MODEL 3100-XX FLAME DETECTOR.
Sierra Monitor Corporation 1991 T arob Court, Milpitas, CA 95035 (408) 262-661 1, T oll Free: 800-727-4377 Fax: 408-262-9042 MODEL 3100-XX Flame Detector APPLICABILITY & EFFECTIVITY This manual pr.
Instruction Manual T able of Contents TABLE OF CONTENTS SECTION PAGE 1 . PRODUCT DESCRIPTION 1 2 . OPERA TION 2 2.1 General 2 2.2 Field-of-V iew 3 2.3 Range 3 2.4 Environment 3 2.5 Configuration 3 2.6 LED operation 4 2.7 Relay operation 5 3 . INST ALLA TION 7 3.
Model 3100 Series Flame Detector (1 1/04) Page: 1 Instruction Manual FIGURE 1-1: Model 3100 Series Flame Detector 1. PRODUCT DESCRIPTION 1.1 Introduction All versions of the Model 3100 Flame Detector Se- ries utilize Ultraviolet, Infrared and V isible spectrum to provide continuous and reliable flame detection.
Instruction Manual Page: 2 Model 3100 Series Flame Detector (1 1/04) 2 . OPERA TION 2. 1 General When the Model 3100 Flame Detector is powered up, the microprocessor checks the configuration switch settings and configures the detector . The mi- croprocessor then runs a full series of self tests.
Model 3100 Series Flame Detector (1 1/04) Page: 3 Instruction Manual 2.2 Field-of-V iew (See Figur e 2-1) Optical Flame Detectors must be able to “see” the fire to declare an alarm. Any obstruction between the detector and the threat area will impair the de- tectors ability to cover the threat area.
Instruction Manual Page: 4 Model 3100 Series Flame Detector (1 1/04) LED 1 LED 2 Mounting Screw (2 locations) Configuration Switches 2.5.2 V erify Control The Enhanced Model 3100-02, -03, -04, - 05 and -06 have the V erified Fire function.
Model 3100 Series Flame Detector (1 1/04) Page: 5 Instruction Manual (“on” or “off”) of a switch (SW1-SW8). The first flash pattern indicates the position of the first switch (SW1), with each consecu- tive flash indicating the position of the next switch in order .
Instruction Manual Page: 6 Model 3100 Series Flame Detector (1 1/04) ing” - remain energized until power is re- moved, ”Fire Following” - de-energize a short time after the fire is no longer detected. The “J2” connector provides connections for both normally open contacts and normally closed contacts on the Fire Relay .
Model 3100 Series Flame Detector (1 1/04) Page: 7 Instruction Manual 3. 0 INST ALLA TION 3.1 General Precautions All wiring and installation must be done in accor- dance with the NFP A 70 and 72 standards and must comply with any codes specific to the application or location.
Instruction Manual Page: 8 Model 3100 Series Flame Detector (1 1/04) 3.3.5 Auxiliary Relay The Auxiliary Relay connector is located be- tween the Power and Fire Relay connectors. The connection points are labeled “Aux In” and “Aux Out”. The Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 9 Instruction Manual 5 . 0 TROUBLESHOOTING The flame detector has several built-in self test mechanisms which verify function and calibration. The following procedure covers most faults and problems which may occur during installation or during the course of normal operation.
Instruction Manual Page: 10 Model 3100 Series Flame Detector (1 1/04) 1. If the relay closes (0 ohms on the meter) and the LEDs come “on” the detector is operating normally .
Model 3100 Series Flame Detector (1 1/04) Page: 11 Instruction Manual 6 .0 SPECIFICA TIONS SIERRA MONITOR CORPORA TION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment.
Instruction Manual Page: 12 Model 3100 Series Flame Detector (1 1/04) Figure A-2: Model 3100 Series Dimensions Figure A-1: Model 3100 Series Exploded V iew APPENDIX A.
Model 3100 Series Flame Detector (1 1/04) Page: 13 Instruction Manual Figure A-3: Model 3100 Series Common W iring Connections.
Instruction Manual Page: 14 Model 3100 Series Flame Detector (1 1/04) Figure A-4: Model 3100 Series (Enhanced) W iring Connections Factory jumpers are used to set NC or NO connections.
Model 3100 Series Flame Detector (1 1/04) Page: 15 Instruction Manual APPENDIX B T ABLES B.1 Dip Switch Settings B.1.1 Sensitivity Sensitivity SW1 SW2 Level 20 Foot O N O N 4 40 Foot OF F O N 3 60 Foot O N OF F 2 80 Foot OF F OF F 1 B.
Instruction Manual Page: 16 Model 3100 Series Flame Detector (1 1/04) B.2 Connectors B.2.1 Fire Relay Connector (J2) Fire Relay Description Pin 1 (Left Most) & Pin 2 Normally Open Side of Relay Pin 3 & Pin 4 (Middle) Common or Center Side of Relay Pin 5 & Pin 6 (Right Most) Normally Closed Side of Relay B.
Model 3100 Series Flame Detector (1 1/04) Page: 17 Instruction Manual B.3 V erify/Aux. Relay Configurations Model # V erify Relay Aux. Relay 3100-02 Open Contacts Closed Contacts 3100-03 Closed Contac ts Open Contacts 3100-04 Open Contacts Open Contacts 3100-05 Closed Contact Closed Contacts B.
Instruction Manual Page: 18 Model 3100 Series Flame Detector (1 1/04) B.7 Detector Response to Fuels T able Fuel Distance Fire Size Response T ime Heptane 80 Feet 1 Square Foot Less than 3 sec. Silane 5 0 Feet 18 inch jet Less than 3 sec. Hydrogen 15 Feet 18 inch jet Less than 5 sec.
Model 3100 Series Flame Detector (1 1/04) Page: 19 Instruction Manual APPENDIX C -- WIRING CONNECTIONS.
Instruction Manual Page: 20 Model 3100 Series Flame Detector (1 1/04) Index A Alarm Mode 2, 4 V erified 2 Auxiliary Relay 1, 2, 5, 6, 7 C Cleaning 8 Conduit 7, 11 Configuration Relay Control 4 Sensitivity 3 Switches 3, 4 V erify Control 4 Configuration Switches 5 Connection 7 Connector Aux.
Model 3100 Series Flame Detector (1 1/04) Page: 21 Instruction Manual T T esting 8 U Ultraviolet 3 V V erified Fire 2, 4, 5, 6 V erify Control 4 Relay 2, 4, 5, 6, 7, 15 V erify Control 6, 15 V ersions.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Sierra Monitor Corporation 3100-01 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Sierra Monitor Corporation 3100-01 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Sierra Monitor Corporation 3100-01, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Sierra Monitor Corporation 3100-01 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Sierra Monitor Corporation 3100-01, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Sierra Monitor Corporation 3100-01.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Sierra Monitor Corporation 3100-01. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Sierra Monitor Corporation 3100-01 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.