GENERAL These condensing units are designed for outdoor installation on a roof or at ground level. Every unit is completely piped and wired at the factory and is shipped ready for immediate installa- tion.
035-15407-002-B-0404 2 Unitary Products Group General ................................................................................ 1 Reference ............................................................................ 1 Inspection ..............
LIMIT ATIONS These units must be installed in accordance with all national and local safety codes. If no local codes apply , installation must conform with the appropriate national codes. See T able 1 for Unit Application Data. Units are designed to meet National Safety Code Standards.
CLEARANCES All units require certain minimum clearances for proper opera- tion and service. Refer to Figure 4 for these clearances. WARNING: Do not permit overhanging structures or shrubs to obstruct condenser air discharge. Additional height may be required for snow clearance if winter operation is expected.
035-15407-002-B-0404 Unitary Products Group 5 Model HCE V oltage Code Compressor Condenser Fan Motor Unit Ampacity (Amps) Max. Fuse Size 1 (Amps) Power Supply RLA LRA Power Supply HP Qty . FLA 090 25 208/230-3-60 25.6 190 208/230-1-60 3/4 1 3.03 35.1 60 46 460-3-60 12.
035-15407-002-B-0404 6 Unitary Products Group FIG. 5 - UNIT DIMENSIONS AND CLEARANCES A I R O U T A I R I N 4- 5/ 8 ( 118) 2 5 - 3 / 4 ( 6 5 5 ) 1 0 - 1 / 8 ( 2 5 8 ) 2 - 1 / 2 ( 6 . 4 ) 4 - 1 / 2 ( 115) G U A G E L I N E A C C E S S 1 - 1 / 8 " ( 2 8 .
REFRIGERANT PIPING GENERAL GUIDELINES Many service problems can be avoided by taking adequate precautions to provide an internally clean and dry system and by using procedures and materials that conform with estab- lished standards. Use hard drawn copper tubing where no appreciable amount of bending around pipes or other obstructions is necessary .
035-15407-002-B-0404 8 Unitary Products Group NOTE: Add the operating charge of the condensing unit, the evaporator coil and the refrigerant lines to determine the total refrigerant charge of the system. 1 Charges are based on 40 ° F suction temperature and a 105 ° F liquid temperature.
EXTENDING THE SERVICE PORTS (Refer to Fig 7.) 1. Loosen the screws securing the service ports in shipping position. 2. Push the service ports through the corner post.
10. After the disc has been removed, burnish the external sur - faces and clean the internal surfaces as outlined above. The suction piping can now be brazed to the suction connection on the evaporator coil while maintaining a minimum flow of dry nitrogen.
035-15407-002-B-0404 Unitary Products Group 11 FIG. 7 - EXTENDING THE SERVICE PORTS.
035-15407-002-B-0404 12 Unitary Products Group FIG. 8 - CHARGING CURVE HCE090 FIG. 9 - CHARGING CURVE HCE120.
035-15407-002-B-0404 Unitary Products Group 13 FIG. 10 - CHARGING CURVE HCE150.
UNIT OPERATION - 7-1/2, 10 & 12-1/2 TON When the external control calls for cooling at terminal Y1: 1. The system controller (SC) is energized. The system con - troller starts the compressors and enables the condenser fans by energizing contactor 1M (and 2M on the 12-1/2 ton, 208/230 volt models).
If the unit continues to be shut down by one of its safety con - trols, service should be called to determine the cause of the problem. Repeatedly resetting the lockout circuit may damage the unit. The following accessories are available to provide low am - bient operation to 0 ° F.
Unitary Products Group 5005 Y ork Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright © 2004 by Y ork International Corporation.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York H5CE090 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York H5CE090 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York H5CE090, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York H5CE090 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York H5CE090, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York H5CE090.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York H5CE090. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York H5CE090 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.