TECHNICAL GUIDE AFFINITY R-410A SPLIT -SYSTEM AIR CONDITIONERS 18 SEER MODELS: CZH024 THRU 060 (2 THRU 5 NOMINAL T ONS) Due to continuou s produc t improvement, specific a tions are subjec t to ch a nge without notice. Visit us on the web at www .york.
350154-YTG-C-0808 2 Johnson Controls Unitary Products All dimensions are in inches. They a re subject to change without notice. Certified dimensions will be provided upon requ est.
350154-YTG -C-0808 Johnson Controls Unitary Products 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for the condenser , the sma llest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system using the above table.
350154-YTG-C-0808 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER 1 PH 18 SEER AC WITH MV CZH0241 1 MV12B 17 FC/MC/PC35B 1 620 18.2 13.
350154-YTG -C-0808 Johnson Controls Unitary Products 5 COOLING CAP ACITY - CZH0241 1 With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC32A 14 1 470 17.
350154-YTG-C-0808 6 Johnson Controls Unitary Products Y*(8,L)C*B12 UC36B 17 1 525 16.6 1 1.9 16.00 13.50 2 765 22.2 15.5 13.25 Y*9C*B12 UC36B 17 1 590 17.0 12.8 16.00 13.75 2 815 22.4 15.7 13.00 G*9V*A12 FC/MC/PC30A 14 1 625 17.8 13.4 16.50 14.00 2 800 23.
350154-YTG -C-0808 Johnson Controls Unitary Products 7 COOLING CAP ACITY - CZH0361 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC37A 14 1 750 25.
350154-YTG-C-0808 8 Johnson Controls Unitary Products Y*9C*C16 FC/MC/PC35C 21 1 790 25.0 17.5 17.25 14.25 2 1215 35.4 24.7 13.00 Y*9C*C20 FC/MC/PC35C 21 1 760 24.6 16.8 17.00 14.25 2 1330 35.6 25.3 12.75 Y*(8,L)C*A12 FC/MC/PC36A 14 1 815 24.8 17.3 16.
350154-YTG -C-0808 Johnson Controls Unitary Products 9 Y*9C*C16 HC42 21 1 815 25.0 17.6 17.25 14.25 2 1240 35.6 24.9 13.00 Y*9C*C20 HC42 21 1 780 25.0 17.6 17.50 14.50 2 1200 35.8 25.1 13.25 Y*(8,L)C*B12 HD48 17 1 750 24.8 17.0 17.25 14.50 2 1210 35.8 25.
350154-YTG-C-0808 10 Johnson Controls Unitary Products G*9V*B12 FC/MC/PC35B 17 1 810 25.0 17.4 16.75 14.00 2 1 190 35.2 24.5 12.75 G*9V*C16 FC/MC/PC35C 21 1 790 25.0 17.5 17.25 14.25 2 1215 35.4 24.7 13.00 G*9V*C20 FC/MC/PC35C 21 1 760 24.6 16.8 17.00 14.
350154-YTG -C-0808 Johnson Controls Unitary Products 11 COOLING CAP ACITY - CZH0481 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*C16 FC/MC/PC48C 21 1 880 33.
350154-YTG-C-0808 12 Johnson Controls Unitary Products Y*(8,L)C*C20 HD48 21 1 1080 32.8 24.0 16.00 13.25 2 1640 45.5 33.7 1 1.75 Y*9C*C16 HD48 21 1 1050 33.0 24.0 16.25 13.25 2 1590 45.0 33.5 1 1.75 Y*9C*C20 HD48 21 1 1055 33.0 24.0 16.25 13.50 2 1655 45.
350154-YTG -C-0808 Johnson Controls Unitary Products 13 G*9V*C20 HD48 21 1 1055 33.0 24.0 16.25 13.50 2 1655 45.0 33.5 1 1.75 G*9V*D20 HD48 24 1 1060 32.8 24.0 16.25 13.25 2 1645 45.5 33.7 1 1.75 G*9V*C16 HD60 21 1 1050 33.4 24.6 16.25 13.50 2 1590 45.
350154-YTG-C-0808 14 Johnson Controls Unitary Products ACCESSORIES* Hard St a rt Kit (024-31994-000, 024-31995-000) - Provides increased starting torque for areas with low voltage.
350154-YTG -C-0808 Johnson Controls Unitary Products 15 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
350154-YTG-C-0808 16 Johnson Controls Unitary Products Multipliers for determining th e performance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (betwe en 7.
350154-YTG -C-0808 Johnson Controls Unitary Products 17 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
350154-YTG-C-0808 18 Johnson Controls Unitary Products P(C,V)9*C20 FC/MC/PC48D 1.01 1.01 1.02 P(C,V)9*C20 UC48D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC/PC48D 1.01 1.01 1.01 P(C,V)9*D20 UC48D 1.01 1.01 1.01 PV8*C20 FC/MC62D 1.01 1.01 1.01 P(C,V)9*C20 FC/MC62D 1.
350154-YTG -C-0808 Johnson Controls Unitary Products 19 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
350154-YTG-C-0808 20 Johnson Controls Unitary Products P(C,V)9*C20 FC/MC/PC48D 0.99 0.99 1.03 P(C,V)9*C20 UC48D 0.99 0.99 1.03 P(C,V)9*D20 FC/MC/PC48D 0.99 0.99 1.02 P(C,V)9*D20 UC48D 0.99 0.99 1.02 PV8*C20 FC/MC62D 1.00 1.00 1.04 P(C,V)9*C20 FC/MC62D 1.
350154-YTG -C-0808 Johnson Controls Unitary Products 21 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
350154-YTG-C-0808 22 Johnson Controls Unitary Products Va r i a b l e S p e e d Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.97 0.97 0.98 PV8*C16 FC/MC/PC48D 0.97 0.97 0.98 PV8*C16 UC48D 0.97 0.97 0.98 PV8*C20 FC/MC/PC48C 1.00 1.00 0.99 PV8*C20 FC/MC/PC48D 1.
350154-YTG -C-0808 Johnson Controls Unitary Products 23 Multipliers for determining the pe rformance with other indoor sect ions NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween.
350154-YTG-C-0808 24 Johnson Controls Unitary Products Va r i a b l e S p e e d Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.97 0.97 1.01 PV8*C16 FC/MC/PC48D 0.97 0.97 1.01 PV8*C16 UC48D 0.97 0.97 1.01 PV8*C20 FC/MC/PC48C 0.98 0.98 1.02 PV8*C20 FC/MC/PC48D 0.
350154-YTG -C-0808 Johnson Controls Unitary Products 25 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet wee.
Subject to change without notice. Printe d in U.S.A. 350154-YTG-C-0808 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 350154-YTG-B-0408 Johnson Controls Unit ary Produ cts 5005 Y ork Drive Norman, OK 73069 Multipliers for determining th e performance with other indoor sections.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York CZH024 THRU 060 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York CZH024 THRU 060 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York CZH024 THRU 060, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York CZH024 THRU 060 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York CZH024 THRU 060, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York CZH024 THRU 060.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York CZH024 THRU 060. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York CZH024 THRU 060 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.