TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 14.5 SEER – R-410A MODELS: YCJF24 THRU 60 (2 THRU 5 NOMINA L TONS, 1 PHASE) Due to continuou s pro duc t impro vement, speci f ic a tio ns are subject to chan ge without notice. Vi si t us on the web at ww w .
413437-YTG-C-0908 2 Johnson Controls Unitary Products All dimensions are in inches. The y are subject to change with- out notice. Certified dimensions will be provi ded upon request.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 3 Additional R-410A Charge / Orifice Size for V arious Matched Sys tems Out door Unit YCJF24S41S1 YCJF30S41S1 YCJF36S41S1 Y CJF42S41S1 Y CJF48S41S.
413437-YTG-C-0908 4 Johnson Controls Unitary Products PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser, the smallest evaporator and 15 feet of intercon- necting line tubing.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SE NS . 14.5 SEER AC WITH MA YCJF24S41S1 MA08B 17 FC/MC24B 800 24.
413437-YTG-C-0908 6 Johnson Controls Unitary Products — = Not applicable. 14.5 SEER AC WITH MV - V ARIABLE SPEED (Contimued) YCJF42S41S1 MV16C 21 FC/MC43C 1400 41.0 30 .8 15.00 12.75 MV16C 21 FC/MC48C 1400 41.5 31 .2 15.50 13.00 MV20D 24 FC/MC48D 1400 42.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - Upflow , Downflow & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TE D CFM NET MBH SEER 1 EER TOT AL SE NS . YCJF24S41S1 600 - 1000 14,17 FC/MC/PC24 800 24.
413437-YTG-C-0908 8 Johnson Controls Unitary Products COOLING CAP ACITY - YCJF24S41S1 With V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 14.5 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC24A 14 750 24.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 9 Y*9C*B12 FC/MC/PC43B 17 800 24.0 16.8 16.00 13.50 Y*(8,L)C*A12 HC30 14 775 24.0 16.8 15.75 13.25 Y*(8,L)C*B12 HC36 17 760 24.0 16.7 15.75 13.50 Y*9C*B12 HC36 17 815 24.0 17.0 15.75 13.50 Y*(8,L)C*A12 HD36 14 805 24.
413437-YTG-C-0908 10 Johnson Controls Unitary Products COOLING CAP ACITY - YCJF30S41S1 With V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT A L SENS. 14.5 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC30A 14 1000 29.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 11 PV8*A12 UC30A 14 1000 29.4 21.2 15.25 13.00 PV8*B16 UC30B 17 1050 29.8 21.8 15.50 13.25 PV9*A12 UC30A 14 1000 29.4 21.2 15.00 12.75 Y*(8,L)C*A12 FC/MC/PC30A 14 1090 29.4 21.6 14.50 12.25 Y*(8,L)C*B12 FC/MC/PC30B 17 955 29.
413437-YTG-C-0908 12 Johnson Controls Unitary Products G*9V*C16 FC/MC/PC35C 21 1005 29.6 22.0 15.75 13 .25 G*9V*C20 FC/MC/PC35C 21 985 29.6 22 .0 15.75 13.25 G*9V*A12 FC/MC/PC36A 14 1000 29.4 21.2 15.25 12.75 G*9V*B12 FC/MC/PC36B 17 985 29.4 21.4 15.50 13.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 13 PV8*C16 FC/MC/PC48C 21 1200 35.4 26.0 16.25 13.25 PV8*C20 FC/MC/PC48C 21 1200 35.4 26.0 16.25 13.25 P(C,V)9*C16 FC/MC/PC48C 21 1200 35.2 25.8 16.00 13.25 P(C,V)9*C20 FC/MC/PC48C 21 1200 35.2 25.
413437-YTG-C-0908 14 Johnson Controls Unitary Products Y*(8,L)C*C16 FC/PC60C 21 1 195 35.4 26.0 16.25 13 .55 Y*(8,L)C*C20 FC/PC60C 21 1215 35.4 26.0 16.20 13 .50 Y*9C*C16 FC/PC60C 21 1235 35.0 25.8 15.50 13.00 Y*9C*C20 FC/PC60C 21 1330 35.6 27.2 15.65 13.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 15 COOLING CAP ACITY - YCJF42S41S1 Wi th V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SE NS . 14.5 SEER AC WITH V ARIAB LE SPEED FURNACES 2 PV8*B16 FC/MC/PC43B 17 1400 41.
413437-YTG-C-0908 16 Johnson Controls Unitary Products Y*(8,L)C*B12 HD48 17 1350 41.0 29.8 14.75 12.50 Y*(8,L)C*C16 HD48 21 1435 41.5 30 .8 15 .25 13.00 Y*(8,L)C*C20 HD48 21 1410 42.0 31 .0 15 .25 13.00 Y*9C*B12 HD48 17 1 150 40.0 28.2 14.75 12.50 Y*9C*C16 HD48 21 1395 41 .
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 17 COOLING CAP ACITY - YCJF48S41S1 Wi th V ariable Speed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SE NS . 14.5 SEER AC WITH V ARIAB LE SPEED FURNACES 2 PV8*C16 FC/MC/PC48C 21 1500 46.
413437-YTG-C-0908 18 Johnson Controls Unitary Products G*9V*C20 FC/PC60C 21 1655 47 .0 33.0 14.75 12.50 G*9V*D20 FC/MC/PC60D 24 1615 47.0 33.0 14.75 12 .50 G*9V*C20 FC/MC62D 21 1655 47.0 33.2 14.75 12 .50 G*9V*D20 FC/MC62D 24 1630 47.0 33.4 15.00 12 .
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 19 ACCESSORIES Refer to Price Manua l for specific model numbers. OFF CYCLE TIMER DELA Y - Provides a 5-minute off cycle to prevent rapid recycling of the compressor .
413437-YTG-C-0908 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. For dry bulb temperatures dif ferent th an those listed (betwe en 73- 8.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 21 V ariable Speed Furnace Coil T .C. S.C. KW PV8*A12 FC/MC/PC24A 1.02 1.05 0.94 PV9*A12 FC/MC/PC24A 1.03 1.06 0.96 P(C,V)9*B12 FC/MC/PC24B 1.03 1.06 0.95 PV8*A12 FC/MC/PC30A 1.02 1.05 0.94 PV9*A12 FC/MC/PC30A 1.
413437-YTG-C-0908 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 23 P(C,V)9*C20 FC/MC/PC36C 1.00 0.99 0.93 PV8*A12 FC/MC/PC37A 1.01 1.01 0.96 PV9*A12 FC/MC/PC37A 1.01 1.01 0.97 PV8*B16 FC/MC/PC43B 1.03 1.05 0.93 PV8*C16 FC/MC/PC43C 1.02 1.02 0.92 PV8*C20 FC/MC/PC43C 1.
413437-YTG-C-0908 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 25 V ariable Speed Furnace Coil T .C. S.C. KW PV8*B16 FC/MC/PC35B 0.99 0.99 0.95 PV8*C16 FC/MC/PC35C 0.99 0.99 0.94 PV8*C20 FC/MC/PC35C 1.00 1.00 0.94 P(C,V)9*B12 FC/MC/PC35B 0.99 0.99 0.97 P(C,V)9*C16 FC/MC/PC35C 0.
413437-YTG-C-0908 26 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 27 V ariable Speed Furnace Coil T .C. S.C. KW PV8*B16 FC/MC/PC43B 1.00 0.99 0.97 PV8*C20 FC/MC/PC43C 1.00 1.00 0.96 P(C,V)9*C16 FC/MC/PC43C 1.00 0.99 0.98 P(C,V)9*C20 FC/MC/PC43C 1.00 1.00 0.96 PV8*C16 FC/MC/PC48C 1.
413437-YTG-C-0908 28 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween.
413437-YTG -C-0908 Johnson Controls Unitary Pro ducts 29 V ariable Speed Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.99 0.97 0.98 PV8*C20 FC/MC/PC48C 1.00 1.00 0.99 P(C,V)9*C16 FC/MC/PC48C 1.00 1.00 1.00 P(C,V)9*C20 FC/MC/PC48C 1.00 1.01 0.98 PV8*C16 FC/MC/PC60C 0.
Subject to change without notice. Printe d in U.S.A. 413437-YTG-C-0908 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 413437-YTG-B-0608 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York YCJF24 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York YCJF24 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York YCJF24, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York YCJF24 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York YCJF24, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York YCJF24.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York YCJF24. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York YCJF24 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.