L23952Y 1-05 INST ALLA TION, OPERA TION, & MAINTENANCE F AN COIL AIR CONDITIONERS Supersedes: Form 1 15.20-NOM2 (1 199) Form 1 15.20-NOM2 (105) ***** W ARNING TO INST ALLER, SERVICE PERSONNEL AND .
YORK INTERNA TIONAL 2 FORM 1 15.20-NOM2 (105) 3 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) T ABLE OF CONTENTS UNIT SIZE CFM 3 300 4 400 5 500 6 600 8 800 10 1000 12 1200 13 1300 16 1600 20 2000 T ABLE 1 - NOMINAL AIRFLOWS FIG.
YORK INTERNA TIONAL 2 FORM 1 15.20-NOM2 (105) 3 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) RECEIVING Material in this shipment has been inspected at the fact ory and relea sed to the tra nsp ort atio n a genc y i n good condition. When received, a visual inspection of all cartons should be made immediately .
INST ALLA TION 4 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 5 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) FIG. 2 – HORIZONT AL UNITS - TYPICAL WIRING .
INST ALLA TION 4 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 5 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) T334 THERMOST A T Heat-Off Cool, Fan Auto-On, 24V , Manual changeover , 4-W ire Thermostat (R, G, Y , W) Adj. Heat Anticipator , Fixed Cooling Anticipator , Fan Cycling (Cooling) or (Heating/Cooling), No Heating Required.
INST ALLA TION 6 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 7 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) Prior to connecting to the fan coil, all external piping must be purged of debris. When connecting piping or valve kits to fan coil units, do not bend or reposition the coil header tubing for align ment purposes .
INST ALLA TION 6 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 7 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) V AL VE CLUSTER 2-W ay Motorized V alve Assemblies 1. The moto riz ed valve asse mbly shou ld be at tach ed to the supply header , which is the connection nearest the air outlet ange on the unit.
INST ALLA TION 8 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 9 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) NOM. CFM (100's) 3, 4, 5, 6, 8, 10 or 13 Unit Style Y - Ceiling Concealed.
INST ALLA TION 8 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 9 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) Ceiling Concealed Model with Insulated Return Plenum and Filter – MODEL YPHBC .
INST ALLA TION 10 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 1 1 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) CEILING EXPOSED CABINET – MODEL YCHBC .
INST ALLA TION 10 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 1 1 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) All 1-1/2" dia. K.O.;s * 4-Pipe system only NOTES: 1. T elescoping panel allows the cabinet to be installed to within 2 inches of the ceiling line.
INST ALLA TION 12 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 13 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) 6 Y HHS - 6.0 - 240 - 3 - RH NOM.
INST ALLA TION 12 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 13 YORK INTERNA TIONAL INST ALLA TION FORM 1 15.20-NOM2 (105) Ceiling Concealed Model with Electric Heat, Insulated Return Plenum and Filt.
INST ALLA TION 14 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 15 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) FEA TURES: 1. Manual air vents 2. 4-speed direct drive motors 3. 1/2" copper tubing 4. Primary and secondary condensate drains on one end 5.
INST ALLA TION 14 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) 15 YORK INTERNA TIONAL FORM 1 15.20-NOM2 (105) F AN COILS ST ART - UP CHECKLIST Fan INSPECTION - The fan should be inspected and cleaned, in conjunction with maintenance of the motor and bearings.
MAINTENANCE MOTOR The blower motor should be cleaned annually and if it has oiling ports, it should be oiled with a good grade of SAE 20 oil. Normally a few drops of oil in each bearing is sufcient. COIL The coil must be kept clean by any of the following methods.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York YPHBC c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York YPHBC - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York YPHBC, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York YPHBC va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York YPHBC, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York YPHBC.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York YPHBC. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York YPHBC ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.