Manuel d'utilisation / d'entretien du produit FP-RLY-420 du fabricant National Instruments
Aller à la page of 12
FieldPoint ™ is a trademark of National Instruments Corporation. Product a nd company names mentioned herein are trad emarks or trade na mes of their resp ective companies. 321904B-01 © Copyright 1998, 1999 National Instruments Corp. All rights reserved.
FP-RLY-420 2 www.natinst.com module. The maximum number of terminal bases per bank multiplied by 1 watt is the total po wer the network module can supply . For e xample, an FP-1000 or FP-1001 can support nine terminal bases (9*1 W = 9 W). Next, refer to the specif ications section in the operating instructions for the I/O modules.
© National Instruments Corp. 3 FP-RLY-420 Field Wiring The terminal base has connections for each of th e eight relay channels and an extern al supply to po wer f ield de vices. Each relay channel of the FP-RL Y -420 has two terminals: N.O. (Normally Open) and I.
FP-RLY-420 4 www.natinst.com Figures 2a and 2b sho w examples of basic wiring connections. Figure 2. Basic Field Connection (T wo Channels Shown) Relay Output Circuit The outputs of the FP-RL Y -420 consist of Form A electromechanical relays. The po wer -up state is off (open) to ensure safe installation.
© National Instruments Corp. 5 FP-RLY-420 Figure 3 shows the diagram of one channel’ s relay output circuit. Figure 3. Relay Output Circuit The maximum switching capacity of each relay is 3 A up to 250 V A C or 35 VDC. T o switch greater DC v oltages, refer to Figure 4.
FP-RLY-420 6 www.natinst.com In addition, the FP-RL Y -420 contains its ow n internal protection MO V to preve nt e xcessi vely high voltage from being applied across the contacts.
© National Instruments Corp. 7 FP-RLY-420 Diode Circuit CR Circuits Varistor Circuit Diagram Notes Use in DC applications only . Compared to RC type, circuit delays release time (2 to 5 times v alues stated in catalog). For larger v oltages, use diode with rev erse breakdown 10 times circuit voltage and forward load ci rcuit.
FP-RLY-420 8 www.natinst.com In-Rush Current The type of load and its in -rush current characteristics, together with switching frequency , can cause contact welding. F or loads with in-rush current, measure the steady state current and in-rush current to determine the proper relay .
© National Instruments Corp. 9 FP-RLY-420 After the module has been inserted into a terminal base ( and po wer is applied), the green POWER indicator lights and the FP-RL Y -420 informs the network mod ule of its presence.
FP-RLY-420 10 www.natinst.com •D o not share the external supply voltages (V and C on the terminal base) with other de vices (including other FieldPoint de vices) unless those devices are also isolated from human contact.
© National Instruments Corp. 11 FP-RLY-420 Maximum switching frequenc y Mechanical ................... ............. . 20 operations per second Electrical..................................... 1 operation per second at maximum load Relays operate time.
Mechanical Dimensions Figure 6 sho ws the mechanical dimensions of the FP-RL Y -420 installed onto a terminal base. Dimensions are gi ven in inches [millimeters].
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté National Instruments FP-RLY-420 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du National Instruments FP-RLY-420 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation National Instruments FP-RLY-420, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le National Instruments FP-RLY-420 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le National Instruments FP-RLY-420, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du National Instruments FP-RLY-420.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le National Instruments FP-RLY-420. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei National Instruments FP-RLY-420 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.