Manuel d'utilisation / d'entretien du produit WINE-MATE VINO4500DS du fabricant Vinotemp
Aller à la page of 31
w w w w w w . . w w i i n n e e m m a a t t e e . . c c o o m m WINE-MATE Ducted System Installation, Operation & Care Manual VINO4500DS VINO6500DS VINO8500DS V V i i n n o o t t e e m m p p I I n n t t e e r r n n a a t t i i o o n n a a l l C C o o r r p p .
- 1 - TABLE OF CONTENTS Important Safety Info rmation…..........................................2 Features & Specifications.…………………….……………..3 Cellar Construction.…………………………….……………..5 Installer’s Instruction…………….
- 2 - Important Safety Information WARNING: • DO NOT USE A GROUND FAUL T INTERRUPTER (GFI). • A DEDICATED 20 OR 30 AMP CIRCUI T IS REQUIRED (4500DS OR 6500- 8500DS).
- 3 - Features and Specifications • WINE-MATE ducted system VINO4500- 8500DS are designed and used to provide a cold temperature between 50~65 ° F for a properly insulated wine room at a normal environment. • The wine room will maintain hum idity of 50~70% RH even when the environment becomes dry and humid.
- 4 - Fig. 2 VINO4500- 8500DS DIMENSIONS The dimensions and capacities are specified as follows: MODEL DIMENSION L”xW”xH” Btu/h, CFM (55/90 ° F) CA PA CITY (55/75 ° F) REF RI GERA NT ELECTRICA.
- 5 - Cellar Construction This is only a guide and shall be c onsidered as minimum requirements. All interior walls and floors shall have a vapor barrier and a minimum of R11 insulation. All exterior walls and ceiling shall have a vapor barrier and a minimum of R19 insulation.
- 6 - Installer’s Instruction Federal law requires that WINE -MATE ducted cooling systems be installed by an EPA certified refrigeration technician. WINE-MATE ducted system is shipped re ady for use only after a certified refrigeration technician has properly inst alled the system.
- 7 - 1. Location • Place the unit in a properly ventilated location. If it is not, heat exhausted by the condensing unit will build up and the cooling syst em will not operate properly. • Cooling unit shall be elevated to avoid possible flooding and shaded from direct sun.
- 8 - Fig. 4 Fan Speed Control 6. Intake and Exhaust Guards • If the intake and exhaust are locat ed outdoor, protection guards may be required. MODEL INSULATED DUCT DRAIN LINE VINO-4500DS 8” DIA 7/8” OD VINO-6500DS 10” DIA 7/8” OD VINO-8500DS 10” DIA 7/8” OD 7.
- 9 - Temperature Control & Humidity Adjustment 1. Temperature Setting • Set the temperature at 55 ° F for the optimum aging of wine • On initial start-up, the time required to reach the desired temperature will vary, depending on the quantit y of bottles, temperature setting and surrounding temperature.
- 10 - 2.1 LED Functions LED MODE FUNCTION ON Compressor enabled Flashing Anti-short cycle enabled ON Defrost cycle enabled ON Fan enabled Flashing Fan delay after defrost enabled ON Alarm occurring ON Temperature measuring unit Flashing Programming mode 3) Alarm Signals 3.
- 11 - 5) Parameter Programming 1. Press the SET + keys for 3 sec until the “ °C” or “°F” LED starts blinking, then release the keys. 2. Press again the SET + keys for more th an 7sec until the Pr2 label will be displayed, then release the keys.
- 12 - Service Guide 1. Refrigeration Piping, Evacu ating, Charging and Starting CAUTION: • ALWAYS USE THE SUPERHE AT AND SUBCOOLING, PRESSURE READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED CHARGES ARE FOR REFERENCE ONLY. • CHARGE 15% MORE REFRIGERANT IN THE SUMMER IF THE UNIT IS EQUIPPED WITH A LOW AMBIENT CONDITION KIT.
- 13 - 9) The temperature split between retu rn air and supply air shall be 8 ~ 10 ° F at 55 ° F wine room temperature. 10) Again, must verify if the superheat at the evaporator unit is around 9 ~ 18 ° F at 50 ~ 65 ° F wine room temperatur e with a normal ambient temperature.
- 14 - BACK POSITION FRONT POSITION MIDDLE POSITION Fig. 9 ROTALOCK Valve Operation BACK POSITION FRONT POSITION MIDDLE POSITION Fig. 10 Base Valve Operation 1 - Process & Manometer; 2 – Receiver Di scharge or Compressor Suction 3 – Liquid Line or Suction Line; 4 - Pressure Control 3.
- 15 - A. P70 Single/Dual Control Fig. 11 Adjustable Pressure Control B. PS2 Dual Control Fig. 12 Adjustable Pressure Control 4. Use of the encapsulated pressu re control (if applicable) Fixed suction pressure setting: Cut in = 32 psig; Cut out = 10 psig Fig.
- 16 - 5. Use of the condenser fan control (i f applicable for low ambient kit) Head pressure setting: Cut in=170 psig; Cut out=120 psig; Differential=50 psig It closes on rise of pressure. It may need to adjust the setting in the field to avoid fan short cycle.
- 17 - 8. Condensing Unit Troubleshooting Unit not running a. Incorrect power supply b. Incorrect or loose wirings c. Failed components d. Liquid refrigerant in the compre ssor e. Low pressure switch sh utting do wn the system a. Check for proper voltag e b.
- 18 - Electrical Wiring CAUTION: • USE MINIMUM 14 GAUGE WIRES. • IF EQUIPPED WITH LOW AMBIENT CO NDITION KIT, USE LOW AMBIENT TEMPERATURE WIRING DIAGRAMS. TURN OFF THE COMPRESSOR BEFORE POWER THE CONDENSING UNIT. ONLY TURN ON THE COMPRESSOR AFTER THE CONDENS ING UNIT HAS BEEN POWERED FOR 24 HOURS.
- 19 - Fig. 15 VINO6500DS Elect rical Wiring Diagram.
- 20 - Fig. 16 VINO8500DS Elect rical Wiring Diagram.
- 21 - Fig. 17 Low Ambient Temperature VINO45000DS Electrical Wiring Diagram.
- 22 - Fig. 18 Low Ambient Temperature VINO65000DS Electrical Wiring Diagram.
- 23 - Fig. 19 Low Ambient Temperature VINO8500DS Electrical Wiring Diagram.
- 24 - Care Guide In general, always unplug system or di sconnect power while doing care. 1. Coil Cleaning • Clean the condenser coil regularly. Coil may need to be cleaned at least every 6 months. • Unplug the system or disconnect power. • Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty.
- 25 - User’s Troubleshooting This Troubleshooting Chart is not prepared to replace the training required for a professional refrigeration servic e person, not is it comprehensive Complaint Possible Causes Response 1.Unit not running a. No power b. Power cord unplug ged c.
- 26 - running continually e. Malfunctioning fans f. Improper evaporator or condenser airflow g. Dir ty Con denser h. Iced evaporator i. Sealed system problem j. Undercharge or overcharg e the exhaust side and leave minimum 1 foot clearance for the fresh air intake side e.
- 27 - 10.Noisy operation a. Mounting area not firm b. Loose parts c. Compressor overlo aded due to high ambient temperatures o r airflow restrict ion d. Malfunctioning components a. Add support to improve installation b. Check fans, cabinet washers, tubing contact and loose screws.
- 28 - Customer Support If you still have problems, please contact us at: Vinotemp International 17631 South Susana Road Rancho Dominguez, CA 90221 Tel: (310) 886-3332 Fax: (310) 886-3310 Email: info@vinotemp.
- 29 - Warranty Thank you for choosing a Vinotemp cooling unit. Please enter the complete model and se rial numbers in the space provided: Model_____________ _________________________ __ _________________ Serial No._________________ ____________________ _________________ Attach your purchase receipt to this owner’s manual.
- 30 - VINOTEMP will, at its discret ion, repair or replace the unit and return it free of charge to the original retail customer. If the unit is found to be in good working order, or beyond the initial twelve month period, it will be returned freight collect.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Vinotemp WINE-MATE VINO4500DS c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Vinotemp WINE-MATE VINO4500DS - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Vinotemp WINE-MATE VINO4500DS, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Vinotemp WINE-MATE VINO4500DS va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Vinotemp WINE-MATE VINO4500DS, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Vinotemp WINE-MATE VINO4500DS.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Vinotemp WINE-MATE VINO4500DS. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Vinotemp WINE-MATE VINO4500DS ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.