254597-YTG-B-0507 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SINGLE P ACKAGE GA S/ELECTRIC UNITS AND SINGLE P ACKAGE AIR CONDITIONERS DH 036, 048 & 060 3, 4 & 5 NOMINAL TONS 12.
254597-YTG-B-0507 2 Unitary Products Group T ABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . .
254597-YTG-B-0507 Unitary Products Group 3 PRODUCT NOMENCLA TURE D H 048 N04 A 2 A AA 1 0 1 2 4 A D = A/C, Single Pkg., R-22 Product Category Airflow N = Belt Drive P = Belt Drive/Single Input Economi.
254597-YTG-B-0507 4 Unitary Products Group FEA TURES All models are available with a wide variety of factory- mounted options such as stainless steel heat exchangers, electric heaters, phase monito r , convenience outlet, dirty filter switch, disconnect switch, smo ke detectors, and coil guard to make them suitable for almost every application.
254597-YTG-B-0507 Unitary Products Group 5 • BAS Controls - Y ork’s Sunlin e™ series unit s offer factory mounted BAS cont rols such as Simplicity ® INTELLI-Com- fort™, Novar , Honeywell, Johnson, and CPC.
254597-YTG-B-0507 6 Unitary Products Group installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor , a Return Air Humidity sensor , an Inside IAQ sensor , and an Outside Air IAQ sensor . Construction mode oper ation, 365-day real ti me clock with 7 day programming plus holiday scheduling is built-in.
254597-YTG-B-0507 Unitary Products Group 7 FIELD-INST ALLE D ACCESSORIES • SINGLE INPUT ELECTR ONIC ENTHALPY ECONO- MIZERS - Includes a slide-in / plug-in damper a ssembly with fully modulating spring-return motor actuator capa- ble of introducing up to 100% outdoor air with nominal 1% leakage type dampers.
254597-YTG-B-0507 8 Unitary Products Group T AB LE 1: SOUND POWER RA TING 1 UNIT SIZE CFM ESP BLOWER SOUND POWER (db 10 -12 Wat ts ) Octave Band Centerline Frequency (Hz) SWL dB(A) dB(A) @ 10Ft. 2 IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000 036 1,200 0.
254597-YTG-B-0507 Unitary Products Group 9 T AB LE 5: DH036 COOLING CAP ACITIES (3 TON) CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 55.2 3.18 35.2 30.7 26.2 21.8 17.3 - - 51.5 3.44 34.1 29.7 25.2 20.7 16.2 - - 67 49.1 3.13 41.7 37.2 32.8 28.
254597-YTG-B-0507 10 Unitary Products Group T AB LE 6: DH048 COOLING CAP ACITIES (4 TON) CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 59 3.3 46 40 34 28 23 - - 55 3.5 43 37 32 26 20 - - 67 53 3.2 53 49 43 38 32 26 21 49 3.4 49 47 41 35 30 24 62 47 3.
254597-YTG-B-0507 Unitary Products Group 11 T AB LE 7: DH060 COOLING CAPACITIES (5 T ON) CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68 72 82 4.3 56 50 43 37 30 - - 76 4.6 54 48 41 34 28 - - 67 70 4.2 67 61 54 48 41 34 28 65 4.5 65 58 51 45 38 31 25 62 67 4.
254597-YTG-B-0507 12 Unitary Products Group T AB LE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TO N BELT DRIVE) - SIDE DUCT APPLICATION RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2.
254597-YTG-B-0507 Unitary Products Group 13 T AB LE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2.
254597-YTG-B-0507 14 Unitary Products Group T AB LE 12: BEL T DRIVE BLOWER MOTOR AND DRIVE DA T A MODEL SIZE BLOWER RANGE (RPM) MOTOR 1 ADJUST A BLE MOTOR PULLEY FIXED BLOWER PULLEY BEL T (NOTCHED) HP FRAME DESIG- NA TION OUTSIDE DIA. (IN.) PITCH DIA.
254597-YTG-B-0507 Unitary Products Group 15 T AB LE 15: ELECTRICAL DA T A - DH036 , 048 & 060 DIRECT DRIVE W/O POWERED CONVENIENCE OUTLET MODEL TONNAGE VOL T AGE COMPRES SORS OD F A N MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO.
254597-YTG-B-0507 16 Unitary Products Group T AB LE 16: ELECTRICAL DA T A - DH036-060 BEL T DRIVE W/O POWERED CONV EN IENCE OUTLET MODEL TONNAGE VOL T AGE COMPRES SORS OD F A N MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO. HEA TER KW HEA TER AMPS MIN.
254597-YTG-B-0507 Unitary Products Group 17 T AB LE 17: ELECTRICAL DA T A - DH036, 048 & 06 0 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET MODEL TONNAGE VOL T AGE COMPRES SORS OD F A N MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO.
254597-YTG-B-0507 18 Unitary Products Group T AB LE 18: ELECTRICAL DA T A - DH036-060 BE L T DRIVE W/POWERED CONV ENIENCE OUTLET MODEL TONNAGE VOL T AGE COMPRES SORS OD F A N MOTOR FLA ID BLOWER MOTOR FLA CONV OUTLET FLA ELECTRIC HEA TER MODEL NO. HEA TER KW HEA TER AMPS MIN.
254597-YTG-B-0507 Unitary Products Group 19 T ABLE 19: PHYSICAL DATA MODELS DH 036 048 060 EV APORA TOR BLOWER Centrifug al Blower (Dia . x Wd. in.) 12 X 10 12 X 10 12 X 10 Fan Motor HP (Dire c t Drive) 3/4 1 1 Fan Motor HP (Belt Driv e) 1 1/2 1 1/2 1 1/2 EV APORA TOR COIL Rows Deep 4 4 4 Fins Per Inc h 13 13 13 Face Area (Sq.
254597-YTG-B-0507 20 Unitary Products Group FIGURE 2 - TYPICA L FIELD POWER & CONTROL WIRING RC RH Y1 Y2 W1 W2 G LED 1 LED 2 COM A1 A2 T T B R Y1 Y2 G C X OCC W2 W1 THERMOSTAT 1 TERMINALS UNIT TER.
254597-YTG-B-0507 Unitary Products Group 21 FIGURE 3 - UNIT DIMENSIONS (3 - 5 T O N COOLING ONL Y/ELECTRIC HEA T) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (3 - 5 T ON COOLING/GAS HEA T) FRONT VIEW.
254597-YTG-B-0507 22 Unitary Products Group FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD FIGURE 6 - UNIT WITH FIXED OUT D OOR AIR/MOTORIZE D DAMPER RAINHOOD DETAIL “A” DETAIL “B”.
254597-YTG-B-0507 Unitary Products Group 23 FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCA TION T ABLE 22: UTILITIES ENTR Y HOLE OPENING SIZE (DIA.) USED FOR A 7/8” KO 1 1. Opening in the bottom to the unit can be located by the side in the insulation.
254597-YTG-B-0507 24 Unitary Products Group FIGURE 9 - TYPICAL APPLICA TIONS.
254597-YTG-B-0507 Unitary Products Group 25 FIGURE 10 - FOUR AND SIX POINT LOADING 44 7 / 8 82 1 / 4 Y X A B C D CONDENSER COIL END OF UNIT FRONT OF UNIT APPROXIMATE CENTER OF GRAVITY BACK OF UNIT 44 .
254597-YTG-B-0507 26 Unitary Products Group T ABLE 26: OPERA TING WEIGHTS (LBS.) MOD E L S IZ E 3 TON 4 TO N 5 TO N BASIC UNIT DH (Cool ing Only) 565 61 0 64 5 DH (Gas/Electric) N04 605 - - N06 - 660 .
254597-YTG-B-0507 Unitary Products Group 27 GUIDE SPECIFICA TIONS GENERAL Units shall be manufactured by Y ork International Unitary Products Group in an ISO 9001 certified facility . Y ork's Sunline Ultra ® units are convertibl e single package units.
254597-YTG-B-0507 28 Unitary Products Group Coils: a. Evaporator and conde nser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. S pecial Phenolic coating shall be available as a factory option.
254597-YTG-B-0507 Unitary Products Group 29 ST AND ARD LIMITED W ARRANTIES • Compressor 5 Y ears • Heat Exchanger 10 Y ears • Electric Heat Element 5 Y ears • Other Part s 1 Y ear OPTIONAL OUT.
254597-YTG-B-0507 30 Unitary Products Group • TECHNICOA T PHENOLIC COA TED CONDENSER AND EV APORA TOR COIL • ELECTRONIC SINGLE ENTHALPY ECONOMIZER • DIRTY FIL TER SWITCH • PHASE MONITOR • CO.
254597-YTG-B-0507 Unitary Products Group 31.
Subject to change without notice. Printed in U.S.A. 254597-YTG-B-0507 Copyright © 2007 by Unitary Products Group. All rights reserved. Supersedes: 254597-YTG-A-0306 Unitary 5005 Norman Product s Y or.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York CSA 48 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York CSA 48 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York CSA 48, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York CSA 48 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York CSA 48, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York CSA 48.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York CSA 48. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York CSA 48 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.