GENERAL YORK Model B*CH units are single package heat pump s designed for outdoor installation on a roof top or a slab. These units can be equipped with factory installed electric heaters for supplemental heating applications. The units are completely assembled on rigid, permanently attached base rails.
035-18895-000-A-0902 2 Unitary Products Group General ................................................................................ 1 Inspection ............................................................................ 1 Reference ..............
LIMIT ATIONS These units must be installed in accordance with applicable national and local or municipal safety codes. Refer to T able 1 for Unit Application Dat a and to T able 2 for Electric Heat Application Data.
FIXED OUTDOOR AIR INT AKE DAMPER This damper assembly is shipped inside the return air compartment. It is completely assembled and ready for installation. A damper baffle inside the hood is adjustable to provide variable amounts of outdoor air int ake on units that are not provided with an economizer or motorized damper option.
insulated wires 1.0mm 2 (#18 A WG) should be used to connect thermostat to unit. Eight conductors are required. The subbase on the low voltage thermostat includes an “Emergency Heat ” position on the system switch and a pilot light. In the “Emergency Heat” position, the thermostat provides electric resistance heat only .
035-18895-000-A-0902 6 Unitary Products Group These heaters are located within the central compartment of the unit with the heater elements extending into the supply air chamber . Refer to Figure 7 for access panel location. Fuses are supplied, where required, by the factory .
035-18895-000-A-0902 Unitary Products Group 7 WEIGHTS (kg. / lbs.) BASIC UNIT 180 948 / 2091 OPTIONS Economizer 73 / 160 Motorized Damper 68 / 150 Electric Heater 18 kW 1 1 / 25 36kW 14 / 30 54 kW 16 .
035-18895-000-A-0902 8 Unitary Products Group FIG . 7 - DIMENSIONS AND CLEARANCES All dimensions are in millimeters and inches, unless otherwise specified. They are subject to change without notice. Certified dimen - sions will be provided upon request.
035-18895-000-A-0902 Unitary Products Group 9 FIG . 7 (Cont'd.) - DIMENSIONS AND CLEARANCES DET AIL “X” ACCESSOR Y SIDE SUPPL Y AND RETURN AIR DUCT OPENINGS DUCT COVERS - Units are shipped with all air duct openings covered. For sideflow duct applications; 1.
035-18895-000-A-0902 10 Unitary Products Group T ABLE 4 - SUPPL Y AIR BLOWER PERFORMANCE BLOWER SPEED, RPM MOTOR PULLEY (TURNS OPEN)* AIRFLOW 1.77 m 3 /s 2.
035-18895-000-A-0902 Unitary Products Group 11 DESCRIPTION EXTERNAL ST A TIC PRESSURE DROP - RESIST ANCE, iwg/Pa m 3 /s (CFM) 180 UNIT 1.77 (3750) 2.12 (4500) 2.48 (5250) 2.83 (6000) WET COIL 0.1 / 25 0.1 / 25 0.1 / 25 0.1 / 25 ELECTRIC HEA T OPTIONS 18 kW 0.
COOLING SYSTEM The cooling section is a complete factory package utilizing an air-cooled condenser . The system is factory-charged with Refrigerant-22. The compressors are hermetically sealed, internally sprung and base-mounted with rubber-insulated hold-down bolts.
HEA T ANTICIP ATOR SETPOINT It is important that the anticipator setpoint be correct. T oo high a setting results in longer heat cycles and a greater temperature swing in the conditioned space. Reducing the value below the correct setpoint causes shorter “ON” cycles and may result in the lowering of the temperature within the conditioned space.
DEFROST SEQUENCE OF OPERATION These heat pumps have a unique “ambient modified” time- temperature defrost control that automatically adjusts to changes in the outdoor temperature. The defrost control shortens the defrost initiation time periods above 2°C (35°F) and extends the defrost initiation time periods below 2°C (35°F .
035-18895-000-A-0902 Unitary Products Group 15 SECURE OWNER'S APPROV AL : When the system is functioning properly , secure the owner's approval. Show him the location of all disconnect switches and the thermostat. T each him how to start and stop the unit and how to adjust temperature settings within the limitations of the system.
035-18895-000-A-0902 5005 Y ork Drive, Norman Oklahoma 73069 Subject to change without notice. Printed in U.S.A Copyright by Y ork International Corporation 2002.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York B2CH180 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York B2CH180 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York B2CH180, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York B2CH180 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York B2CH180, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York B2CH180.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York B2CH180. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York B2CH180 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.