indoor coil sensor 1 shortE34Compressor 3 de-ice E17Indoor coil sensor 2 shortE35Compressor 4 de-ice E18Indoor coil sensor 3 short
4. Installation Of LCD Remote Controller 4.1 Accessories The following accessories are included together with this manual. If any part is missing, contact your dealer immediately. 1 Remote controller
Page 4 of the Acson SEQ-0501 user manual — +5V
Page 4 · cliquer pour agrandir
Page 4

2 Wooden screw 4.1 x 16 (2 pieces) 3 Instruction manual

4.2 Step-by-step Guide i) First, open up the casing of the LCD remote controller into its top and bottom case using a screwdriver. To do this, insert the screwdriver into the lower slot and slide it in the outward direction. ii) Fix the bottom case onto the wall with the 2 wooden screws provided. Then, insert the 4 connecting wires (from the main board) through the slot on the lower center of the case as shown below. iii) Connect one end in each of the 4 wires to the terminal block behind the top case as illustrated. The wire that goes into the “GND” terminal at the top case must be connected at the other end to the “GND” terminal at the main board. The same goes for the “+5V”, “B” and “A” connection. iv) Fasten back the top and bottom case into place. Hook the two upper claws into their respective slots and snap the lower part shut.

Acson SEQ-0501 — GND diagram (page 4)
Fig. 3

GND

+5V

B A

Lower slot for opening LCD casing

GND

2 x Wooden screw

+5V

B A

top case LCD Remote (Bottom case)

Show 7 more labels / short text on this page
LCD Remote · (Top case) · Connection at · main board · Connection · wires · Connection behind

Poser une question sur : Acson SEQ-0501

Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Aucune question pour l'instant sur le Acson SEQ-0501

Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.

Document d'origine

Acson SEQ-0501 manuel PDF

21 pages·809 KB·Climatiseur·PDF
Cliquez sur une page ci-dessus pour l'ouvrir ici
Page 1 / …
100%
Chargement des pages…