DESCRIPTION This fan coil unit provides the flexibility for installation in any upflow or horizontal application. These versatile models may be used for split-system cooling or heat pump operation. Compact cabinets along with return air options in both the upflow and horizontal positions allow this unit to fit into tight spaces such as attics, crawl spaces, and closets.

York F*FV — TECHNICAL GUIDE diagram (page 1)
Fig. 2
York F*FV — TECHNICAL GUIDE diagram (page 1)
Fig. 3

FEATURES CABINET -The compact and sturdy cabinet is protected with a durable, attractive finish to prevent rust. The cabinet is also insulated to prevent cabinet sweating. F*FP and F*FV mod- els have 3/4 inch insulation.

TECHNICAL GUIDE

SINGLE PIECE AIR HANDLERS

FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS

BLOWERS - Blowers are sized to circulate air both quietly and efficiently. The direct-drive, multi-speed motors provide a selection of air volume to match any application. Motor speeds may be selected via quick connect terminal at the motor. Slide-out blower/motor assemblies provide for easy servicing.

HEAT PUMP MODELS:

F*FP VARIABLE SPEED MODEL:

F*FV

COILS - Using the latest in heat transfer technology, the rifled tube coil/aluminum fin coils produce high performance ratings and provide long lasting quality. The coils are capable of bot- tom return air in the upflow position, and right or left end return air in the horizontal position.

FACTORY INSTALLED TXV - Air handler models F*FP and F*FV have factory installed TXV metering device.

ELECTRIC HEATERS - Models providing up to 25kw of heat are available as field installed accessories. Electric heaters are available in both single and three phase.

EASY INSTALLATION - These fan coil units are designed to provide the lowest total installation cost. Accessible color coded control wiring, top and side power wiring knockouts, easy to install drain connections and electric heaters all com- bine to minimize installed cost on every job.

CONTROL BOARD - The control board is equipped with low voltage terminal strips for easy installation. The control board is also equipped with plug-in receptacles for the auxiliary heaters.

ISO 9001 Certified Quality Management System

Due to continuous product improvement, specifications are subject to change without notice.

Visit us on the web at www.york.com

Additional rating information can be found at www.ari.org/aridirectory

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

Page 2 of the York F*FV user manual — DIMENSIONS
Page 2 · cliquer pour agrandir
Page 2

DIMENSIONS

York F*FV — DIMENSIONS diagram (page 2)
Fig. 4

ALL DIMENSIONS ARE IN INCHES. THEY ARE SUBJECT TO CHANGE WITHOUT NOTICE. CERTIFIED DIMENSIONS WILL BE PROVIDED UPON REQUEST.

(21 INCHES) MAX. FILTER WIDTH (B MINUS 1-1/2 INCHES)

FILTER ACCESS DRAIN CONNECTIONS FOR UPFLOW APPLICATIONS BOTTOM VIEW

ModelDimensionsWiring K.O.s1Refrigerant Connections Line Size ABCDEFJKLiquidVapor HeightWidthDepthPowerControl F4FP024H06T2*40-3/4182212-1/8 17-3/814-7/816-1/27/8 (1/2) 1-3/8 (1)7/8 (1/2)3/85/8 F4FP030H06T2*40-3/41814-7/816-1/23/4 F4FP036H06T2*40-3/421-1/218-3/8203/4 F4FP040H06T2*40-3/421-1/218-3/8207/8 F4FP042H06T2*40-3/421-1/218-3/8207/8 F4FP045H06T2*50-3/42420-7/822-1/27/8 (1/2) 1-3/8(1) 1-23/32 (1-1/4)7/8 F5FP048H06T2*50-3/42420-7/822-1/27/8 F5FP060H06T2*50-3/42420-7/822-1/27/8 F4FV060H06T2*50-3/42420-7/822-1/27/8
York F*FV — DIMENSIONS diagram (page 2)
Fig. 5
1. Actual conduit size is shown in parenthesis. 2. All models only available with factory installed horizontal drain pan.
Page 3 of the York F*FV user manual — COOLING CAPACITY
Page 3 · cliquer pour agrandir
Page 3

COIL TECHNICAL DATA

ModelsApplicationRefrigerant Connection TypeFace Area (Sq. Ft.)Deep RowsFins Per InchCoil Slab SizeTube GeometryTube Dia.Fin. TypeMetering Device HW F4FP024H06T2AA/C & HPSweat3.402141417.51 x .8863/8EnhancedTXV-2A F4FP024H06T2BA/C & HP3.402141417.5TXV-2B F4FP030H06T2AA/C & HP3.892141617.5TXV-2A F4FP036H06T2AA/C & HP3.403121417.5TXV-2A F4FP040H06T2AA/C & HP3.893111617.5TXV-2A F4FP040H06T2CA/C & HP3.893111617.5TXV-2C F4FP042H06T2AA/C & HP3.893111617.5TXV-2A F4FP042H06T2CA/C & HP3.893111617.5TXV-2C F4FP045H06T2CA/C & HP5.833122417.5TXV-2C F5FP048H06T2CA/C & HP5.353122217.5TXV-2C F5FP060H06T2CA/C & HP5.833122417.5TXV-2C F4FV060H06T2CA/C & HP5.833122417.5TXV-2C

COOLING CAPACITY

Blower ModelRated CFMEntering Air °F (Dry / Wet Bulb)MBH @ Evaporator Temperature and Corresponding Pressure °F / PSIG 35 / 61.540 / 68.545 / 76.050 / 84.0 Upflow / Horizontal Positions Only F4FP024H06T2*83085 / 72 80 / 67 75 / 62 70 / 5736.3 33.4 27.4 22.233.0 30.2 24.3 19.329.5 26.7 21.0 16.225.6 23.1 17.7 12.6 F4FP030H06T2*105085 / 72 80 / 67 75 / 62 70 / 5741.5 36.2 29.1 24.137.8 32.4 25.3 21.533.7 28.6 24.0 18.729.5 24.5 19.2 15.8 F4FP036H06T2*125085 / 72 80 / 67 75 / 62 70 / 5753.4 42.8 33.4 28.748.6 37.8 28.1 26.543.4 33.1 30.6 24.538.3 28.2 22.8 22.8 F4FP040H06T2*105085 / 72 80 / 67 75 / 62 70 / 5755.3 44.2 34.5 29.647.5 37.1 27.5 26.039.6 30.2 22.4 22.431.2 23.1 18.7 18.7 F4FP042H06T2*140085 / 72 80 / 67 75 / 62 70 / 5788.4 70.8 55.2 47.476.0 59.4 43.9 41.563.3 48.4 35.8 35.850.0 37.0 29.9 29.9 F4FP045H06T2*140085 / 72 80 / 67 75 / 62 70 / 5792.7 74.2 57.8 49.778.1 61.3 45.3 42.863.4 48.4 35.7 35.748.1 35.4 28.6 28.6 F5FP048H06T2*160085 / 72 80 / 67 75 / 62 70 / 57100.5 80.4 62.7 53.986.4 67.5 49.9 47.272.0 55.0 40.7 40.756.8 42.1 34.0 34.0 F5FP060H06T2*185085 / 72 80 / 67 75 / 62 70 / 57119.9 96.0 74.8 64.3101.0 79.2 58.6 55.482.0 62.6 46.2 46.262.2 45.8 37.0 37.0 F4FV060H06T2*198085 / 72 80 / 67 75 / 62 70 / 57122.0 98.1 76.9 66.4103.1 81.3 60.7 57.584.1 64.7 50.3 48.364.3 47.9 39.1 39.1
Page 4 of the York F*FV user manual — EXTENDED AIRFLOW DATA 1 FOR 230 VOLT - HEAT PUMP MODELS
Page 4 · cliquer pour agrandir
Page 4

ACCESSORIES Refer to Price Manual for specific model numbers.

LIMITATIONS These units must be wired and installed in accordance with all national and local safety codes. Voltage limits are as fol- lows:

VERTICAL SUSPENSION KIT - The suspension kit is designed to be used with all sizes of fan coil units whenever the application requires vertical suspension of the unit.

Normal Operating voltage Range1

ELECTRIC HEATERS - Models shown under Electrical Data include sequencers and temperature dual limit switches for safe, efficient operation. Circuit breakers are provided where shown.

1. Utilization range “A” in accordance with ARI Std. 110.

Air flow must be within the minimum and maximum limits approved for electric heat, evaporator coils and outdoor units:

BOLT-ON THERMAL EXPANSION VALVE - TXV kits are available for enhanced efficiency. These fan coil units have factory installed TXV’s.

Entering Air Temperature Limits Wet Bulb Temp. ºFDry Bulb Temp. ºF Min.Max.Min.Max. 57726595

EXTENDED AIRFLOW DATA 1 FOR 230 VOLT - HEAT PUMP MODELS

ModelsBlower Motor Speed230 Volt CFM @ External Static Pressure - IWC 0.100.200.300.400.500.600.700.800.901.00 F4FP024H06T2*High950910865835775730662590502400 Med845815785745705654594524439344 Low650630605575540508450383285158 F4FP030H06T2*High1,2701,2101,1501,0851,015946862769645502 Med1,0501,040995930855804714624494364 Low855820780735680624550447333190 F4FP036H06T2*High-1,3101,2501,1751,1201,053983894779645 Med1,2001,1501,1001,040985933879795711587 Low1,0601,015970925860809740661572453 F4FP040H06T2*High1,2701,2101,1501,0851,015946802769645502 Med1,0501,040995930855804714624494364 Low855820780735680624550447333190 F4FP042H06T2*High-1,5751,5001,4201,3501,2731,1921,102996871 Med1,4601,3951,3301,2601,1901,1251,052960842695 Low1,2501,2001,1551,1001,0501,001931851751631 F4FP045H06T2*High1,5751,5351,4751,3901,3101,2451,1471,030897735 Med High1,3751,3151,2551,1851,1101,040944848732606 Med Low1,2101,1601,1101,050980921844737640533 Low1,035990940890825770698616524432 F5FP048H06T2*High2223215820902029192918611788167915941501 Med High1948190418011815177717411681161815391453 Med1741169016491606156415161476143613871353 Med Low1499145414151370132812691228119111321093 Low128612331177114210921039987960888842 F5FP060H06T2*High2195214520702008192018521754166315701462 Med High1938189918731824179117241679160315211420 Med1726168116411607156015171485143314021349 Med Low1525148314411383135612911253120811691123 Low1306125412041160111410611008980914876 F4FV060H06T2*High2,2852,1952,1052,0151,9501,8451,7701,6851,5901,485 Med.2,1252,0201,9101,8051,7051,5971,4911,3861,2801,175 Low1,6551,6051,5501,5001,4501,3981,3261,2451,1531,052
1. Includes Return Air Filter and Largest Electric Heater. All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

187-253

Page 5 of the York F*FV user manual — APPLICATION FACTORS-RELATED CFM VS. ACTUAL CFM
Page 5 · cliquer pour agrandir
Page 5

EXTENDED AIR FLOW DATA 1 FOR 208 VOLT - HEAT PUMP MODELS

ModelsBlower Motor Speed208 Volt CFM @ External Static Pressure - IWC 0.100.200.300.400.500.600.700.800.901.00 F4FP024H06T2*High855819779752698657596531452360 Med.760733706670634589535472395310 Low585567545518486457405344257142 F4FP030H06T2*High114310891035977914851776692581451 Med.941936895837770724643562445328 Low770738702662612561495402300171 F4FP036H06T2*High12351179112510581008947885804701580 Med.10801035990936887840791716640528 Low954914873833774728666595515408 F4FP040H06T2*High114310891035977914851776692581451 Med.941936895837770724643562445328 Low770738702662612561495402300171 F4FP042H06T2*High1400141813501278121511451073991897784 Med.131412661197113510711012947864758625 Low112510801040990945901838766676568 F4FP045H06T2*High1418138213281251117911201032927807661 Med-high1238118411301067999936850763659545 Med-low10891044999945882829760663576480 Low932891846801743693628554472389 F5FP048H06T2*High2209214020932000193918641746172416551587 Med High1945190618711819178417411667164015951550 Med1739169016401602155915161470143113871343 Med Low1506146414151369132512831238119311391100 Low1301124811971151109510541005958909860 F5FP060H06T2*High2134212420521979186117561639159715121427 Med High1916187518381777174416711594158415371490 Med1716167116131569152314751429138413371290 Med Low1494143513901341128412411194113910871036 Low127612231168111510681009965902847792 F4FV060H06T2*High2057197618951814172816611593151714311337 Med.1913181817191625153514371342124711521057 Low149014451395135013051258119411201038946
1. Includes Return Air Filter and Largest Electric Heater. All F*FP series air handler units are UL Listed up to 0.50" w.c. external static pressure, including air filter, wet coil, and largest KW size heater.

APPLICATION FACTORS-RELATED CFM VS. ACTUAL CFM

% Of Rated Airflow80%90%RATED CFM110%120% Capacity Factor0.960.981.001.021.03
Page 6 of the York F*FV user manual — ELECTRIC HEAT CFM
Page 6 · cliquer pour agrandir
Page 6

EXTENDED AIR FLOW DATA - F4FV VARIABLE SPEED MODELS

CFM/TAP SELECTION - F4FV 1

DELAY PROFILE

High SpeedCooling andHeat Pump CFM ModelJumperSetting F4FV060H06T2*"COOL” TAP“ADJ TAP“ 2100“A”“B" 1980"B”"B" 1860"A”"A" 1750"B”"A" 1675"A”"C" 1605"C”"B" 1575"B”"C" 1510"D”"B" 1420"C”"A" 1335"D”"A" 1280"C”"C" 1200"D”“C” NOTE:
"DELAY" TapComfort Setting ANormal BHumid CDry DTemperate

Normal The normal setting provides a 30-second ramp-up from zero airflow to full capacity and a 30-second ramp-down from full capacity back to zero airflow. Whenever there is a change in airflow mode, such as a call for cooling or a change from low heat to high heat, the motor will take 30 seconds to ramp from one speed to the other.

Humid The humid setting is best-suited for installations where the humidity is frequently very high during cooling season, such as in the southern part of the country. On a call for cooling, the blower will ramp up to 50% of full capacity and will stay there for two minutes, then will ramp up to 82% of full capac- ity and will stay there for five minutes, and then will ramp up to full capacity, where it will stay until the wall thermostat is satisfied. In every case, it will take the motor 30 seconds to ramp from one speed to another.

1. Both the “COOL” and the “ADJ” tap must be set for the cooling CFM. 2. Fan only CFM = 63% of high speed cooling. 3. Low speed cooling used only with two stage outdoor units. (Speed is preset to 65% of high speed). 4. Dehumidification speed is 85% of cooling speed. 5. When operating in both heat pump and electric heat modes, the CFM will be whichever is greater. 6. CFM indicator light flashes once for every 100 CFM (i.e., 12 Flashes is 1200 CFM).

Dry The dry setting is best suited to parts of the country where excessive humidity is not generally a problem, where the summer months are usually dry. On a call for cooling the motor will ramp up to full capacity and will stay there until the thermostat is satisfied. At the end of the cooling cycle, the blower will ramp down to 50% of full capacity where it will stay for 60 seconds. Then it will ramp down to zero. In every case, it will take the motor 30 seconds to ramp from one speed to another.

ELECTRIC HEAT CFM

ModelCFMTap Selections F4FV060H06T2*–"HEAT" 1860"A" 1750"B" 1420"C" 1335"D"

Temperate The temperate setting is best suited for most of the country, where neither excessive humidity nor extremely dry condi- tions are the norm. On a call for cooling, the motor will ramp up to 63% of full capacity and will stay there for 90 seconds, then will ramp up to full capacity. At the end of the cooling cycle, the motor will ramp down to 63% of full capacity and will stay there for 30 seconds, then will ramp down to zero. In every case, it will take the motor 30 seconds to ramp from one speed to another.

Page 7 of the York F*FV user manual — ELECTRICAL DATA - Cooling Only
Page 7 · cliquer pour agrandir
Page 7

Physical and Electrical Data

MODELF4FP024H06T2*F4FP030H06T2*F4FP036H06T2*F4FP040H06T2*– Blower - Diameter Width10x610x810x810x8– MotorHP1/41/31/21/3– Nominal RPM1075107510751075– Voltage208/230 AMPSFull Load1.6/1.42.5/2.23.3/2.92.5/2.2– Locked Rotor3.3/2.96.2/5.57.4/6.56.2/5.5– Filter1TypeDisposable/Permanent Size16x20x116x20x120x20x120x20x1– Permanent Type Kit1PF0601BK1PF0601BK1PF0602BK1PF0601BK– Shipping/Operating Weight (lbs.)98/93105/100115/109121/115– MODELF4FP042H06T2*F4FP045H06T2*F5FP048H06T2*F5FP060H06T2*F4FV060H06T2* Blower - Diameter x Width10x810x1011x1011x1011x10 MotorHP3/41/31.01.01.0 Nominal RPM1130925105010501200 Voltage208/230230 AmpsFull Load4.4/3.83.0/2.77.67.67.8/7.0 Locked Rotor11.9/10.34.8/4.1––– Filter1TypeDisposable/Permanent Size20x20x122x20x122x20x122x20x122x20x1 Permanent Type Kit1PF0602BK1PF0603BK1PF0603BK1PF0603BK1PF0603BK Shipping/Operating Weight (lbs.)121/115150/144153/147160/154160/154
1. Field Supplied.

ELECTRICAL DATA - Cooling Only

ModelsTotal Motor AmpsMinimum Circuit ampacityMax. O.C.P.1 Amps/ TypeMinimum Wire Size A.W.G. 208V240V208V240V F4FP024H06T2*1.61.52.01.81514 F4FP030H06T2*2.52.33.22.81514 F4FP036H06T2*3.33.04.23.71514 F4FP040H06T2*2.52.33.22.81514 F4FP042H06T2*4.44.05.54.81514 F4FP045H06T2*3.12.63.93.41514 F5FP048H06T2*7.67.69.59.51514 F5FP060H06T2*7.67.69.59.51514 VARIABLE SPEED MODEL F4FV060H06T2*––––1514
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay Fuse.
Page 8 of the York F*FV user manual — KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
Page 8 · cliquer pour agrandir
Page 8

ELECTRICAL DATA - 1∅ - 208/230 - 1-60

ModelsHeater1 ModelMAX. STATIC & MIN. CFMTotal Heat2KW Staging3 KWMBHW1 OnlyW2 OnlyW1 + W2 StaticTap208V240V208V240V208V240V208V240V208V240V F4FP024H06T2*2HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 F4FP030H06T2*2HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BHigh11.315.038.651.23.85.07.510.011.315.0 F4FP036H06T2*2HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BMed11.315.038.651.23.85.07.510.011.315.0 2HK16501906B4High13.217.645.160.12.83.810.413.813.217.6 F4FP040H06T2*2HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BHigh11.315.038.651.23.85.07.510.011.315.0 F4FP042H06T2*2HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BLow7.510.025.634.13.85.07.510.07.510.0 2HK16501506BLow11.315.038.651.23.85.07.510.011.315.0 F4FP045H06T2*2HK*6500506B0.5Low3.85.013.017.13.85.03.85.03.85.0 2HK*6500806BLow5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BMed7.510.025.634.13.85.07.510.07.510.0 2HK16501506BHigh11.315.038.651.23.85.07.510.011.315.0 F5FP048H06T2*2HK16500506B0.5Med-Low3.85.013.017.13.85.03.85.03.85.0 2HK16500806BMed-Low5.67.519.125.63.85.05.67.55.67.5 2HK*6501006BMed-Low7.510.025.634.13.85.07.510.07.510.0 2HK16501506BMed-Low11.315.038.651.23.85.07.510.011.315.0 2HK16502006BMed-Low15.020.051.268.33.85.011.310.015.020.0 2HK16502506BMed-Low18.825.064.285.33.85.011.315.018.825.0 F5FP060H06T2*2HK*6501006B0.5Med3.85.013.017.13.85.03.85.03.85.0 2HK16500806BMed5.67.519.125.63.85.05.67.55.67.5 2HK16501006BMed7.510.025.634.13.85.07.510.07.510.0 2HK16501506BMed11.315.038.651.23.85.07.510.011.315.0 2HK16502006BMed15.020.051.268.33.85.07.510.015.020.0 2HK16502506BMed18.825.064.285.33.85.011.315.018.825.0 F4FV060H06T2*2HK*6500806B0.513355.67.519.125.63.85.05.67.55.67.5 2HK*6501006B13357.510.025.634.13.85.07.510.07.510.0 2HK16501506B133511.315.038.651.23.85.07.510.011.315.0 2HK16502006B133515.020.051.268.33.85.07.510.015.020.0 2HK16502506B133518.825.064.285.33.85.011.315.018.825.0
1. 0 or as follows: 0 = No Breaker, 1 = Breaker.
2. See Conversion Table below:
3. If first stage heat or 66 is connected to W1, otherwise refer to this table.
4. 2HK16501906B only applies to F4FP036 Model.

KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT

FOR 230V OPERATION MULTIPLY 240V TABULATED KW & MBH BY .918

Page 9 of the York F*FV user manual — KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
Page 9 · cliquer pour agrandir
Page 9

ELECTRICAL DATA - 1∅ (SINGLE SOURCE POWER SUPPLY) - COPPER WIRE

ModelsHeater Model1Heater Amps 240VField Wiring Min. Circuit AmpacityMax. O.C.P.2 Amps/Type75°C Wire Size - AWG 208V240V208V240V208V240V F4FP024H06T2*2HK*6500506B20.824.727.725301010 2HK*6500806B31.335.540.7404588 2HK*6501006B41.746.953.7506086 F4FP030H06T2*2HK*6500506B20.825.828.730301010 2HK*6500806B31.336.741.7404588 2HK*6501006B41.748.154.7506086 2HK16501506B62.570.980.8809043 F4FP036H06T2*2HK*6500506B20.826.829.530301010 2HK*6500806B31.337.742.6404588 2HK*6501006B41.749.155.6506086 2HK16501506B62.571.981.6809043 2HK16501906B373.383.395.29010033 F4FP040H06T2*2HK*6500506B20.825.828.730301010 2HK*6500806B31.336.741.7404588 2HK*6501006B41.748.154.7506086 2HK16501506B62.570.980.8809043 F4FP042H06T2*2HK*6500506B20.828.130.53035108 2HK*6500806B31.338.943.6404588 2HK*6501006B41.750.356.6606066 2HK16501506B62.573.282.6809043 F4FP045H06T2*2HK*6500506B20.826.629.330301010 2HK*6500806B31.337.442.3404588 2HK*6501006B41.748.855.3506086 2HK16501506B62.571.781.4809043 F5FP048H06T2*2HK16500506B20.832.835.6354088 2HK*6500806B31.343.048.4455088 2HK*6501006B41.755.361.5607064 2HK16501506B62.577.387.8809043 2HK16502006B83.3101.0113.811012521 2HK16502506B104.2124.3139.912515011/0 F5FP060H06T2*2HK*6500506B20.832.835.6354088 2HK*6500806B31.342.948.3455088 2HK*6501006B41.755.361.6607064 2HK16501506B62.578.587.8809043 2HK16502006B83.3101.0113.811012521 2HK16502506B104.2122.2139.512515011/0 F4FV060H06T2*2HK*6500806B31.343.847.8455088 2HK*6501006B41.755.260.8607064 2HK16501506B62.578.086.9809043 2HK16502006B83.3100.3112.911012521 2HK16502506B104.2123.1139.012515011/0
York F*FV — KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT diagram (page 9)
Fig. 6
1. 0 or 1 as follows: 0 = No Breaker, 1 = Breaker
2. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.
3. 2HK16501906B only applies to F4FP036 Model.
Page 10 of the York F*FV user manual — KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
Page 10 · cliquer pour agrandir
Page 10

ELECTRICAL DATA - 1 Ø (MULTI-SOURCE POWER SUPPLY) - COPPER WIRE

ModelsHeater ModelMin. Circuit AmpacityMax. O.C.P.1 Amps/Type75°C Wire Size - AWG CircuitCircuitCircuit 1st2nd3rd1st2nd3rd1st2nd3rd 208/240V208/240V208/240V208/240V208/240V208/240V208/240V208/240V208/240V F4FP030H06T2*2HK16501506B25.8/28.745.1/52.1—30/3050/60—10/108/6— F4FP036H06T2*2HK16501506B26.8/29.545.1/52.1—30/3050/60—10/108/6— 2HK16501906B238.3/42.645.7/52.6—40/4550/60—8/88/6— F4FP040H06T2*2HK16501506B25.8/28.745.1/52.1—30/3050/60—10/108/6— F4FP042H06T2*2HK16501506B28.1/30.545.1/52.1—30/3550/60—10/88/6— F4FP045H06T2*2HK16501506B26.6/29.345.1/52.1—30/3050/60—10/108/6— F5FP048H06T2*2HK16501506B32.8/35.645.1/52.1—35/4050/60—8/88/6— 2HK16502006B55.3/61.645.1/52.1—60/7050/60—6/48/6— 2HK16502506B32.8/35.645.1/52.145.1/52.135/4050/6050/608/88/68/6 F5FP060H06T2*2HK16501506B32.8/35.645.1/52.1—35/4050/60—8/88/6— 2HK16502006B55.3/61.645.1/52.1—60/7050/60—6/48/6— 2HK16502506B33.8/35.645.1/52.145.1/52.135/4050/6050/608/88/68/6 F4FV060H06T2*2HK16501506B33.0/34.845.1/52.1—35/3550/60—8/88/6— 2HK16502006B55.2/60.845.1/52.1—60/7050/60—6/48/6— 2HK16502506B33.0/34.845.1/52.145.1/52.135/3550/6050/608/88/68/6
York F*FV — ELECTRICAL DATA - 1 Ø (MULTI-SOURCE POWER SUPPLY) - COPPER WIRE diagram (page 10)
Fig. 7
1. OCP = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse. 2. 2HK16501906B only applies to F4FP036 Model.

ELECTRICAL DATA - 3 ∅ - 208/230-3-60

ModelsHeater ModelMAX. STATIC & MIN. CFMTotal Heat1KW Staging2 KWMBHW1 OnlyW2 OnlyW1 + W2 StaticTap208V240V208V240V208V240V208V240V208V240V F4FP024H06T2*2HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 F4FP030H06T2*2HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 F4FP036H06T2*2HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 F4FP040H06T2*2HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 F4FP042H06T2*2HK06501025B0.5Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5Low11.315.038.651.23.85.07.510.011.315.0 F4FP045H06T2*2HK06501025B0.5Med7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5High11.315.038.651.23.85.07.510.011.315.0 F5FP048H06T2*2HK06501025B0.5Med Low7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5Med Low11.315.038.651.23.85.07.510.011.315.0 F5FP060H06T2*2HK06501025B0.5Med7.510.025.634.13.85.07.55.07.510.0 2HK06501525B0.5Med11.315.038.651.23.85.07.510.011.315.0 F4FV060H06T2*2HK06501025B0.513357.510.025.634.13.85.07.510.07.510.0 2HK06501525B0.5133511.315.038.851.23.85.07.510.011.315.0
1. See Conversion Table below.
2. If first stage heat is connected to W1/66, otherwise refer to Table below.

KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT

FOR 230V OPERATION MULTIPLY 240V TABULATED KW & MBH BY .918

Page 11 of the York F*FV user manual — OUTDOOR UNIT
Page 11 · cliquer pour agrandir
Page 11

ELECTRICAL DATA - 3∅ - (SINGLE SOURCE POWERSUPPLY) - COPPER WIRE

ModelsHeater ModelsField Wiring Min. Circuit AmpacityMax. O.C.P.1 Amps75°C Wire Size - AWG 208V240V208V240V208V240V F4FP024H06T2*2HK06501025B41.246.5455088 F4FP030H06T2*2HK06501025B42.247.4455088 2HK06501525B42.247.4455088 F4FP036H06T2*2HK06501025B43.148.2455088 2HK06501525B43.148.2455088 F4FP040H06T2*2HK06501025B42.247.4455088 2HK06501525B42.247.4455088 F4FP042H06T2*2HK06501025B44.249.1455088 2HK06501525B44.249.1455088 F4FP045H06T2*2HK06501025B42.847.9455088 2HK06501525B42.847.9455088 F5FP048H06T2*2HK06501025B48.353.9506086 2HK06501525B48.353.9506086 F5FP060H06T2*2HK06501025B48.353.9506086 2HK06501525B48.353.9506086 F4FV060H06T2*2HK06501025B48.652.9506086 2HK06501525B48.652.9506086
1. O.C.P. = Over Current Protection device, must be HACR type Circuit Breaker or Time Delay fuse.

FIELD WIRING CONNECTION - COOLING ONLY FIELD WIRING CONNECTION - WITH HEATER KIT

OUTDOOR UNIT

OUTDOOR UNIT

THERMOSTAT

THERMOSTAT

R

R

Y

Y

G

G

W

W

FAN COIL UNIT

FAN COIL UNIT

R Y G W2 W1 O C

R Y G W2 W1 O C

* NOT REQUIRED ON 2 OR 5KW

*

Page 12 of the York F*FV user manual — Y1
Page 12 · cliquer pour agrandir
Page 12

FIELD WIRING CONNECTIONS - COOLING MODELS WITH ELECTRIC HEAT WIRING

F* SERIES F* SERIES

Air Handler Control Wiring Typical A/C - Cooling only Applications

Air Handler Control Wiring Typical A/C with Electric Heat Applications

THERMOSTAT AIR HANDLER

THERMOSTAT AIR HANDLER

BOARD 1 - STAGE AIR CONDITIONING R R

BOARD 1 - STAGE AIR CONDITIONING R R

Y Y

Y

Y Y

Y

G G

G G

1 Field Installed Jumper - If Required

W1

W1

HUMIDISTAT

W1

W1

HUMIDISTAT

W2

W2

W2

W2

O

O

HUM

HUM

CFM selection board only on F4FV model

1 NOTEDehumidification control connection (”Humidistat” jumper on CFM selection board

CFM selection board only on F4FV model

Y1

Y1

Y2

Y2

FIELD WIRING CONNECTIONS - SINGLE STAGE HEAT PUMP

AIR HANDLER

BOARD HEAT PUMP

THERMOSTAT

R R R

Y Y Y

G G

E W1 W1 Out

W2 W2

O O O

L X/L

W1 W

HUMIDISTAT 1

HUM

CFM selection board only on F4FV model

Y1

Y2

1. “Y” Terminal on Air Handler Control Board must be connected for full CFM and applications requiring 60 second Blower Off Delay for SEER enhancement.
2. 1 Optional Dehumidification Humidistat contacts open on rise. 3. For F4FV model - Remove Humidistat Jumper on CFM Selection Board - if used. 4. For F4FV model - For Heat Pump Applications - Remove Heat Pump Jumper on CFM Selection Board. 5. To change quantity of heat during HP defrost cycle - Reverse connections at W1 and W2 on Air Handler Control Board.

t b d) · t b d)

Page 13 of the York F*FV user manual — TYPICAL APPLICATIONS
Page 13 · cliquer pour agrandir
Page 13

TYPICAL INSTALLATION

York F*FV — TYPICAL INSTALLATION diagram (page 13)
Fig. 8

TYPICAL APPLICATIONS

York F*FV — TYPICAL APPLICATIONS diagram (page 13)
Fig. 9
Page 14 of the York F*FV user manual — TYPICAL INSTALLATION
Page 14 · cliquer pour agrandir
Page 14
Page 14 of the York F*FV user manual — TYPICAL INSTALLATION
Page 15 of the York F*FV user manual — TYPICAL INSTALLATION
Page 15 · cliquer pour agrandir
Page 15
Page 15 of the York F*FV user manual — TYPICAL INSTALLATION
Page 16 of the York F*FV user manual — Unitary 5005 Norman Products York OK Group Drive 73069
Page 16 · cliquer pour agrandir
Page 16

Subject to change without notice. Printed in U.S.A. 295421-YTG-B-0707 Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 295421-YTG-A-0507

Unitary 5005 Norman Products York OK Group Drive 73069

Poser une question sur : York F*FV

Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Aucune question pour l'instant sur le York F*FV

Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.

Document d'origine

York F*FV manuel PDF

16 pages·184 KB·Climatiseur·PDF
Cliquez sur une page ci-dessus pour l'ouvrir ici
Page 1 / …
100%
Chargement des pages…