Sunline 2000 units are highly efficient, convertible rooftops. All models have dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. These units are designed and manufactured under ISO 9002 Quality System Certification. Cooling only, cooling with gas heat and cooling with supplemental electric heat units are available with a wide variety of field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails. The base rails have holes in the four corners for overhead rigging.
With horizontal ductwork, it should be mounted on the return air duct.
All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.
All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls.
Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. Powder paint cabinets provide an exceptionally durable finish with the 750 hour salt spray process per ASTM-B117 test standard.
All gas heat models are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger with aluminized steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards.
All models are available with three different outdoor air damper accessosries:
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit.
All models (including those with an economizer ) are suitable for either downflow or sideflow duct connections. For downflow duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For sideflow duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory.
All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive current and temperature by fuses and two thermal limit switches.
A fixed outdoor air intake assembly is shipped in the return air compartment of all units. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel.
The power supply wiring can be routed into the control box through a threaded pipe connection in the base pan of the unit or through a knockout in the wiring panel on the front of the unit.
® · DCG Shown



ALUMINIZED STEEL
THROWAWAY
D*CG UNITS
(OPTION / ACCESSORY)
FEMALE
MODEL DCG
RATINGS
CAPACITY RATINGS - Cooling / Electric Heating

1T1 = Moderate Climates, T2 = Hot Climates, T3 = Cool Climates.
2COP = Coefficient of Performance - total output kW divided by the total input kW.
3EER = Energy Efficiency Ratio - total output Mbh divided by the total input kW.
4Heaters available as factory-installed options or field-installed accessories - all with single point power supply.

*Based on net input and 2nd. -H family, G20 (methane) net fuel value (9.97 kWh/m3).
® · (Gas Heating)

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.

1These capacities are gross ratings. For net capacity, deduct the heat of the supply air blower motor. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2These ratings include the condenser fan motors (Total 2.3 kW) and the compressor motors but not the supply air blower motor.





NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.





NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.





NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.





NOTES: 1. Blower performance values include fixed outdoor air, a dry indoor coil, the standard unit filters and no electric heat. 2. Refer to Page 12 for the resistance values for all other unit options or applications. ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower. *Do NOT close pulley below minimum turns open.


1All motors are totally enclosed, fan cooled (TEFC), 1450 RPM with solid bases and a 1.15 service factor. 2Do NOT close this pulley below the minimum number of turns open.
* Deduct these resistance values from the available unit ESP values listed in the respective blower performance table except for Horizontal Duct Connections. Add the Horizontal Duct Connection values due to less airflow resistance.


LINE VOLTAGE TERMINAL BLOCK 2TB IN UNIT CONTROL BOX
Refer to the ELECTRICAL DATA tables to size the power wiring, the fuses and the disconnect switch.
24 VOLT TRANSFORMER
GRD. LUG
ELECTRICAL DATA - Cooling Only Units and Units With Gas Heat
OUTDOOR
SUPPLY AIR
TOTAL UNIT
COMPRESSOR
FAN MOTOR, (#1 & #2) FLA, EACH
BLOWER MOTOR, (FLA)
AMPACITY,
MAX. FUSE SIZE 1
MIN. WIRE SIZE 2 ,
UNIT SIZE
POWER SUPPLY
(AMPS)
(mm2/AWG) RLA LRA 3 kW 4 HP 5.6 kW 7.5 HP 3 kW 4 HP 5.6 kW 7.5 HP #1 #2 #1 #2 180 380/400/415-3+N-50 19.2 9.6 146 73 2.4 8.6 - 47.0 - 60 10 / 8 240 380/400/415-3+N-50 19.2 19.2 146 146 2.4 - 11.7 - 59.7 70 16 / 6


10 / 8 16 / 6 25 / 4 35 / 2
10 / 8 16 / 6 25 / 4 35 / 2
16 / 6 16 / 6 25 / 4 35 / 2
16 / 6 16 / 6 25 / 4 50 / 2

D*CE UNITS 180 866 / 1910 240 957 / 2110 D*CG UNITS 180 975 / 2150 240 1066 / 2350 OPTIONS / ACCESSORIES Economizer 73 / 160 Motorized Damper 68 / 150
CENTRIFUGAL BLOWER DIA. x WD. (mm) 381 x 381 457 x 381 DIA. x WD. (in.) 15 x 15 18 x 15 FAN MOTOR kW / HP 3.7 / 5 5.6 / 7.5
ROWS DEEP 3 3 FINS PER 25mm (1 in.) 13.5 13.5 FACE AREA m2 / Ft.2 1.45 / 15.5 1.92 / 20.5
COIL
PROPELLER DIA. mm / in. 762 / 30 (ea.) 762 / 30 (ea.) FAN MOTOR kW / HP 0.7 / 1 (ea.) 0.7 / 1 (ea.)
FANS (Two Per Unit)
NOMINAL AIRFLOW m3 / s 2.83 (ea.) 3.78 (ea.) CFM 6000 (ea.) 8000 (ea.)
18 kW 11 / 25 36 kW 14 / 30 54 kW 16 / 35 72 kW 18 / 40
ROWS DEEP 2 2 FINS PER 25mm (1 in.) 13 20 FACE AREA m2 / Ft.2 3.35 / 36.0 4.02 / 43.3 COMPRESSOR
COIL
Roof Curb 180 79 / 175 240 84 / 185 Barometric Damper 20 / 45 Wood Skid*
TANDEM (10 TON NOMINAL CAPACITY) 1* 2 HERMETIC (5 TON NOMINAL CAPACITY) 1 -
(Qty. Per Unit)
QUANTITY PER UNIT 406 x 508 x 51 (mm) - 4 16 x 20 x 2 (in.)
QUANTITY PER UNIT 406 x 635 x 51 (mm) - 4 16 x 25 x 2 (in.)
*Allows handling of unit using 2300mm (90") long forks.
QUANTITY PER UNIT 457 x 610 x 51 (mm) 5 - 18 x 24 x 2 (in.) TOTAL FACE AREA m2 / Ft.2 1.40 / 15.0 1.87 / 20.0
CHARGE REFRIGERANT 22 SYS. #1 ( kg. / lbs.) 7.94 / 17.5 8.16 / 18.0 SYS. #2 (kg. / lbs.) 3.86 / 8.5 8.16 / 18.0
*This compressor will be energized first.
180 240


1235 (48-5/8") (180) 1337 (52-5/8") (240)
3181 (125-1/4") (180) 3461 (136-1/4") (240)
616 (24-1/4") (180) 895 (35-1/4") (240)

All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request.
CLEARANCES (mm / in.)
Front 914 / 36
Back 610 / 24 (Less Economizer) 1245 / 49 (With Economizer)
Left Side (Filter Access) 610 / 24 (Less Economizer) 1372 / 54 (With Economizer) Right Side (Outdoor Coil) 914 / 36 Below Unit 20 / 0
OPENING DIAMETER*
HOLE
USED FOR
1829 / 72 With 914 / 36 Maximum Horizontal Overhang (For Outdoor Air Discharge)
(mm / in.)
A 28.6 / 11⁄8 KO Control Wiring
Front 19.1 / 3⁄4 NPS (Fem.) Bottom
B 92.1 / 35⁄8 KO Power Wiring
Front 76.2 / 3 NPS (Fem.) Bottom
*Units must be installed oudoors. Overhanging structures or shrubs should not obstruct outdoor air discharge outlet.
*KO denotes Knockout facility.
OUTDOOR AIR (Discharge) · OUTDOOR AIR (Economizer) · Above Unit*


1235 (48-5/8") (180) 1337 (52-5/8") (240)
3181 (125-1/4") (180) 3561 (136-1/4") (240)
616 (24-1/4") (180) 895 (35-1/4") (240)
SUPPLY AIR
CLEARANCES (mm / in. )
Front1 914 / 36
Back 610 / 24 (Less Economizer) 1245 / 49 (With Economizer)
All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimensions will be provided upon request.
Left Side (Filter Access) 610 / 24 (Less Economizer) 1372 / 54 (With Economizer) Right Side (Outdoor Coil) 914 / 36 Below Unit2 0 / 0
Above Unit3 1829 / 72 with 914 / 36 maximum Horizontal Overhang (For Outdoor Air Discharge)
HOLE
USED FOR
(in. / mm)
A 1-1/8 / 29 KO Control Wiring Front 3/4 NPS / 19 (Fem.) Bottom
B 3-5/8 / 92 KO Power Wiring Front 3 NPS / 76 (Fem.) Bottom C 2-3/8 / 60 KO Gas Piping (Front) D 1-11/16 / 43 Hole Gas Piping (Bottom)**
*KO denotes Knockout facility. **Opening in the bottom of the unit can be located by the slice in the insulation.
OUTDOOR AIR (Discharge) · OUTDOOR AIR (Economizer)


DUCT COVERS - Units are shipped with the bottom duct openings covered. An accessory flange kit is available for connecting side ducts. For downflow duct applications: 1. Remove the side panels from the supply and return air compartments to gain access to the bottom supply and return air duct covers. 2. Remove and discard the bottom duct covers. 3. Replace the side supply and return air compartment panels. For sideflow duct applications; 1. Replace the side panels on the supply and return air compartments with the accessory flange kit panels. 2. Connect ductwork to the duct flanges on the rear of the unit.
727 (28-5/8") (180) 1006 (39-5/8") (240)

397 155⁄8“
610 (24") (180) 889 (35") (240)

3181 (125-1/4") (180) 3461 (136-1/4") (240)
2337 (92") · 1524 (60") · 1143 (45")


362 (14-1/4") (180) 641 (25-1/4") (240) 2927 (115-1/4") (180) 3207 (126-1/4") (240)
* Supply and Return Air (including duct suppport rails) as shown, are typical for downflow duct applications.
For location of sideflow duct applications (on back of unit), refer to Unit Dimension details.
UNIT AND CURB APPLICATION


2927 (115-1/4") (180) 3207 (126-1/4") (240)


TYPICAL APPLICATIONS - Cont’d.



P.O. Box 1592, York, Pennsylvania USA 17405-1592 Subject to change without notice. Printed in U.S.A Copyright by York International Corporation 1994. All Rights Reserved.