SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERSp.1D3CE / D3CG 180 & 240 (WORLD 50 HZ)p.1SUNLINE 2000p.1DESCRIPTIONp.1FIELD-INSTALLED ACCESSORIESp.2TABLE OF CONTENTSp.2(OPTION / ACCESS.) DCE UNITSp.3ALUMINIZED STEELp.3THROWAWAYp.3D*CG UNITSp.3(OPTION / ACCESSORY)p.3FEMALEp.3MODEL DCGp.3RATINGSp.3CAPACITY RATINGS - Cooling / Electric Heatingp.3CAPACITY RATINGS - Gas Heatingp.3COOLING CAPACITIES (m 3 /s Air Flow) - 180 UNITSp.4COOLING CAPACITIES (m 3 /s Air Flow) - 240 UNITSp.6BLOWER PERFORMANCE (D*CE180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.8STANDARD DRIVE (m /s) 3p.8HIGH SPEED DRIVE (m /s) 3p.8STANDARD DRIVE (CFM)p.8HIGH SPEED DRIVE (CFM)p.8BLOWER PERFORMANCE (D*CE240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.9BLOWER PERFORMANCE (D*CG180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.10STANDARD DRIVE (m /s)p.10BLOWER PERFORMANCE (D*CG240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.11BLOWER MOTOR AND DRIVE DATAp.12STATIC RESISTANCES*p.12FIELD WIRING - Electric/Electric and Gas/Electric Unitsp.13N NEUTRAL TERMINALp.1324 VOLT TRANSFORMERp.13GRD. LUGp.13ELECTRICAL DATA - Cooling Only Units and Units With Gas Heatp.13OUTDOORp.13SUPPLY AIRp.13TOTAL UNITp.13COMPRESSORp.13FAN MOTOR, (#1 & #2) FLA, EACHp.13BLOWER MOTOR, (FLA)p.13AMPACITY,p.13MAX. FUSE SIZE 1p.13MIN. WIRE SIZE 2 ,p.13UNIT SIZEp.13POWER SUPPLYp.13(AMPS)p.13ELECTRICAL DATA - Units With Supplemental Electric Heatingp.14PHYSICAL DATAp.14COMPONENT DESCRIPTION UNIT SIZE (MBH)p.14INDOORp.14COILp.14AIR FILTERSp.14UNIT DIMENSIONS - D*CE180 & 240 UNITSp.15RETURN AIRp.15CLEARANCES (mm / in.)p.15UTILITIES ENTRY DATAp.15OPENING DIAMETER*p.15HOLEp.15USED FORp.15UNIT DIMENSIONS - D*CG180 & 240 UNITSp.16CLEARANCES (mm / in. )p.16UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d.)p.17DETAIL “X” ACCESSORY SIDE SUPPLY AND RETURN AIR DUCT OPENINGSp.17DETAIL “Y” UNIT WITH ECONOMIZER AND FIXED OUTDOOR AIR HOODSp.17OUTDOOR COIL END OF UNITp.17CENTER OF GRAVITYp.17ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITSp.18ROOF CURB BENEFITSp.18UNIT AND CURB APPLICATIONp.18TYPICAL APPLICATIONSp.18ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN)p.19
Page 1 of the York D3CE user manual — DESCRIPTION
Page 1 · cliquer pour agrandir
Page 1
York D3CE — SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS diagram (page 1)
Fig. 1

SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS

D3CE / D3CG 180 & 240 (WORLD 50 HZ)

SUNLINE 2000

York D3CE — D3CE / D3CG 180 & 240 (WORLD 50 HZ) diagram (page 1)
Fig. 2

DESCRIPTION

Sunline 2000 units are highly efficient, convertible rooftops. All models have dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. These units are designed and manufactured under ISO 9002 Quality System Certification. Cooling only, cooling with gas heat and cooling with supplemental electric heat units are available with a wide variety of field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails. The base rails have holes in the four corners for overhead rigging.

With horizontal ductwork, it should be mounted on the return air duct.

All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.

All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls.

Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard.

All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.

All models are available with three different outdoor air damper accessosries:

  • Single enthalpy economizer
  • Differential enthalpy economizer
  • Motorized outdoor air intake damper

The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.

All models (including those with an economizer ) are suitable for either downflow or sideflow duct connections. For downflow duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For sideflow duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory.

All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.

A fixed outdoor air intake assembly is shipped in the return air compartment of all units. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel.

The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.

® · DCG Shown

Page 2 of the York D3CE user manual — Table des matières
Page 2 · Table des matières
Table des matières

Table des matières

SINGLE PACKAGE GAS / ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERSp.1D3CE / D3CG 180 & 240 (WORLD 50 HZ)p.1SUNLINE 2000p.1DESCRIPTIONp.1FIELD-INSTALLED ACCESSORIESp.2TABLE OF CONTENTSp.2(OPTION / ACCESS.) DCE UNITSp.3ALUMINIZED STEELp.3THROWAWAYp.3D*CG UNITSp.3(OPTION / ACCESSORY)p.3FEMALEp.3MODEL DCGp.3RATINGSp.3CAPACITY RATINGS - Cooling / Electric Heatingp.3CAPACITY RATINGS - Gas Heatingp.3COOLING CAPACITIES (m 3 /s Air Flow) - 180 UNITSp.4COOLING CAPACITIES (m 3 /s Air Flow) - 240 UNITSp.6BLOWER PERFORMANCE (D*CE180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.8STANDARD DRIVE (m /s) 3p.8HIGH SPEED DRIVE (m /s) 3p.8STANDARD DRIVE (CFM)p.8HIGH SPEED DRIVE (CFM)p.8BLOWER PERFORMANCE (D*CE240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.9BLOWER PERFORMANCE (D*CG180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.10STANDARD DRIVE (m /s)p.10BLOWER PERFORMANCE (D*CG240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONSp.11BLOWER MOTOR AND DRIVE DATAp.12STATIC RESISTANCES*p.12FIELD WIRING - Electric/Electric and Gas/Electric Unitsp.13N NEUTRAL TERMINALp.1324 VOLT TRANSFORMERp.13GRD. LUGp.13ELECTRICAL DATA - Cooling Only Units and Units With Gas Heatp.13OUTDOORp.13SUPPLY AIRp.13TOTAL UNITp.13COMPRESSORp.13FAN MOTOR, (#1 & #2) FLA, EACHp.13BLOWER MOTOR, (FLA)p.13AMPACITY,p.13MAX. FUSE SIZE 1p.13MIN. WIRE SIZE 2 ,p.13UNIT SIZEp.13POWER SUPPLYp.13(AMPS)p.13ELECTRICAL DATA - Units With Supplemental Electric Heatingp.14PHYSICAL DATAp.14COMPONENT DESCRIPTION UNIT SIZE (MBH)p.14INDOORp.14COILp.14AIR FILTERSp.14UNIT DIMENSIONS - D*CE180 & 240 UNITSp.15RETURN AIRp.15CLEARANCES (mm / in.)p.15UTILITIES ENTRY DATAp.15OPENING DIAMETER*p.15HOLEp.15USED FORp.15UNIT DIMENSIONS - D*CG180 & 240 UNITSp.16CLEARANCES (mm / in. )p.16UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d.)p.17DETAIL “X” ACCESSORY SIDE SUPPLY AND RETURN AIR DUCT OPENINGSp.17DETAIL “Y” UNIT WITH ECONOMIZER AND FIXED OUTDOOR AIR HOODSp.17OUTDOOR COIL END OF UNITp.17CENTER OF GRAVITYp.17ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITSp.18ROOF CURB BENEFITSp.18UNIT AND CURB APPLICATIONp.18TYPICAL APPLICATIONSp.18ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN)p.19
Page 3 of the York D3CE user manual — CAPACITY RATINGS - Gas Heating
Page 3 · cliquer pour agrandir
Page 3

SUNLINE 2000

York D3CE — SUNLINE 2000 diagram (page 3)
Fig. 3

(OPTION / ACCESS.) DCE UNITS

ALUMINIZED STEEL

THROWAWAY

D*CG UNITS

(OPTION / ACCESSORY)

FEMALE

MODEL DCG

RATINGS

CAPACITY RATINGS - Cooling / Electric Heating

York D3CE — (OPTION / ACCESS.) DCE UNITS diagram (page 3)
Fig. 4
ModelRating1 PointTotal Output, Mbh / kWTotal Input, kWCOP2EER3Sensible Output, Mbh / kWLatent Output, Mbh / kWElectric Heat4 Nominal Capacity, kW D3CE180T1 T2 T3159 / 46.6 142 / 41.7 152 / 44.618.2 20.0 16.42.60 2.10 2.758.80 7.15 9.40132 / 38.7 141 / 41.2 119 / 34.926.9 / 7.9 1.6 / 0.5 33.2 / 9.718, 36, 54, 72 D3CE240T1 T2 T3210 / 61.5 182 / 53.3 196 / 57.524.8 27.1 22.22.50 2.00 2.608.50 6.75 8.80176 / 51.5 182 / 53.3 152 / 44.634.0 / 10.0 0.0 / 0.0 42.6 / 12.518, 36, 54, 72

1T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.

2COP = Coefficient of Performance - total output kW divided by the total input kW.

3EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.

4Heaters available as factory-installed options or field-installed accessories - all with single point power supply.

CAPACITY RATINGS - Gas Heating

York D3CE — CAPACITY RATINGS - Gas Heating diagram (page 3)
Fig. 5 · CAPACITY RATINGS - Gas Heating
ModelCooling Capacity, Mbh / kWGas Heat Capacity Input (Net) Mbh / kWOutput Mbh / kWGas Rate* cfh / m3/hTemp. Rise (°F / °C) At Full Input Min.Max. D3CG180N320180 / 52.7291 / 85.2258 / 75.6302 / 8.530 / 1760 / 33 D3CG240N320240 / 70.3

*Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m3).

® · (Gas Heating)

Page 4 of the York D3CE user manual — COOLING CAPACITIES (m 3 /s Air Flow) - 180 UNITS
Page 4 · cliquer pour agrandir
Page 4

COOLING CAPACITIES (m 3 /s Air Flow) - 180 UNITS

Total Cap.1 kWPower Input2 kW WB °C3230282624
3.4023 21 19 17 1566.4 62.3 58.2 56.7 55.214.7 14.4 14.0 14.0 13.951 59 58 57 5544 52 58 57 5537 44 52 56 5530 37 45 49 5223 30 38 41 45- 23 31 34 37 2.8023 21 19 17 1561.5 57.7 53.9 52.5 51.114.5 14.2 13.9 13.8 13.746 53 54 52 5140 46 53 52 5134 40 47 51 5127 34 41 44 4821 28 35 38 42- 22 28 32 35 2.1023 21 19 17 1557.1 53.6 50.1 48.7 47.414.3 14.0 13.6 13.6 13.537 43 48 49 4732 38 44 47 4728 33 39 42 4523 29 34 37 4019 24 30 33 36- 19 25 28 31
3.4023 21 19 17 1560.7 57.2 53.7 52.3 51.015.9 15.5 15.2 15.1 15.050 57 54 52 5143 50 54 52 5136 43 51 52 5129 36 43 47 4722 29 36 40 40- 22 29 32 33 2.8023 21 19 17 1556.3 53.1 49.8 48.6 47.315.9 15.6 15.2 15.1 15.044 51 50 49 4738 44 50 49 4732 38 45 48 4725 32 39 41 4419 26 32 35 38- 20 26 29 32 2.1023 21 19 17 1551.9 48.9 45.9 44.7 43.615.6 15.3 14.9 14.8 14.736 41 46 45 4431 37 42 45 4427 32 38 40 4322 27 33 35 3817 23 28 31 33- 18 24 26 29
3.4023 21 19 17 1549.6 47.3 45.0 43.6 42.118.2 17.6 17.1 17.1 17.146 47 45 44 4239 46 45 44 4232 39 45 44 4225 32 39 40 3918 25 32 33 31- 18 25 26 24 2.8023 21 19 17 1549.4 47.2 44.9 43.4 42.017.8 17.2 16.6 16.6 16.641 47 45 43 4235 42 45 43 4229 36 42 43 4223 29 36 37 3917 23 30 31 33- 17 24 25 27 2.1023 21 19 17 1546.5 44.4 42.3 40.9 39.517.5 17.0 16.4 16.4 16.433 39 42 41 4029 34 40 41 4024 30 35 36 3819 25 31 32 3315 20 26 27 28- 16 21 22 24

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

Page 5 of the York D3CE user manual — COOLING CAPACITIES (m 3 /s Air Flow) - 180 UNITS
Page 5 · cliquer pour agrandir
Page 5
Total Cap.1 MBHPower Input2 kW WB °F9086827975
720073 70 66 63 59227 213 199 193 18814.7 14.4 14.0 14.0 13.9175 200 199 193 188151 176 199 193 188126 152 177 190 188102 127 153 166 17678 103 128 142 152- 79 104 117 128 593073 70 66 63 59210 197 184 179 17414.5 14.2 13.9 13.8 13.7157 180 184 179 174136 159 182 179 174115 138 160 172 17493 116 139 151 16372 95 118 130 142- 74 97 109 121 445073 70 66 63 59195 183 171 166 16214.3 14.0 13.6 13.6 13.5127 146 165 166 162111 130 149 159 16295 114 133 143 15379 98 117 127 13763 82 101 111 121- 66 86 96 105
720073 70 66 63 59207 195 183 179 17415.9 15.5 15.2 15.1 15.0170 195 183 179 174146 171 183 179 174122 147 172 179 17498 123 148 159 16274 99 124 135 138- 75 100 111 113 593073 70 66 63 59192 181 170 166 16115.9 15.6 15.2 15.1 15.0150 172 170 166 161129 151 170 166 161108 130 153 162 16187 109 132 141 15166 88 110 120 130- 67 89 99 109 445073 70 66 63 59177 167 157 153 14915.6 15.3 14.9 14.8 14.7123 142 157 153 149107 126 145 153 14991 110 129 137 14575 94 113 121 12959 78 97 105 113- 62 81 89 97
720073 70 66 63 59169 161 154 149 14418.2 17.6 17.1 17.1 17.1157 161 154 149 144133 158 154 149 144109 134 154 149 14485 110 135 137 13261 85 110 112 107- 61 86 88 83 593073 70 66 63 59169 161 153 148 14317.8 17.2 16.6 16.6 16.6141 161 153 148 143120 142 153 148 14399 121 144 148 14378 100 123 128 13357 79 102 107 112- 58 81 86 90 445073 70 66 63 59159 151 144 139 13517.5 17.0 16.4 16.4 16.4114 133 144 139 13598 117 136 139 13582 101 120 124 12866 85 104 108 11250 69 88 92 96- 53 72 76 80

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

Page 6 of the York D3CE user manual — COOLING CAPACITIES (m 3 /s Air Flow) - 240 UNITS
Page 6 · cliquer pour agrandir
Page 6

COOLING CAPACITIES (m 3 /s Air Flow) - 240 UNITS

Total Cap.1 kWPower Input2 kW WB °C3230282624
4.4023 21 19 17 1580.4 77.6 74.8 72.4 70.019.0 18.8 18.6 18.4 18.174 78 75 72 7065 70 75 72 7055 61 67 71 7046 52 57 62 6537 43 48 53 56- 33 39 44 47 3.8023 21 19 17 1576.9 74.3 71.6 69.3 67.018.8 18.6 18.4 18.2 17.968 73 72 69 6760 65 70 69 6752 57 62 67 6744 49 54 59 6336 41 46 51 55- 33 38 43 47 2.8023 21 19 17 1571.2 68.7 66.3 64.1 62.018.5 18.3 18.1 17.9 17.656 60 65 64 6250 54 59 62 6244 48 52 56 6037 42 46 50 5431 36 40 44 47- 30 34 38 41
4.4023 21 19 17 1574.9 72.3 69.8 67.4 65.021.0 20.7 20.4 20.1 19.971 72 70 67 6561 68 70 67 6552 58 65 67 6543 49 55 58 6034 40 46 49 51- 31 37 40 42 3.8023 21 19 17 1571.3 68.9 66.4 64.2 61.920.7 20.5 20.2 19.9 19.765 69 66 64 6257 62 66 64 6249 54 60 63 6241 46 52 55 5833 38 44 47 50- 30 36 39 42 2.8023 21 19 17 1565.4 63.1 60.9 58.8 56.720.4 20.1 19.8 19.6 19.352 57 61 59 5746 51 56 58 5740 45 50 52 5434 39 44 46 4828 33 38 40 42- 27 31 34 36
4.4023 21 19 17 1566.4 63.3 60.2 59.0 57.823.4 22.9 22.3 22.3 22.265 63 60 59 5856 62 60 59 5847 53 60 59 5838 44 51 53 5329 35 41 43 44- 26 32 34 35 3.8023 21 19 17 1563.8 60.8 57.8 56.7 55.523.3 22.7 22.2 22.1 22.160 61 58 57 5652 58 58 57 5644 50 56 57 5636 42 48 50 5228 34 40 42 44- 26 32 34 35 2.8023 21 19 17 1559.4 56.6 53.8 52.8 51.723.1 22.5 22.0 21.9 21.949 54 54 53 5242 47 53 53 5236 41 46 48 4930 35 40 42 4324 29 34 36 37- 23 28 30 31

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

Page 7 of the York D3CE user manual — COOLING CAPACITIES (m 3 /s Air Flow) - 240 UNITS
Page 7 · cliquer pour agrandir
Page 7
Total Cap.1 MBHPower Input2 kW WB °F9086827975
932073 70 66 63 59274 265 255 247 23919.0 18.8 18.6 18.4 18.1252 265 255 247 239221 240 255 247 239189 208 227 243 239158 177 196 211 223127 146 164 180 192- 114 133 149 161 805073 70 66 63 59263 253 244 236 22918.8 18.6 18.4 18.2 17.9232 250 244 236 229205 222 240 236 229177 195 213 228 229150 168 186 200 215123 141 158 173 188- 113 131 146 160 593073 70 66 63 59243 234 226 219 21218.5 18.3 18.1 17.9 17.6191 206 221 219 212170 185 200 212 212149 164 179 191 204128 143 158 170 183107 122 137 149 162- 101 116 128 141
932073 70 66 63 59256 247 238 230 22221.0 20.7 20.4 20.1 19.9241 247 238 230 222209 230 238 230 222178 199 220 230 222147 168 189 199 206115 136 157 168 175- 105 126 136 143 805073 70 66 63 59243 235 227 219 21120.7 20.5 20.2 19.9 19.7221 235 227 219 211193 213 227 219 211166 186 206 215 211139 158 178 188 197111 131 151 161 170- 104 124 133 143 593073 70 66 63 59223 215 208 201 19320.4 20.1 19.8 19.6 19.3179 195 208 201 193158 174 191 199 193137 153 170 178 186116 133 149 157 16595 112 128 136 144- 91 107 115 123
932073 70 66 63 59226 216 205 201 19723.4 22.9 22.3 22.3 22.2223 216 205 201 197191 213 205 201 197160 182 204 201 197129 151 172 179 18297 119 141 148 150- 88 110 117 119 805073 70 66 63 59218 207 197 193 18923.3 22.7 22.2 22.1 22.1204 207 197 193 189177 197 197 193 189149 170 190 193 189122 142 163 169 17695 115 136 142 148- 88 108 115 121 593073 70 66 63 59203 193 184 180 17623.1 22.5 22.0 21.9 21.9166 183 184 180 176145 162 179 180 176124 141 158 164 169103 120 137 143 14882 99 116 122 127- 78 95 101 106

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

Page 8 of the York D3CE user manual — HIGH SPEED DRIVE (CFM)
Page 8 · cliquer pour agrandir
Page 8

BLOWER PERFORMANCE (D*CE180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS

STANDARD DRIVE (m /s) 3

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.10 m3/s2.45 m3/s2.80 m3/s3.10 m3/s3.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 845 885 925 960 1000 10406.0 5.0 4.0 3.0 2.0 1.0173 208 245 281 323 3691.8 1.9 2.0 2.1 2.3 2.42.2 2.3 2.4 2.6 2.7 2.9138 172 208 242 283 3272.2 2.3 2.4 2.6 2.7 2.92.6 2.8 2.9 3.1 3.2 3.483 115 149 182 222 2642.6 2.7 2.9 3.0 3.2 3.33.1 3.3 3.4 3.6 3.8 4.018 49 82 114 152 1933.0 3.1 3.3 3.4 3.6 3.83.5 3.7 3.9 4.1 4.3 4.5- - - 30 67 107- - - 3.8 4.0 4.2- - - 4.6 4.8 5.1
York D3CE — STANDARD DRIVE (m /s) 3 diagram (page 8)
Fig. 6 · STANDARD DRIVE (m /s) 3

HIGH SPEED DRIVE (m /s) 3

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.10 m3/s2.45 m3/s2.80 m3/s3.10 m3/s3.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 1030 1070 1115 1155 1200 12406.0 5.0 4.0 3.0 2.0 1.0357 405 461 514 577 6362.4 2.5 2.7 2.9 3.1 3.32.8 3.0 3.2 3.4 3.7 3.9316 362 416 468 529 5872.8 3.0 3.2 3.4 3.6 3.83.4 3.6 3.8 4.0 4.3 4.5253 298 351 401 461 -3.3 3.5 3.7 3.9 4.1 -3.9 4.2 4.4 4.7 5.0 -183 226 278 - - -3.7 3.9 4.2 - - -4.5 4.7 5.0 - - -97 -4.2 -5.0 -
York D3CE — HIGH SPEED DRIVE (m /s) 3 diagram (page 8)
Fig. 7 · HIGH SPEED DRIVE (m /s) 3

STANDARD DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 4450 CFM5190 CFM5930 CFM6565 CFM7200 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 845 885 925 960 1000 10406.0 5.0 4.0 3.0 2.0 1.00.7 0.8 1.0 1.1 1.3 1.52.4 2.6 2.7 2.9 3.0 3.22.2 2.3 2.4 2.6 2.7 2.90.6 0.7 0.8 1.0 1.1 1.32.9 3.1 3.3 3.4 3.6 3.82.6 2.8 2.9 3.1 3.2 3.40.3 0.5 0.6 0.7 0.9 1.13.5 3.7 3.8 4.0 4.2 4.53.1 3.3 3.4 3.6 3.8 4.00.1 0.2 0.3 0.5 0.6 0.84.0 4.2 4.4 4.6 4.8 5.13.5 3.7 3.9 4.1 4.3 4.5- - - 0.1 0.3 0.4- - - 5.2 5.4 5.7- - - 4.6 4.8 5.1
York D3CE — STANDARD DRIVE (CFM) diagram (page 8)
Fig. 8

HIGH SPEED DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 4450 CFM5190 CFM5930 CFM6565 CFM7200 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 1030 1070 1115 1155 1200 12406.0 5.0 4.0 3.0 2.0 1.01.4 1.6 1.9 2.1 2.3 2.63.2 3.4 3.6 3.9 4.1 4.42.8 3.0 3.2 3.4 3.7 3.91.3 1.5 1.7 1.9 2.1 2.43.8 4..0 4.3 4.5 4.8 5.13.4 3.6 3.8 4.0 4.3 4.51.0 1.2 1.4 1.6 1.8 -4.4 4.7 5.0 5.2 5.5 -3.9 4.2 4.4 4.7 5.0 -0.7 0.9 1.1 - - -5.0 5.3 5.6 - - -4.5 4.7 5.0 - - -0.4 -5.6 -5.0 -
York D3CE — HIGH SPEED DRIVE (CFM) diagram (page 8)
Fig. 9

NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.

Page 9 of the York D3CE user manual — HIGH SPEED DRIVE (CFM)
Page 9 · cliquer pour agrandir
Page 9

BLOWER PERFORMANCE (D*CE240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS

STANDARD DRIVE (m /s) 3

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.80 m3/s3.30 m3/s3.80 m3/s4.10 m3/s4.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 765 795 820 850 875 9056.0 5.0 4.0 3.0 2.0 1.0137 176 209 250 284 3272.9 3.0 3.1 3.3 3.4 3.63.3 3.4 3.6 3.8 3.9 4.193 132 165 206 240 2832.9 3.1 3.2 3.4 3.6 3.83.3 3.5 3.7 3.9 4.1 4.323 62 95 136 170 2123.2 3.4 3.6 3.8 4.0 4.33.7 3.9 4.1 4.4 4.6 4.9- - 40 81 115 157- - 4.0 4.2 4.4 4.7- - 4.5 4.8 5.0 5.3- - - 16 51 93- - - 4.7 4.9 5.2- - - 5.3 5.6 5.9
York D3CE — STANDARD DRIVE (m /s) 3 diagram (page 9)
Fig. 10 · STANDARD DRIVE (m /s) 3

HIGH SPEED DRIVE (m /s) 3

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.80 m3/s3.30 m3/s3.80 m3/s4.10 m3/s4.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 895 930 970 1005 1045 10806.0 5.0 4.0 3.0 2.0 1.0312 362 421 473 535 5903.5 3.7 4.0 4.2 4.4 4.64.0 4.3 4.5 4.8 5.0 5.3268 318 377 429 491 5463.7 4.0 4.2 4.5 4.8 5.04.3 4.5 4.9 5.1 5.5 5.8198 248 306 359 420 4754.2 4.5 4.8 5.1 5.4 5.74.8 5.1 5.5 5.8 6.2 6.5143 193 252 304 365 4204.6 4.9 5.2 5.6 5.9 6.25.2 5.6 6.0 6.4 6.8 7.179 129 187 240 - -5.1 5.4 5.8 6.1 - -5.8 6.2 6.6 7.0 - -
York D3CE — HIGH SPEED DRIVE (m /s) 3 diagram (page 9)
Fig. 11 · HIGH SPEED DRIVE (m /s) 3

STANDARD DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 5930 CFM6990 CFM8050 CFM8685 CFM9320 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 765 795 820 850 875 9056.0 5.0 4.0 3.0 2.0 1.00.6 0.7 0.8 1.0 1.1 1.33.8 4.0 4.2 4.4 4.6 4.83.3 3.4 3.6 3.8 3.9 4.10.4 0.5 0.7 0.8 1.0 1.13.9 4.1 4.4 4.6 4.8 5.13.3 3.5 3.7 3.9 4.1 4.30.1 0.2 0.4 0.5 0.7 0.94.3 4.6 4.8 5.1 5.4 5.73.7 3.9 4.1 4.4 4.6 4.9- - 0.2 0.3 0.5 0.6- - 5.3 5.6 5.9 6.3- - 4.5 4.8 5.0 5.3- - - 0.1 0.2 0.4- - - 6.2 6.6 6.9- - - 5.3 5.6 5.9
York D3CE — STANDARD DRIVE (CFM) diagram (page 9)
Fig. 12

HIGH SPEED DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 5930 CFM6990 CFM8050 CFM8685 CFM9320 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 895 930 970 1005 1045 10806.0 5.0 4.0 3.0 2.0 1.01.3 1.5 1.7 1.9 2.1 2.44.7 5.0 5.3 5.6 5.9 6.24.0 4.3 4.5 4.8 5.0 5.31.1 1.3 1.5 1.7 2.0 2.25.0 5.3 5.7 6.0 6.4 6.84.3 4.5 4.9 5.1 5.5 5.80.8 1.0 1.2 1.4 1.7 1.95.6 6.0 6.4 6.8 7.3 7.74.8 5.1 5.5 5.8 6.2 6.50.6 0.8 1.0 1.2 1.5 1.76.1 6.6 7.0 7.4 7.9 8.45.2 5.6 6.0 6.4 6.8 7.10.3 0.5 0.8 1.0 - -6.8 7.2 7.8 8.2 - -5.8 6.2 6.6 7.0 - -
York D3CE — HIGH SPEED DRIVE (CFM) diagram (page 9)
Fig. 13

NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.

Page 10 of the York D3CE user manual — HIGH SPEED DRIVE (CFM)
Page 10 · cliquer pour agrandir
Page 10

BLOWER PERFORMANCE (D*CG180 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS

STANDARD DRIVE (m /s)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.10 m3/s2.45 m3/s2.80 m3/s3.10 m3/s3.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 845 885 925 960 1000 10406.0 5.0 4.0 3.0 2.0 1.0206 242 278 311 349 3871.8 1.9 2.0 2.1 2.2 2.32.2 2.3 2.4 2.5 2.6 2.8146 183 220 253 292 3312.0 2.2 2.3 2.4 2.6 2.72.5 2.6 2.7 2.9 3.1 3.380 117 155 189 228 2682.4 2.5 2.7 2.8 3.0 3.22.8 3.0 3.2 3.4 3.6 3.918 56 94 128 168 2092.7 2.9 3.1 3.2 3.5 3.73.2 3.4 3.7 3.9 4.2 4.4- - 28 63 103 144- - 3.5 3.7 4.0 4.3- - 4.2 4.5 4.8 5.1
York D3CE — STANDARD DRIVE (m /s) diagram (page 10)
Fig. 14 · STANDARD DRIVE (m /s)

HIGH SPEED DRIVE (m /s) 3

York D3CE — HIGH SPEED DRIVE (m /s) 3 diagram (page 10)
Fig. 15 · HIGH SPEED DRIVE (m /s) 3
BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.10 m3/s2.45 m3/s2.80 m3/s3.10 m3/s3.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 1030 1070 1115 1155 1200 12406.0 5.0 4.0 3.0 2.0 1.0378 417 461 502 548 5902.3 2.4 2.6 2.8 3.0 3.22.7 2.9 3.1 3.3 3.6 3.8321 361 407 448 495 5382.7 2.9 3.1 3.3 3.6 3.83.2 3.4 3.7 4.0 4.3 4.6258 299 345 387 435 -3.2 3.4 3.7 3.9 4.2 -3.8 4.1 4.4 4.7 5.0 -199 240 286 - - -3.6 3.9 4.2 - - -4.4 4.7 5.0 - - -134 -4.2 -5.0 -

STANDARD DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 4450 CFM5190 CFM5930 CFM6565 CFM7200 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 845 885 925 960 1000 10406.0 5.0 4.0 3.0 2.0 1.00.8 1.0 1.1 1.2 1.4 1.62.5 2.6 2.7 2.8 2.9 3.12.2 2.3 2.4 2.5 2.6 2.80.6 0.7 0.9 1.0 1.2 1.32.7 2.9 3.1 3.2 3.4 3.72.5 2.6 2.7 2.9 3.1 3.30.3 0.5 0.6 0.8 0.9 1.13.2 3.4 3.6 3.8 4.0 4.32.8 3.0 3.2 3.4 3.6 3.90.1 0.2 0.4 0.5 0.7 0.83.6 3.8 4.1 4.3 4.7 5.03.2 3.4 3.7 3.9 4.2 4.4- - 0.1 0.3 0.4 0.6- - 4.7 5.0 5.3 5.7- - 4.2 4.5 4.8 5.1
York D3CE — STANDARD DRIVE (CFM) diagram (page 10)
Fig. 16

HIGH SPEED DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 4450 CFM5190 CFM5930 CFM6565 CFM7200 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 1030 1070 1115 1155 1200 12406.0 5.0 4.0 3.0 2.0 1.01.5 1.7 1.9 2.0 2.2 2.43.1 3.3 3.5 3.7 4.0 4.32.7 2.9 3.1 3.3 3.6 3.81.3 1.4 1.6 1.8 2.0 2.23.6 3.8 4.1 4.4 4.8 5.13.2 3.4 3.7 4.0 4.3 4.61.0 1.2 1.4 1.6 1.7 -4.3 4.5 4.9 5.2 5.6 -3.8 4.1 4.4 4.7 5.0 -0.8 1.0 1.2 - - -4.9 5.2 5.6 - - -4.4 4.7 5.0 - - -0.5 -5.6 -5.0 -
York D3CE — HIGH SPEED DRIVE (CFM) diagram (page 10)
Fig. 17

NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.

Page 11 of the York D3CE user manual — HIGH SPEED DRIVE (CFM)
Page 11 · cliquer pour agrandir
Page 11

BLOWER PERFORMANCE (D*CG240 UNIT SUPPLY AIR) - w/DOWNFLOW DUCT APPLICATIONS

STANDARD DRIVE (m /s) 3

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.80 m3/s3.30 m3/s3.80 m3/s4.10 m3/s4.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 765 795 820 850 875 9056.0 5.0 4.0 3.0 2.0 1.0202 238 268 305 336 3472.1 2.3 2.4 2.5 2.7 2.82.4 2.6 2.7 2.9 3.0 3.280 117 150 189 222 2622.7 2.9 3.0 3.2 3.4 3.63.1 3.3 3.4 3.7 3.8 4.1- - - 50 85 128- - 3.9 4.1 4.3- - - 4.5 4.7 5.0- 37- 4.8- 5.5---
York D3CE — STANDARD DRIVE (m /s) 3 diagram (page 11)
Fig. 18 · STANDARD DRIVE (m /s) 3

HIGH SPEED DRIVE (m /s) 3

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 2.80 m3/s3.30 m3/s3.80 m3/s4.10 m3/s4.40 m3/s ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW)ESP (Pa)Output (kW)Input (kW) 895 925 955 990 1020 1050 10806.0 5.0 4.0 3.0 2.0 1.0 0.0361 400 439 486 527 569 6122.8 2.9 3.1 3.3 3.5 3.7 3.93.2 3.4 3.6 3.8 4.0 4.2 4.4249 290 332 381 425 469 5143.5 3.7 3.9 4.1 4.3 4.6 4.84.0 4.2 4.4 4.7 5.0 5.2 5.5114 157 201 254 299 346 3934.3 4.5 4.7 5.0 5.2 5.5 5.84.9 5.1 5.4 5.7 6.0 6.3 6.622 66 112 166 213 261 3104.7 5.0 5.2 5.5 5.8 6.1 6.45.4 5.7 6.0 6.3 6.7 7.0 7.3- - 15 70 119 - -- - 5.8 6.1 6.4 - -- - 6.6 7.0 7.3 - -
York D3CE — HIGH SPEED DRIVE (m /s) 3 diagram (page 11)
Fig. 19 · HIGH SPEED DRIVE (m /s) 3

STANDARD DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 5930 CFM6990 CFM8050 CFM8685 CFM9320 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 765 795 820 850 875 9056.0 5.0 4.0 3.0 2.0 1.00.8 1.0 1.1 1.2 1.3 1.52.8 3.0 3.2 3.4 3.6 3.82.4 2.6 2.7 2.9 3.0 3.20.3 0.5 0.6 0.8 0.9 1.13.6 3.8 4.0 4.3 4.5 4.83.1 3.3 3.4 3.7 3.8 4.1- - - 0.2 0.3 0.5- - - 5.3 5.5 5.8- - - 4.5 4.7 5.0- 0.1- 6.5- 5.5---
York D3CE — STANDARD DRIVE (CFM) diagram (page 11)
Fig. 20

HIGH SPEED DRIVE (CFM)

BLOWER SPEED, RPMMOTOR PULLEY (TURNS OPEN)*AIRFLOW 5930 CFM6990 CFM8050 CFM8685 CFM9320 CFM ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW)ESP (iwg)Output (bhp)Input (kW) 895 925 955 990 1020 1050 10806.0 5.0 4.0 3.0 2.0 1.0 0.01.5 1.6 1.8 2.0 2.1 2.3 2.53.7 3.9 4.2 4.4 4.7 4.9 5.23.2 3.4 3.6 3.8 4.0 4.2 4.41.0 1.2 1.3 1.5 1.7 1.9 2.14.7 4.9 5.2 5.5 5.8 6.1 6.44.0 4.2 4.4 4.7 5.0 5.2 5.50.5 0.6 0.8 1.0 1.2 1.4 1.65.7 6.0 6.3 6.7 7.0 7.4 7.74.9 5.1 5.4 5.7 6.0 6.3 6.60.1 0.3 0.4 0.7 0.9 1.0 1.26.3 6.7 7.0 7.4 7.8 8.2 8.55.4 5.7 6.0 6.3 6.7 7.0 7.3- - 0.1 0.3 0.5 -- - 7.8 8.2 8.6 -- - 6.6 7.0 7.3 -
York D3CE — HIGH SPEED DRIVE (CFM) diagram (page 11)
Fig. 21

NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.

Page 12 of the York D3CE user manual — STATIC RESISTANCES*
Page 12 · cliquer pour agrandir
Page 12

BLOWER MOTOR AND DRIVE DATA

York D3CE — BLOWER MOTOR AND DRIVE DATA diagram (page 12)
Fig. 22
BLOWER RANGE (RPM)MOTOR1ADJUSTABLE MOTOR PULLEY2FIXED BLOWER PULLEY kW/HPFRAME SIZEEFF. (%)PITCH DIA. (mm/in.)BORE (mm/in.)DESIGNATIONPITCH DIA. (mm / in.)BORE (mm/in.)DESIGNATIONPITCH LENGTH (mm/in.)DESIGNATION 180845-10403.0 / 4.0184T84109-135 4.3-5.329 / 11⁄81VP56188 / 7.425 / 1BK801773 / 69.8BX68 240765-9055.6 / 7.5213T87140-165 5.5-6.535 / 13⁄81VP68264 / 10.430 / 13⁄16BK1102103 / 82.8BX81 1801030-12403.0 / 4.0184T84124-150 4.9-5.929 / 11⁄81VP62175 / 6.925 / 1BK751773 / 69.8BX68 240895-10805.6 / 7.5213T87147-178 5.8-7.035 / 13⁄81VP75239 / 9.430 / 13⁄16BK1002103 / 82.8BX81

1All motors are totally enclosed, fan cooled (TEFC), 1450 RPM with solid bases and a 1.15 service factor. 2Do NOT close this pulley below the minimum number of turns open.

STATIC RESISTANCES*

DESCRIPTIONEXTERNAL STATIC [RESSURE DRP RESISTANCE, Pa/IWG M3/S / CFM MODEL 180MODEL 240 2.1 / 45002.8 / 60003.4 / 72002.8 / 60003.8 / 80004.4 / 9400 WET COIL24.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.1 ELECTRIC HEAT OPTIONS18 kW24.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.1 36 kW24.8 / 0.150.0 / 0.274.4 / 0.324.8 / 0.150.0 / 0.274.4 / 0.3 54 kW50.0 / 0.274.4 / 0.399.2 / 0.450.0 / 0.274.4 / 0.399.2 / 0.4 72 kW50.0 / 0.299.2 / 0.4149.0 / 0.650.0 / 0.299.2 / 0.4149.0 / 0.6 ECONOMIZER OPTION24.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.124.8 / 0.1 HORIZONTAL DUCT CONNECTIONS50.0 / 0.274.4 / 0.3124.0 / 0.550.0 / 0.274.4 / 0.3124.0 / 0.5

* Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections. Add the Horizontal Duct Connection values due to less airflow resistance.

Page 13 of the York D3CE user manual — N NEUTRAL TERMINAL
Page 13 · cliquer pour agrandir
Page 13

FIELD WIRING - Electric/Electric and Gas/Electric Units

York D3CE — FIELD WIRING - Electric/Electric and Gas/Electric Units diagram (page 13)
Fig. 23 · FIELD WIRING - Electric/Electric and Gas/Electric Un…

LINE VOLTAGE TERMINAL BLOCK 2TB IN UNIT CONTROL BOX

Refer to the ELECTRICAL DATA tables to size the power wiring, the fuses and the disconnect switch.

N NEUTRAL TERMINAL

24 VOLT TRANSFORMER

GRD. LUG

ELECTRICAL DATA - Cooling Only Units and Units With Gas Heat

OUTDOOR

SUPPLY AIR

TOTAL UNIT

COMPRESSOR

FAN MOTOR, (#1 & #2) FLA, EACH

BLOWER MOTOR, (FLA)

AMPACITY,

MAX. FUSE SIZE 1

MIN. WIRE SIZE 2 ,

UNIT SIZE

POWER SUPPLY

(AMPS)

(mm2/AWG) RLA LRA 3 kW 4 HP 5.6 kW 7.5 HP 3 kW 4 HP 5.6 kW 7.5 HP #1 #2 #1 #2 180 380/400/415-3+N-50 19.2 9.6 146 73 2.4 8.6 - 47.0 - 60 10 / 8 240 380/400/415-3+N-50 19.2 19.2 146 146 2.4 - 11.7 - 59.7 70 16 / 6

Page 14 of the York D3CE user manual — AIR FILTERS
Page 14 · cliquer pour agrandir
Page 14

ELECTRICAL DATA - Units With Supplemental Electric Heating

York D3CE — ELECTRICAL DATA - Units With Supplemental Electric Heating diagram (page 14)
Fig. 24 · ELECTRICAL DATA - Units With Supplemental Electric H…

10 / 8 16 / 6 25 / 4 35 / 2

10 / 8 16 / 6 25 / 4 35 / 2

16 / 6 16 / 6 25 / 4 35 / 2

16 / 6 16 / 6 25 / 4 50 / 2

PHYSICAL DATA

COMPONENT DESCRIPTION UNIT SIZE (MBH)

York D3CE — COMPONENT DESCRIPTION UNIT SIZE (MBH) diagram (page 14)
Fig. 25

D*CE UNITS 180 866 / 1910 240 957 / 2110 D*CG UNITS 180 975 / 2150 240 1066 / 2350 OPTIONS / ACCESSORIES Economizer 73 / 160 Motorized Damper 68 / 150

CENTRIFUGAL BLOWER DIA. x WD. (mm) 381 x 381 457 x 381 DIA. x WD. (in.) 15 x 15 18 x 15 FAN MOTOR kW / HP 3.7 / 5 5.6 / 7.5

SUPPLY AIR

ROWS DEEP 3 3 FINS PER 25mm (1 in.) 13.5 13.5 FACE AREA m2 / Ft.2 1.45 / 15.5 1.92 / 20.5

INDOOR

COIL

PROPELLER DIA. mm / in. 762 / 30 (ea.) 762 / 30 (ea.) FAN MOTOR kW / HP 0.7 / 1 (ea.) 0.7 / 1 (ea.)

OUTDOOR

FANS (Two Per Unit)

NOMINAL AIRFLOW m3 / s 2.83 (ea.) 3.78 (ea.) CFM 6000 (ea.) 8000 (ea.)

18 kW 11 / 25 36 kW 14 / 30 54 kW 16 / 35 72 kW 18 / 40

ROWS DEEP 2 2 FINS PER 25mm (1 in.) 13 20 FACE AREA m2 / Ft.2 3.35 / 36.0 4.02 / 43.3 COMPRESSOR

OUTDOOR

COIL

Roof Curb 180 79 / 175 240 84 / 185 Barometric Damper 20 / 45 Wood Skid*

TANDEM (10 TON NOMINAL CAPACITY) 1* 2 HERMETIC (5 TON NOMINAL CAPACITY) 1 -

(Qty. Per Unit)

QUANTITY PER UNIT 406 x 508 x 51 (mm) - 4 16 x 20 x 2 (in.)

QUANTITY PER UNIT 406 x 635 x 51 (mm) - 4 16 x 25 x 2 (in.)

*Allows handling of unit using 2300mm (90") long forks.

AIR FILTERS

QUANTITY PER UNIT 457 x 610 x 51 (mm) 5 - 18 x 24 x 2 (in.) TOTAL FACE AREA m2 / Ft.2 1.40 / 15.0 1.87 / 20.0

CHARGE REFRIGERANT 22 SYS. #1 ( kg. / lbs.) 7.94 / 17.5 8.16 / 18.0 SYS. #2 (kg. / lbs.) 3.86 / 8.5 8.16 / 18.0

*This compressor will be energized first.

180 240

Page 15 of the York D3CE user manual — UTILITIES ENTRY DATA
Page 15 · cliquer pour agrandir
Page 15

UNIT DIMENSIONS - D*CE180 & 240 UNITS

York D3CE — UNIT DIMENSIONS - D*CE180 & 240 UNITS diagram (page 15)
Fig. 26

1235 (48-5/8") (180) 1337 (52-5/8") (240)

3181 (125-1/4") (180) 3461 (136-1/4") (240)

616 (24-1/4") (180) 895 (35-1/4") (240)

York D3CE — UNIT DIMENSIONS - D*CE180 & 240 UNITS diagram (page 15)
Fig. 27

RETURN AIR

All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request.

SUPPLY AIR

CLEARANCES (mm / in.)

Front 914 / 36

Back 610 / 24 (Less Economizer) 1245 / 49 (With Economizer)

Left Side (Filter Access) 610 / 24 (Less Economizer) 1372 / 54 (With Economizer) Right Side (Outdoor Coil) 914 / 36 Below Unit 20 / 0

UTILITIES ENTRY DATA

OPENING DIAMETER*

HOLE

USED FOR

1829 / 72 With 914 / 36 Maximum Horizontal Overhang (For Outdoor Air Discharge)

(mm / in.)

A 28.6 / 11⁄8 KO Control Wiring

Front 19.1 / 3⁄4 NPS (Fem.) Bottom

B 92.1 / 35⁄8 KO Power Wiring

Front 76.2 / 3 NPS (Fem.) Bottom

*Units must be installed oudoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.

*KO denotes Knockout facility.

OUTDOOR AIR (Discharge) · OUTDOOR AIR (Economizer) · Above Unit*

Page 16 of the York D3CE user manual — OPENING DIAMETER*
Page 16 · cliquer pour agrandir
Page 16

UNIT DIMENSIONS - D*CG180 & 240 UNITS

York D3CE — UNIT DIMENSIONS - D*CG180 & 240 UNITS diagram (page 16)
Fig. 28

1235 (48-5/8") (180) 1337 (52-5/8") (240)

3181 (125-1/4") (180) 3561 (136-1/4") (240)

616 (24-1/4") (180) 895 (35-1/4") (240)

RETURN AIR

SUPPLY AIR

CLEARANCES (mm / in. )

Front1 914 / 36

Back 610 / 24 (Less Economizer) 1245 / 49 (With Economizer)

All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request.

Left Side (Filter Access) 610 / 24 (Less Economizer) 1372 / 54 (With Economizer) Right Side (Outdoor Coil) 914 / 36 Below Unit2 0 / 0

UTILITIES ENTRY DATA

Above Unit3 1829 / 72 with 914 / 36 maximum Horizontal Overhang (For Outdoor Air Discharge)

OPENING DIAMETER*

HOLE

USED FOR

  • 1 Locate unit so that the vent air outlet hoods are at least:
  • 0.9 meter (3 ft) above any forced air inlet located within 3.0m (10 ft) horizontal (excluding those integral to the unit).
  • 1.2 meters (4 ft) below, 1.2m (4 ft.) horizontal from, or 0.31m(1 ft) above any door or gravity air inlet into the building.
  • 1.2 meters (4 ft) from electric meters, gas meters, regulators and relief equipment. 2 Units may be installed on combustible surfaces capable of continuous exposure to temperatures of 92 ° C (197 ° F), and intermittent exposure to temperatures of 124 ° C (255 ° F). 3 Units must be installed outdoors. Overhanging structures or shrubs should not obstruct the outdoor air discharge outlet. NOTE: A 25mm (1 in.) clearance must be provided between any combustible material and the supply air ductwork for a distance of 0.9m (3 ft) from the unit. The products of combustion must not be allowed to accumulate within a confined space and recirculate.

(in. / mm)

A 1-1/8 / 29 KO Control Wiring Front 3/4 NPS / 19 (Fem.) Bottom

B 3-5/8 / 92 KO Power Wiring Front 3 NPS / 76 (Fem.) Bottom C 2-3/8 / 60 KO Gas Piping (Front) D 1-11/16 / 43 Hole Gas Piping (Bottom)**

*KO denotes Knockout facility. **Opening in the bottom of the unit can be located by the slice in the insulation.

OUTDOOR AIR (Discharge) · OUTDOOR AIR (Economizer)

Page 17 of the York D3CE user manual — CENTER OF GRAVITY
Page 17 · cliquer pour agrandir
Page 17

UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d.)

York D3CE — UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d.) diagram (page 17)
Fig. 29 · UNIT DIMENSIONS - D*CE / D*CG180 & 240 UNITS (Cont’d…

DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For downflow duct applications: 1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. 2. Remove and discard the bottom duct covers. 3. Replace the side supply and return air compartment panels. For sideflow duct applications; 1. Replace the side panels on the supply and return air compartments with the accessory flange kit panels. 2. Connect ductwork to the duct flanges on the rear of the unit.

727 (28-5/8") (180) 1006 (39-5/8") (240)

DETAIL “X” ACCESSORY SIDE SUPPLY AND RETURN AIR DUCT OPENINGS

York D3CE — DETAIL “X” ACCESSORY SIDE SUPPLY AND RETURN AIR DUCT OPENINGS diagram (page 17)
Fig. 30

397 155⁄8“

610 (24") (180) 889 (35") (240)

DETAIL “Y” UNIT WITH ECONOMIZER AND FIXED OUTDOOR AIR HOODS

York D3CE — DETAIL “Y” UNIT WITH ECONOMIZER AND FIXED OUTDOOR AIR HOODS diagram (page 17)
Fig. 31

OUTDOOR COIL END OF UNIT

3181 (125-1/4") (180) 3461 (136-1/4") (240)

CENTER OF GRAVITY

2337 (92") · 1524 (60") · 1143 (45")

Page 18 of the York D3CE user manual — TYPICAL APPLICATIONS
Page 18 · cliquer pour agrandir
Page 18

ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITS

York D3CE — ROOF CURB DIMENSIONS - D*CE / D*CG180 & 240 UNITS diagram (page 18)
Fig. 32

362 (14-1/4") (180) 641 (25-1/4") (240) 2927 (115-1/4") (180) 3207 (126-1/4") (240)

* Supply and Return Air (including duct suppport rails) as shown, are typical for downflow duct applications.

For location of sideflow duct applications (on back of unit), refer to Unit Dimension details.

ROOF CURB BENEFITS

UNIT AND CURB APPLICATION

York D3CE — ROOF CURB BENEFITS diagram (page 18)
Fig. 33
York D3CE — ROOF CURB BENEFITS diagram (page 18)
Fig. 34

2927 (115-1/4") (180) 3207 (126-1/4") (240)

TYPICAL APPLICATIONS

York D3CE — TYPICAL APPLICATIONS diagram (page 18)
Fig. 35
Page 19 of the York D3CE user manual — ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN)
Page 19 · cliquer pour agrandir
Page 19

TYPICAL APPLICATIONS - Cont’d.

ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN)

York D3CE — ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN) diagram (page 19)
Fig. 36
Page 20 of the York D3CE user manual — ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN)
Page 20 · cliquer pour agrandir
Page 20
York D3CE — ROOF-TOP INSTALLATION (GAS/ELECTRIC UNIT SHOWN) diagram (page 20)
Fig. 37

P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A Copyright by York International Corporation 1994. All Rights Reserved.

530.26TG3YI SupersedesNothing

Poser une question sur : York D3CE

Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.

Add your email to get notified when it’s answered — no spam, ever.

0 questions
Aucune question pour l'instant sur le York D3CE

Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.

Document d'origine

York D3CE manuel PDF

20 pages·829 KB·Climatiseur·PDF
Cliquez sur une page ci-dessus pour l'ouvrir ici
Page 1 / …
100%
Chargement des pages…