12/29/2005 1 300 Series Media Converter & Industrial Ethernet Switches Installation Guide.
12/29/2005 2 Industrial Ethernet Switch In stallation Guid e 302MC-XX 302MCE-XX-YY 304TX 305FX-XX 305FXE-XX-YY 306TX 306FX2-XX 306FXE2-XX-YY 308TX Where: XX = ST or SC and YY = -15, -40, or -80.
12/29/2005 3 Copyright, © N-TRON Corp., 2005 820 S. University Blvd., Suite 4E Mobile, AL 36609 USA All rights reserved. Reproduction, adaptation, or translation without prior written permission from N-TRO N Corp. is prohibited, except as allowed under copyright laws.
12/29/2005 4 Safety Warnings ELECTRICAL SAFETY WARNING: Disconnect the power cable before removing the enclosure top. WARNING: Do not operate the unit with the top cover removed. WARNING: Do not work on equipment or cables during periods of lightning activity.
12/29/2005 5 Hazardous Location Installation Requirements 1. WARNING! Do not disconnect while circuit is live, unless area is known to be non-hazardous. 2. WARNING! Install only in accordance with Local & National Codes of Authorities Having Jurisdiction.
12/29/2005 6 300 Series Industrial Ethernet Switches The 300 Series Unmanaged Indu strial Ethernet Switches support high speed layer 2 switching between p orts.
12/29/2005 7 PACKAGE CONTENTS Please make sure the Ethernet Switch package contains the following items: 1. 300 Series Unit 2. N-Tron Product CD Contact your carrier if any items are damaged. INSTALLATION Read the following warning before beginning the installation: WARNING FXE units contain a class 1 laser.
12/29/2005 8 DIN-Rail Mounting Install the unit in a standard DIN-Rail. Recess the unit to allow at least 5” of horizontal clearance for fiber optic cable bend radius (2” for TX models).
12/29/2005 9 FRONT PANEL LNK Link LED for Fiber Optic Ports TX Fiber Optic Transmit Ports RX Fiber Op tic Receive Ports ACT Activity LED for Fiber Optic Ports RJ45 Ports Po rts 1-4 Auto sensing 10/100BaseT Connections Green LED lights when Power is connected NOTE: Each RJ45 data port has two LED’s for each connector.
12/29/2005 10 APPLYING POWER (Top View) Unscrew & Remove the DC Voltage Input Plug from the top header. Install the DC Power Cables into the Plug (observing polarity on unit). Plug the Voltage Input Plug back into the top header. All LED’s will flash ON Momentarily Verify the Power LED stays ON (GREEN).
12/29/2005 11 TROUBLESHOOTING 1. Make sure the (Power LED) is ON. 2. Verify that Link LED’s are ON for connected ports. 3. Verify cabling used between stations. 4. Verify that cabling is Category 5 (or greater) for 100Mbit Operation. 5. Verify TX is connected to far end RX and vise versa (fiber optic units only).
12/29/2005 12 KEY SPECIFICATIONS Physical Height: 3.98” (max.) Width: 2.01” (max.) Depth: 4.19” (max.) Weight: 0.75 lbs. Electrical Input Voltage: 10-30 VDC (Regulated) Input Current: 290mA max. @ 24VDC (Steady State) Inrush Current: 8.0A mp/0.6ms max.
12/29/2005 13 N-TRON Limited Warrant y N-TRON, Corp. warr ants to the end use r that this hardware product wil l be free from defects in workmanship a nd mate rials, under normal use and service, f or the applicable warranty period from the data o f purchase from N-TRON or its authorized reseller.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté N-Tron 300 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du N-Tron 300 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation N-Tron 300, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le N-Tron 300 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le N-Tron 300, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du N-Tron 300.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le N-Tron 300. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei N-Tron 300 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.