GENERAL YORK Model DEE units are single package air conditioners designed for outdoor installation on a rooftop or a slab. Electric heaters are available as field-installed accessories. The units are completely assembled on rigid, permanently attached base rails.
035-12046-003-A-0204 2 Unitary Products Group General ................................................................................ 1 Inspection ............................................................................ 1 Reference ..............
LIMIT ATIONS These units must be installed in accordance with the current edition of the following national and local safety codes: In USA: 1. National Electrical Code ANSI/NFP A No. 70. 2. Local electric utility requirements. In Canada: 1. Canadian Electrical Code C22.
kept clean or replaced with same size and type. Dirty filters will reduce the capacity of the unit and will result in frosted coils or safety shutdown. Minimum filter area and required sizes are shown in T able 2. CONDENSA TE DRAIN Plumbing must conform to local codes.
All direct-drive units with 460 and 575 voltage are shipped with the wire labeled #1 16 connected to the “HIGH” speed tap on the blower motor . If the medium speed is required, connect wire #1 16 to the “MED” speed tap and the blue motor lead to the “HIGH” speed tap.
10. T o check that the damper blades move smoothly without binding, carefully turn the minimum position adjusting screw fully clockwise and then energize and de-energize terminals “R” to “G”. With terminals “R” to “G” energized, turn the minimum position screw counterclockwise until the desired minimum position has been attained.
035-12046-003-A-0204 Unitary Products Group 7 FIG. 5 - DIMENSIONS & CLEARANCES - 3 - 5 TONS DUCT COVERS - Units are shipped with all air duct openings covered. For side duct applications; 1.Remove and discard the supply and return air duct covers.
Install the bracket on the left hand side of the unit as shown in Figure 5. Several existing screws at the top of the unit and one screw approximately midway down from the top will be used for mounting the bracket. Screws should be loosened only - NOT REMOVED.
035-12046-003-A-0204 Unitary Products Group 9 T ABLE 4 - SUPPL Y AIR PERFORMANCE - 3 & 4 TON w/Belt-Drive Blower UNIT SIZE (MBH) AIR FLOW CFM Available External Static Pressure - IWG* 0.
035-12046-003-A-0204 10 Unitary Products Group T ABLE 5 - SUPPL Y AIR PERFORMANCE - 5 TON w/Belt-Drive Blower UNIT SIZE (MBH) AIR FLOW CFM Available External Static Pressure - IWG* 0.
035-12046-003-A-0204 Unitary Products Group 11 EXTERNAL ST A TIC PRESSURE DROP DESCRIPTION RESIST ANCE, IWG CFM 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 Economizer 1, 3 0.07 0.08 0.09 0.1 1 0.13 0.15 0.17 0.20 0.23 0.26 0.30 Electric Heaters 1 5 - 15 KW 0.
The heaters are wired for a single point power supply . Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located in the upper portion of the unit control box. Fuses are supplied, where required, by the factory .
HEA T ANTICIP ATOR SETPOINTS It is important that the anticipator setpoint be correct. T oo high of a setting will result in longer heat cycles and a greater temperature swing in the conditioned space.
035-12046-003-A-0204 14 Unitary Products Group SECURE OWNER'S APPROV AL : When the system is functioning properly , secure the owner's approval. Show him the location of all disconnect switches and the thermostat. T each him how to start and stop the unit and how to adjust tem - perature settings within the limitations of the system.
035-12046-003-A-0204 Unitary Products Group 15.
Unitary Products Group 5005 York Drive, Norman, Oklahoma 73069 Subject to change without notice. Printed in U.S.A 035-12046-003-A-0204 Copyright © 2004 by Unitary Products Group.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York D1EE 060 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York D1EE 060 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York D1EE 060, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York D1EE 060 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York D1EE 060, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York D1EE 060.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York D1EE 060. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York D1EE 060 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.