036-2 1528-003- A- 0703 FOR DISTRI BUTI ON USE ONL Y - NOT TO BE USED A T POINT OF RET AIL SALE ® CHAMPION ® ULTRA SINGLE PACKAGE HEAT PUM PS BHP024 THRU 048 2 THRU 4 NOMINAL TONS 13 S EER FACTORY MOUNTE D TX V DESCRIPTION These packaged heat pum ps are designed for outdoor installation.
036-2 1528-003- A- 0 703 2 Uni t a ry P rod uc ts Gr o up CONDENSA TE P A N A non-corrosive, lon g-lasting, water-tight pan is posi- tioned below the evaporator coil t o collect and drain all condensate; less collection o f stagnate conde nsate will build-up.
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 3 PROT ECTED COMPRESSO R The com pressor is internally prot ected ag ainst high pressure and tem perature. This is accom plished by the simultaneous operat ion of high pressure relief valve and a temperature sensor which protects the compres- sor, if und esirable operat ing condi tions occ ur.
036-2 1528-003- A- 0 703 4 Uni t a ry P rod uc ts Gr o up RECT ANGLE TO RO UND ADAP TERS Kit includes one supply and one return air rectangle to round duct adapter. Adapt ers are preformed and designed to fit over current duct openings on the base unit.
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 5 SEER =S easonal Energy Efficien cy Ratio - the total cool ing output i n BTU's du ring a no rmal annual usage per iod for coo ling divi d ed by the total electric power i nput in watt -hour s during the same per iod.
036-2 1528-003- A- 0 703 6 Uni t a ry P rod uc ts Gr o up T ABLE 3: COOLING CAP AC ITIES - 2 TO N (BHP024) TEMPERA TURE AIR O N OUTDOOR COIL TEMPERA TURE OF AIR ON INDOOR CO IL 800 CFM 900 C FM WB ° F WB ° F 72 67 62 57 72 67 62 57 85 °F NET CAP . MB H 29.
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 7 T ABLE 4: COOLING CAP AC ITIES - 2-1/2 TON (BHP030) TEMPERAT URE AIR O N OUT DOOR CO IL TEMPERA TURE OF AIR O N INDOOR COI L 1000 C FM 1 125 C FM WB °F WB ° F 72 67 62 57 72 67 62 57 85 °F NET CAP .
036-2 1528-003- A- 0 703 8 Uni t a ry P rod uc ts Gr o up T ABLE 5: COOLING CAP AC ITIES - 3 TO N (BHP036) TEMPERAT URE AIR O N OUT DOOR CO IL TEMPERA TURE OF AIR O N INDOOR COI L 1050 C FM 1200 CFM WB °F WB ° F 72 67 62 57 72 67 62 57 85 °F NET CAP .
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 9 T ABLE 6: COOLING CAP AC ITIES - 3-1/2 TON (BHP042) TEMPERAT URE AIR O N OUT DOOR CO IL TEMPERA TURE OF AIR O N INDOOR COI L 1300 C FM 1400 CFM WB °F WB ° F 72 67 62 57 72 67 62 57 85 °F NET CAP .
036-2 1528-003- A- 0 703 10 Uni t a ry P rod uc ts Gr o up T ABLE 7: COOLING CAP AC ITIES - 4 TO N (BHP048) TEMPERAT URE AIR O N OUT DOOR CO IL TEMPERA TURE OF AIR O N INDOOR COI L 1500 C FM 1600 CFM WB °F WB ° F 72 67 62 57 72 67 62 57 85 °F NET CAP .
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 11 T ABLE 8: HEA TING CAP AC ITIES - 2 TO N (BHP024) CFM RETURN AIR °F CAP 1 & KW OUTDOOR AIR TE MPERA TURE, °F (72% RH) -10 0 10 20 30 40 50 60 600 55 MBH 10.216 1 1.7 48 13.601 15.8 43 1 8.
036-2 1528-003- A- 0 703 12 Uni t a ry P rod uc ts Gr o up T ABLE 10: HEA TING CAP ACITIES - 3 TON (BHP036) CFM RETURN AIR °F CAP 1 & KW OUTDOOR AIR TEM PERA T URE, °F (72% RH) -10 0 10 20 30 40 50 60 900 55 MBH 10.597 12.79 2 15.448 18 .660 22.
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 13 T ABLE 12: HEA TING CAP ACITIES - 4 T ON (BHP048) CFM RETURN AIR °F CAP 1 & KW OUTDOOR AIR TEM PERA T URE, °F (72% RH) -10 0 10 20 30 40 50 60 1200 55 MBH 13 .91 1 17.0 96 21.021 25.859 31.
036-2 1528-003- A- 0 703 14 Uni t a ry P rod uc ts Gr o up NOTE: Above d ata includes allowanc es for a dr y ind oor coil and no fil ters. For ad ditional pres sure drops, r efer to th e “Additio n al S ta tic Pressure Resis t an ce” tabl e. T ABLE 13: SIDE & BOTT OM SUPPLY A IR BLO WER PERFO RMANCE (208 /230/460 VOL T 1 ) MODEL NO.
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 15 FIGURE 2 - FIELD WIRING DIAGRAM R G W R C Y Y W2 C W1 O O G THERMOST A T UNIT TERMINAL STRIP * ** ** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire. * = Only required on units with supplemental electric heat.
036-2 1528-003- A- 0 703 16 Uni t a ry P rod uc ts Gr o up T ABLE 15: ELECTRICAL DA T A (BASIC UNIT) MOD EL BHP POWER SUPPL Y VOL T AGE LIMI T ATIO NS 1 COMPRESSOR OUTDOOR FA N MOTOR , FLA SUPPL Y AIR BLO WER MOT OR, FLA MINI MUM CIRC UIT AMP ACI TY MAX FUS E SIZE, AMP S 2 MAX .
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 17 * KW liste d is for 240 volts, u se T abl e 15 for 208 o r 230 v olts. ** KW listed is for 480 volts, use T able 15 for 460 v olts.
036-2 1528-003- A- 0 703 18 Uni t a ry P rod uc ts Gr o up T ABLE 17: APPLI C A TION DA T A MODE L BHP 024 030 03 6 042 048 MINI MUM AIR FLOW (C FM ) COOLIN G 800 1000 105 0 1300 1500 HEA T ING 800 1 .
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 19 FIGURE 5 - UNIT DIMENSIONS.
036-2 1528-003- A- 0 703 20 Uni t a ry P rod uc ts Gr o up FIGURE 6 - TYPICA L APPLICA TIONS.
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 21 FIGURE 7 - ROO F CURB DIMENSIONS.
036-2 1528-003- A- 0 703 22 Uni t a ry P rod uc ts Gr o up FIGURE 8 - TYPI CAL WIRING DIAGRAM ( 2 08/230-1-60 POWER SUPPLY).
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 23 FIGURE 9 - TYPICAL W IRING DIAGRAM ( 2 30-3-60 POWE R SUPPLY).
036-2 1528-003- A- 0 703 24 Uni t a ry P rod uc ts Gr o up FIGURE 10 - T YP ICA L WIRING DIAGRAM (460-3-60 POWER SU PPLY).
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 25 MECHANICAL SPE CIFICATIONS GENERAL DESCRIPTION Units shal l be f actory-assem bled, single packaged , Heat Pumps, designed for outdoor mou nted installa- tion. Units sha ll have minimum SE ER ratings of 13.
036-2 1528-003- A- 0 703 26 Uni t a ry P rod uc ts Gr o up B. Shall hav e internal isolat i o n and sound muf fli ng to mini m i ze vibrat ion and noise, a nd be externally i so- lat ed on a dedi cated, indep endent mount ing .
036-21 528-003-A-0 703 Uni t a ry P rod uc ts Gr o up 27.
Subjec t to change wi thout noti ce. Pri nted in U.S.A. CD: 6-21528 036-2 1528-003- A-0 703 Copyri ght © by Unit ary Product s Group 2003. All righ ts reserv ed.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York BHP024 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York BHP024 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York BHP024, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York BHP024 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York BHP024, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York BHP024.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York BHP024. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York BHP024 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.