© 2010 Trane 2 22-1817-10


Model No. 1 4TTX5018A1 4TTX5024A1 4TTX5030A1 4TTX5036A1 Electrical Data V/Ph/Hz 2 200/230/1/60 200/230/1/60 200/230/1/60 208/230/1/60 Min Cir Ampacity 8 11 15 22 Max Fuse Size (Amps) 15 20 25 35 Compressor CLIMATUFF® - SCROLL No. Used - No Stages 1-1 RL Amps - LR Amps 6.2 - 38.6 8.6 - 57.8 11.1 - 63 16.7 - 79 Outdoor Fan FL Amps 0.74 0.74 0.74 0.93 Fan HP 1/8 1/8 1/8 1/5 Fan Dia (inches) 27.6 27.6 27.6 26.6 Coil Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™ Refrigerant R-410A 6/09-LB/OZ 6/10-LB/OZ 6/10-LB/OZ 7/11-LB/OZ Line Size - (in.) O.D. Gas 3 1/2 5/8 3/4 3/4 Line Size - (in.) O.D. Liquid 3 3/8 Dimensions H x W x D (Crated) 45.4 x 35.1 x 38.7 45.4 x 35.1 x 38.7 45.4 x 35.1 x 38.7 53.4 x 35.1 x 38.7 Weight - Shipping 271 275 276 283 Weight - Net 227 230 232 235 Start Components YES YES YES NO Sound Enclosure YES Compressor Sump Heat NO Optional Accessories: 4 Anti-short Cycle Timer TAYASCT501A Evaporator Defrost Control A/C AY28X079 Rubber Isolator Kit BAYISLT101 Crank Case Heater Kit BAYCCHT300 BAYCCHT300 BAYCCHT300 BAYCCHT301 Hard Start Kit Scroll BAYKSKT260 Extreme Condition Mounting Kit BAYECMT001 Snow Leg - Base & Cap 4" High BAYLEGS002 Snow Leg - 4" Extension BAYLEGS003 Seacoast Kit BAYSEAC001 Refrigerant Lineset 5 TAYREFLN850 TAYREFLN950 TAYREFLN7* TAYREFLN7* 1 Certified in accordance with the Unitary Air-Conditioner equipment certification program which is based on AHRI Standard 210/240. 2 Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. 3 Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0†. (†denotes latest revision) 4 For accessory description and usage, see page 5. 5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.
4 22-1817-10

Model No. 1 4TTX5042A1 4TTX5048A1 4TTX5049E1 4TTX5060A1 4TTX5061E Electrical Data V/Ph/Hz 2 208/230/1/60 230/1/60 Min Cir Ampacity 26 28 28 34 39 Max Fuse Size (Amps) 45 50 45 60 60 Compressor CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL CLIMATUFF® - SCROLL No. Used - No. Stages 1-1 1-2 RL Amps - LR Amps 19.9 - 109 21.8 - 117 19.9 - 109 26.4 - 134 28.8 - 152.9 Outdoor Fan FL Amps 0.93 0.93 2.8 0.93 2.8 Fan HP 1/5 1/5 1/3 1/5 1/3 Fan Dia (inches) 27.6 Coil Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™ Spine Fin™ Refrigerant R-410A 7/00-LB/OZ 11/00-LB/OZ 11/9-LB/OZ 11/00-LB/OZ 12/9-LB/OZ Line Size - (in.) O.D. Gas 3 3/4 7/8 7/8 1-1/8 1-1/8 Line Size - (in.) O.D. Liquid 3 3/8 Dimensions H x W x D (Crated) 53.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 57.4 x 35.1 x 38.7 Weight - Shipping 305 352 324 354 332 Weight - Net 257 302 287 304 295 Start Components NO NO NO YES NO Sound Enclosure YES YES NO YES NO Compressor Sump Heat NO Optional Accessories: 4 Anti-short Cycle Timer TAYASCT501A Evaporator Defrost Control A/C AY28X079 Rubber Isolator Kit BAYISLT101 Crank Case Heater Scroll BAYCCHT301 Hard Start Kit Scroll BAYKSKT260 BAYKSKT260 BAYKSKT260 Extreme Condition Mounting Kit BAYECMT001 BAYECMT001 BAYECMT004 BAYECMT001 BAYECMT004 Snow Leg - Base & Cap 4" High BAYLEGS002 Snow Leg - 4" Extension BAYLEGS003 Seacoast Kit BAYSEAC001 Refrigerant Lineset 5 TAYREFLN7* TAYREFLN3* TAYREFLN3* TAYREFLN4* TAYREFLN*4
1 Certified in accordance with the Air-Source Unitary Heat Pump Equipment certification program which is based on AHRI Standard 210/240. 2 Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses. 3 Standard line lengths - 60'. Standard lift - 60' Suction and Liquid line. For 061 units, Max. linear length 60 ft.; Max. lift - Suction 25 ft.; Max lift - Liquid 25 ft. For Greater lengths and lifts refer to refrigerant piping software Pub# 32-3312-0†. (†denotes latest revision) 4 For accessory description and usage, see page 5. 5 * = 15, 20, 25, 30, 40 and 50 foot lineset available.
22-1817-10 5

AHRI Standard Capacity Rating Conditions
Anti-Short Cycle Timer — Solid state timing device that prevents compressor recycling until 5 minutes have elapsed after satisfying call or power interruptions. Use in area with questionable power deliv ery, commercial applications, long lineset, etc.
AHRI STANDARD 210/240 RATING CONDITIONS — (A) Cooling 80°F DB, 67°F WB air entering indoor coil, 95°F DB air
entering outdoor coil. (B) High Temperature Heating 47°F DB, 43°F WB air entering out
Evaporator Defrost Control — SPST Temperature actuated switch that cycles the condenser off as indoor coil reaches freeze-up condi tions. Used for low ambient cooling to 30°F with TXV.
door coil, 70°F DB air entering indoor coil. (C) Low Temperature Heating 17°F DB, 15°F WB air entering out
door coil, 70°F DB air entering indoor coil. (D) Rated indoor airflow for heating is the same as for cooling.
Rubber Isolators — 5 large rubber donuts to isolate condensing unit from transmitting energy into mounting frame or pad. Use on any ap plication where sound transmission needs to be minimized.
AHRI STANDARD 270 RATING CONDITIONS — (Noise rating numbers are determined with the unit in cooling operation.) Standard Noise Rating number is at 95°F outdoor air.
Hard Start kit — Start capacitor and relay to assist compressor mo tor startup. Use in areas with marginal power supply, on long linesets, low ambient conditions, etc.
Extreme Condition Mount Kit — Bracket kits to securely mount condensing unit to a frame or pad without removing any panels. Use in areas with high winds, or on commercial roof tops, etc.
6 22-1817-10

4 T T X 5 0 3 6 A 1 0 0 0 A A
T U Y 0 8 0 R 9 V 3 W 0


Type C = Condensing D = Induced Draft E = Electronic Ignition X = Direct Vent Condensing Y = Direct Vent Condensing Variable Speed
Product Type W = Split Heat Pump T = Split Cooling
Product Family Z = Leadership – Two Stage X = Leadership R = Replacement/Retail B = Basic A = Light Commercial
Major Design Change C = Single Stage R = Two Stage All other = Standard System
Family SEER 0 = 10 3 = 13 6 = 16 1 = 11 4 = 14 8 = 18 2 = 12 5 = 15 9 = 19
Airflow Capacity for Cooling Example: 36 = 3 Tons 400 CFM/Ton 400 x 3 Tons = 1200 CFM V3 = 1 1/2 – 3 Tons, Variable Speed Motor (ICM) V4 = 2 – 4 Tons, Variable Speed Motor (ICM) V5 = 3 – 5 Tons, Variable Speed Motor (ICM)
Power Supply 1 = 200-230/1/60 or 208-230/1/60 3 = 200-230/3/60 4 = 460/3/60
4 T E E 3 F 3 6 A 1 A A 0 0 0
T X C 0 2 4 C 4 H P C 0


Refrigerant Type 4 = R-410A 2 = R-22
Refrigerant Type T = R-22 R = R-410A C = Cooling only
Application TE = Fully Convertible TG = Semi Convertible TF = Front Return TV = Vertical
Furnace Coils XA = Uncased “A” Coil Upflow/Downflow XC = Cased Coil Upflow/Downflow/Horizontal XH = Cased Horizontal Only CB = Cased/Brazed Upflow – Cooling Only UB = Uncased/Brazed Upflow – Cooling Only
Product Family E = Leadership – Variable Speed P = Leadership C = Replacement/Retail B = Basic
Coupling 0 = Braze
Flow Control 3 = Nonbleed TXV 4 = FCCV*
Product Family C = Universal S = High Efficiency – Nonbleed TXV E = High Efficiency – Bleed TXV A = Upflow Only D = Reverse Airflow
Feature Identifier 0 = Standard Unit F = Air-Tite™
Power Supply 1 = Single Phase
Refrigerant Control 2 = Cap Tube 3 = Nonbleed TXV 4 = Accutron™ Flow Control/Check Valve (FCCV) 5 = Bleed TXV
Electrical Connection 0 = Pig Tails B = Circuit Breaker D = Pull Disconnect
HP = Heat Pump 00 = Cooling only (7 1/2 to 10 ton)
Future Option – Factory Installed Heater Nominal KW Value
Service Digit – Not Orderable

© 2010 Trane 8 22-1817-10

22-1817-10 9

10 22-1817-10

22-1817-10 11

12 22-1817-10

Printed from D156578P01v · 22-1817-10 13

14 22-1817-10

22-1817-10 15

16 22-1817-10

22-1817-10 17

4TTX5 Outline Drawing Note: All dimensions are in MM (Inches).
MODELS BASE FIG. A B C D E F G H J K
From Dwg. 21D152635 Rev. 14
4TTX5049E 4 1 1369 (53-7/8) 946 (37-1/4) 870 (34-1/4) 7/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)
4TTX5061E 4 1 1369 (53-7/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 730 (28-3/4)
18 22-1817-10

General The 4TTX5 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.
Condenser Coil The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels.
Low Ambient Cooling As manufactured, this unit has a cool ing capability to 55°F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30°F.
Casing Unit casing is constructed of heavy gauge, G90 galvanized steel and painted with a weather-resistant powder paint on all louvers, panels, prepaint on all other panels. Corrosion and weather proof CMBP-G30 DuraTuff™ base.
Accessories Thermostats — Cooling only and heat/ cooling (manual and automatic change over). Sub-base to match thermostat and locking thermostat cover.
Evaporator Defrost Control — See Low Ambient Cooling.
Refrigerant Controls Refrigeration system controls include condenser fan, compressor contactor and high pressure switch. High and low pressure controls are inherent to the compressor. A factory installed liquid line drier is standard.
Compressor The Climatuff® compressor features internal over temperature and pressure protection and total dipped hermetic motor. Other features include: roto lock suction and discharge refrigerant con nections, centrifugal oil pump and low vibration and noise.
22-1817-10 19

Trane A business of American Standard Companies www.trane.com
Trane has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
Pages mentionnées dans ce manuel — fabricant, assistance et téléchargements.
Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.
Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.