Manuel d'utilisation / d'entretien du produit AFFINITY R-410A du fabricant York
Aller à la page of 56
® FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 333495-YTG-C- 0908 TECHNICAL GUIDE Description These York ® Affinity ™ packaged heat pump s are designed for outdoor installation. Only ut i lity and duct connections are required at the point of installation.
333495-YTG-C-0908 2 Johnson Controls Unitary Products Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
333495-YTG-C-0908 Johnson Controls Unitary Products 3 Nomenclature Heat Pump Features and Benefits Standard Features • Operating Efficiency - All heat pump units provide operating efficiencies of 13 to 15 SEER and 7.7 to 8.0 HSPF. All efficiencies exceed legislated minimum levels.
333495-YTG-C-0908 4 Johnson Controls Unitary Products • More Attracti ve Appearanc e - A single piece Water Shed top cover containing a top discharge condenser fan arrangement requires less square foo tage on installation and provides a wider variety of installations.
333495-YTG-C-0908 Johnson Controls Unitary Products 5 2ET07700224 and 2ET04700224 a re used. Standard in all BHX units. • Filter/Fram e Kit (Sin gle Phase Only) - Kit contains the necessary hardware to field install return air filters into the base unit.
333495-YTG-C-0908 6 Johnson Controls Unitary Products Refrigerant Components Compressors: a. Shall be fully herme tic type, direct drive, internally protected with in ternal high-pressure reli ef and over temperature protection. The herme tic motor shall be suction gas cooled an d have a voltage range of +/- 10 % of the unit nameplate voltage.
333495-YTG-C-0908 Johnson Controls Unitary Products 7 Physical Data BHZ024-060 Physical Data Component Models BHZ024 BHZ030 BHZ036 BHZ042 BHZ048 BHZ060 Nominal Tonnage 2.0 2.5 3.0 3.5 4.0 5.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 22.
333495-YTG-C-0908 8 Johnson Controls Unitary Products BHX024-060 Physical Data Component Models BHX024 BHX036 BHX048 BHX060 Nominal Tonnage 2.0 3.0 4.0 5.0 ARI COOLING PERFORMANCE Gross Capacity @ ARI A point (Btu) 24.9 35.3 49.2 58.8 ARI net capacity (Btu) 24.
333495-YTG-C-0908 Johnson Controls Unitary Products 9 BHZ and BHX Unit Limitations Size (Tons) Model Unit Voltage Unit Limitation s Applied Voltage Outdoor DB Temp Min Max Max (°F) 024 (2.0) BHZ 208/230-1-60 187 252 125 BHX 208/230-1-60 187 252 115 030 (2.
333495-YTG-C-0908 10 Johnson Controls Unitary Products Capacity Performance BHZ024-060 Cooling Capa cities BHZ024 (2.0 Ton) Air on Evaporator Coil Temperature of Air on Condenser Coil Net Capacity 1 (.
333495-YTG-C-0908 Johnson Controls Unitary Products 11 115°F 125°F 600 77 22.6 2.3 12.1 9.2 6.4 - - - 22.5 2.6 12.4 9.5 6.7 - - - 72 20.6 2.3 16.0 13.1 10.3 7.4 - - 19.7 2.5 15.7 12.8 10.0 7.1 - - 67 18.6 2.3 18.6 17.0 14.1 11.3 8.4 - 16.9 2.5 16.9 16.
333495-YTG-C-0908 12 Johnson Controls Unitary Products BHZ030 (2.5 Ton) Air on Evaporator Coil Temperature of Air on Condenser Coil Net Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) Net.
333495-YTG-C-0908 Johnson Controls Unitary Products 13 115°F 125°F 750 77 29.2 3.1 13.8 10.2 6.7 - - - 26.0 3.3 12.5 8.9 5.3 - - - 72 26.4 3.1 18.6 15.1 11.5 7.9 - - 23.4 3.4 17.5 13.9 10.4 6.8 - - 67 23.7 3.2 23.5 19.9 16.3 12.8 9.2 - 20.8 3.5 20.8 19.
333495-YTG-C-0908 14 Johnson Controls Unitary Products BHZ036 (3.0 Ton) Air on Evaporator Coil Temperature of Air on Condense r Coil Net Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh) Net.
333495-YTG-C-0908 Johnson Controls Unitary Products 15 115°F 125°F 900 77 34.1 3 .9 18.5 14.2 9 .9 - - - 31.2 4.4 16.9 12.6 8.3 - - - 72 30.5 3 .8 24. 0 19.7 15.4 11 .1 - - 27.3 4. 3 22.4 1 8.1 13.8 9 .6 - - 67 26.8 3.7 26.8 25.2 20.9 16.6 12 .3 - 23.
333495-YTG-C-0908 16 Johnson Controls Unitary Products BHZ042 (3.5 Ton) Air on Evaporator Coil Temperature of Air on Condenser Coil Net Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) Net.
333495-YTG-C-0908 Johnson Controls Unitary Products 17 115°F 125°F 1050 77 36.6 4.1 21.7 16.7 11.7 - - - 33.6 4.3 21.1 16.1 11.2 - - - 72 32.6 4.0 28.7 23.7 18.7 13.7 - - 29.0 4.3 27.5 22.6 17.6 12.6 - - 67 28.7 3.9 28.7 28.7 25.7 20.7 15 .7 - 24.4 4.
333495-YTG-C-0908 18 Johnson Controls Unitary Products BHZ048 (4.0 Ton) Air on Evaporator Coil Temperature of Air on Condenser Coil Net Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) Net.
333495-YTG-C-0908 Johnson Controls Unitary Products 19 115°F 125°F 1200 77 47.0 4.1 27.1 21.4 15.7 - - - 42.2 4.5 26.3 20.6 14.9 - - - 72 41.5 4.0 34.9 29.2 23.5 17.8 - - 36.5 4.3 34.1 28.4 22.7 17.0 - - 67 36.0 4.0 36.0 36.0 31.4 25.7 20 .0 - 30.9 4.
333495-YTG-C-0908 20 Johnson Controls Unitary Products BHZ060 (5.0 Ton) Air on Evaporator Coil Temperature of Air on Condenser Coil Net Capacity 1 (MBh) Total Input (kW) 2 Sensible Capacity (MBh ) Net.
333495-YTG-C-0908 Johnson Controls Unitary Products 21 115°F 125°F 1500 77 52.2 6.2 27.9 20.8 13.7 - - - 46.7 6.6 26.3 19.2 12.1 - - - 72 47.9 6.1 36.8 29.7 22.6 15.5 - - 42.0 6.5 33.6 26.5 19.4 12.2 - - 67 43.5 5.9 43.5 38.6 31.5 24.3 17 .2 - 37.2 6.
333495-YTG-C-0908 22 Johnson Controls Unitary Products BHX024-060 Cooling Capacities BHX024 (2.0 Ton) Air on Evaporator Coil Temperature of Air on Condense r Coil Net Capacity 1 (MBh) 1. These capacities are Net Capacities. Total Input (kW) 2 2. These ratings include the compressor, co ndenser fan and supply air blower motors.
333495-YTG-C-0908 Johnson Controls Unitary Products 23 BHX036 (3.0 Ton) Air on Evaporator Coil Temperature of Air on Condense r Coil Net Capacity 1 (MBh) 1. These capacities are Net Capacities. Total Input (kW) 2 2. These ratings include the compressor, co ndenser fan and supply air blower motors.
333495-YTG-C-0908 24 Johnson Controls Unitary Products BHX048 (4.0 Ton) Air on Evaporator Coil Temperature of Air on Condenser Coil Net Capacity 1 (MBh) 1. These capacities are Net Capacities. Total Input (kW) 2 2. These ratings include the compressor, co ndenser fan and supply air blower motors.
333495-YTG-C-0908 Johnson Controls Unitary Products 25 BHX060 (5.0 Ton) Air on Evaporator Coil Temperature of Air on Condense r Coil Net Capacity 1 (MBh) 1. These capacities are Net Capacities. Total Input (kW) 2 2. These ratings include the compressor, co ndenser fan and supply air blower motors.
333495-YTG-C-0908 26 Johnson Controls Unitary Products Heating Capacities BHZ024-060 Size (Tons) Air Over Evaporator Coil Capacity 1 & kW 2 Outdoor Temperature (°F @ 72% RH) CFM DB (°F ) -10 0 10 20 30 40 50 60 024 (2.0) 600 55 MBH 4.86 6.37 8.30 10.
333495-YTG-C-0908 Johnson Controls Unitary Products 27 036 (3.0) 900 55 MBH 11.61 13.92 16.68 19.98 23.94 28.67 34.32 41.0 9 KW 1.98 2.15 2.32 2.49 2.65 2.82 2.99 3.16 70 MBH 10.65 12.96 15.72 19.02 22.98 27.71 33.37 40.1 4 KW 2.34 2.51 2.68 2.85 3.02 3.
333495-YTG-C-0908 28 Johnson Controls Unitary Products 048 (4.0) 1200 55 MBH 17.36 20.44 24.07 28.36 33.44 39.45 46.55 54.9 5 KW 2.47 2.63 2.78 2.93 3.08 3.23 3.39 3.54 70 MBH 15.59 18.66 22.29 26.58 31.66 37.67 44.78 53.1 8 KW 2.93 3.09 3.24 3.39 3.54 3.
333495-YTG-C-0908 Johnson Controls Unitary Products 29 BHX024-060 (5.0 Ton) Size (Tons) Air Over Evaporator Coil Capacity 1 & kW 2 1. These Capacities are net capacities - the indoor motor heat has been added. 2. These power inputs are total power inputs - the indoor motor watts have been added.
333495-YTG-C-0908 30 Johnson Controls Unitary Products Airflow Performanc e Side Duct Application BHX024-060 Size (Tons) Model Mod e Thermostat Input Speed Tap CFM External Static Pr essure (Inch Water Gauge) 0 . 20 . 30 . 40 . 50 . 60 . 70 . 80 . 91 .
333495-YTG-C-0908 Johnson Controls Unitary Products 31 048 (4.0) BHX Cool Low Y1 COOL-A 1050 184 216 248 280 313 346 380 414 448 Y1 COOL-B 918 138 166 194 224 254 286 31 8 351 385 Y1 COOL-C 984 160 19.
333495-YTG-C-0908 32 Johnson Controls Unitary Products BHZ024-060 Size (Tons) Model Unit Speed External Static Pressure (Inch Water Gauge) 0.2 0.4 0.6 0.
333495-YTG-C-0908 Johnson Controls Unitary Products 33 Bottom Duct Application BHX024-060 Size (Tons) Model Mod e Thermostat Input Speed Tap CFM External Static Pr essure (Inch Water Gauge) 0 . 20 . 30 . 40 . 50 . 60 . 70 . 80 . 91 . 0 Watts Watts Watts Watts Watts Watts Watts Watts Watts 024 (2.
333495-YTG-C-0908 34 Johnson Controls Unitary Products 048 (4.0) BHX Cool Low Y1 COOL-A 1050 184 216 248 280 313 346 380 414 448 Y1 COOL-B 918 138 166 194 224 254 286 31 8 351 385 Y1 COOL-C 984 160 19.
333495-YTG-C-0908 Johnson Controls Unitary Products 35 BHZ024-060 Size (Tons) Model Unit Speed External Static Pressure (Inch Water Gauge) 0.2 0.4 0.6 0.
333495-YTG-C-0908 36 Johnson Controls Unitary Products Additional Static Resistance Size (Tons) Model C FM Wet Indoor Coil Econom izer 1 1. The pressure drop through the economizer is greater for 100 % out door air than for 100% retu rn air. If the resistance of the r eturn air duct is less than 0.
333495-YTG-C-0908 Johnson Controls Unitary Products 37 Sound Performance Electric Heat Minimum Supply Air Size (Tons) Model Voltage Minimum Supply Air (CFM) Heater kW 5.0 7.5 10.0 15 .0 20.0 25.0 024 (2.0) BHZ BHX 208/230-1-60 630 630 800 - - - 030 (2.
333495-YTG-C-0908 38 Johnson Controls Unitary Products Electrical Data BHZ024-060 Heat Pump With/Without Electric Heat Size (Tons) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Electr i c H e at O pt ion MCA 1 (Amps) 1. Minimum Circuit Ampacity.
333495-YTG-C-0908 Johnson Controls Unitary Products 39 BHX024-060 Heat Pu mp With/Without Electric Heat Size (Tons) Volt Compressors (each) OD Fan Motors (each) Supply Blower Motor Electric Heat Option MCA 1 (Amps) 1. Minimum Circuit Ampacity. Max Fuse 2 / Breaker 3 Size (Amps) 2.
333495-YTG-C-0908 40 Johnson Controls Unitary Products Typical BHX/BHZ024-060 Wiring Diag rams Typical BHX024, 048 and 060 Heat Pump 20 8/230-1-60 volt Wiring Diagram.
333495-YTG-C-0908 Johnson Controls Unitary Products 41 Typical BHX036 Heat Pump 208/ 230-1-60 vo lt Wiring Diagram.
333495-YTG-C-0908 42 Johnson Controls Unitary Products Typical BHZ024-060 Heat Pump 208 /230-1-60 volt Wiring Diagram.
333495-YTG-C-0908 Johnson Controls Unitary Products 43 Typical BHX048 and 060 Heat Pump 230-3-60 volt Wiring Dia gram.
333495-YTG-C-0908 44 Johnson Controls Unitary Products Typical BHX036 Heat Pump 2 30-3-60 volt W iring Diagram.
333495-YTG-C-0908 Johnson Controls Unitary Products 45 Typical BHZ030-060 Heat Pump 230-3-60 vo lt Wiring Diagram.
333495-YTG-C-0908 46 Johnson Controls Unitary Products Typical BHX048 and 060 Heat Pump 460-3-60 volt Wiring Dia gram.
333495-YTG-C-0908 Johnson Controls Unitary Products 47 Typical BHX036 Heat Pump 4 60-3-60 volt W iring Diagram.
333495-YTG-C-0908 48 Johnson Controls Unitary Products Typical BHZ030-060 Heat Pump 460-3-60 vo lt Wiring Diagram.
333495-YTG-C-0908 Johnson Controls Unitary Products 49 Weights and Dimensions BHX AND BHZ Unit Weights Unit 4 Point Load Weig ht Size (Tons) Model Weight (lbs.) Center of Gravity 4 Point Load Locatio n (lbs.) Shipping Operating X Y A B C D 024 (2.0) BHZ 360 355 22.
333495-YTG-C-0908 50 Johnson Controls Unitary Products Heat Pump Unit Dimensions Note: For units applied with a roof curb, the minimu m clear ance may be reduced from 1 inch to 1/2 in ch between combustible roof curb material a nd this supply air duct.
333495-YTG-C-0908 Johnson Controls Unitary Products 51 Unit Dimensions Front and Bottom Unit Dimensions Back and Bottom 6 19-1/4 1 1-7/8 8-7/8 FRONT GAS SUPPL Y 1-5/8" DIA. KNOCKOUT (1/2" NPTI CONNECTION) LOW VOL T AGE CONN. 7/8" DIA. KNOCKOUT 4-5/8 26-3/4 CONDENSA TE DRAIN 3/4" NPTF HIGH VOL T AGE CONN.
333495-YTG-C-0908 52 Johnson Controls Unitary Products Unit Typical Duct Applications Unit Typical Slab on Ground Installation ROOF CURB INST ALLA TION REAR DUCT ROOF CURB INST ALLA TION BOTTOM DUCT S.
333495-YTG-C-0908 Johnson Controls Unitary Products 53 Unit Typical Roof Curb Installation Unit Accessory Dimensions Roof Curb 1 1. 8” Roof Curb also available.
333495-YTG-C-0908 54 Johnson Controls Unitary Products Roof Curb Cross Section 1" UNIT BASE RAIL COUNTERFLASHING CANT STRIP INSULA TION AND ROOFING MA TERIAL ROOF DECK AND ROOFING MA TERIAL INSULA TION CURB FRAME 14" 8" MIN.
333495-YTG-C-0908 Johnson Controls Unitary Products 55.
Subject to change without notice. Print ed in U. S.A. 333495-YTG-C-0908 Copyright © 2008 by Johnson Controls, In c. All rights reserved. Supersedes: 333495- YTG-B-0807 Johnson Cont rols Unitary Pr od.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté York AFFINITY R-410A c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du York AFFINITY R-410A - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation York AFFINITY R-410A, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le York AFFINITY R-410A va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le York AFFINITY R-410A, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du York AFFINITY R-410A.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le York AFFINITY R-410A. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei York AFFINITY R-410A ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.