Liebert’s Load Bus Sync (LBS) Extender/Adapter for Dual Bus UPS is designed to extend the LBS function, up to 150m (492 ft.) between Liebert NX series uninterruptible power system (UPS) modules of a dual bus system (DBS). The adapter also enables a Liebert NX UPS to synchronize with other UPS models.
8.5” (216.2mm)
DY3-4ZPW
POWER ON
COM1
COM2
SWITCH
LED1
Figure 2 Horizontal installation
DY3-4ZPW
POWER ON
COM2 COM1
SWITCH
LED1
Figure 3 Vertical installation
General

! WARNING Installation by qualified electrical personnel only—hazardous voltage may be present at the UPS output connectors.
1. Connect the power cables of the adapter to the Phase A, Neutral and Ground output of each UPS. 2. Connect the LBS cable to COM1 of each LBS Signal Adapter. 3. Connect the other end of each LBS cable to X4 on the parallel board (UHW241M3) in the NX UPS. 4. Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal Adapter. 5. The switch of both LBS signal adapters should be in the right position (see Figure 4).

up to 492 ft. (150m)
Installation · Communication Cable

! WARNING Installation by qualified electrical personnel only—hazardous voltage may be present at the UPS output connectors.
1. Connect the power cables of the adapter to the Phase A, Neutral and Ground Output of each UPS. 2. Connect the LBS cable to COM1 of the LBS Signal Adapter connected to the Liebert NX. 3. Connect the other end of the LBS cable to X4 on the parallel board (UHW241M3) in the NX UPS. 4. Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal Adapter. 5. The switches of LBS signal adapters connected to the Liebert NX should be in the right position and the switches of LBS signal adapters connected to the non-NX UPS should be in the left position (see Figure 5).

up to 492 ft. (150m)

Power port Connect to Phase A, Neutral and Ground of output of UPS.
LED1 (red) Power LED. It illuminates when the power is on, turns off when the power fails.
COM1 LBS Signal interface. Connect to NX series UPS unit.
RS485 interface. Connect to other Signal Adapter. Green LED: Communication Power is OK. Yellow LED: Adapter is connected to Non NX series UPS.
SWITCH Switch to left: Connect to Non-NX series UPS unit. Switch to right: Connect to NX series UPS unit.

Installation · Communication Cable

Technical Support/Service
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Web Site www.liebert.com
Monitoring 800-222-5877 monitoring@liebert.com Outside the US: 614-841-6755
800-222-5877 upstech@liebert.com Outside the US: 614-841-6755
800-543-2378 powertech@liebert.com
Outside the United States
614-888-0246 Locations United States 1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Italy Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) +39 049 9719 111 Fax: +39 049 5841 257
© 2006 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
Asia 7/F, Dah Sing Financial Centre 108 Gloucester Road, Wanchai Hong Kong 852 25722201 Fax: 852 28029250
SL-25247 (2/06) Rev. 0
Emerson Network Power. The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
Connectivity DC Power Systems
Power Protection Integrated Cabinet Solutions
Precision Cooling Site Monitoring and Services
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2005 Emerson Electric Co.
Pages mentionnées dans ce manuel — fabricant, assistance et téléchargements.
Les utilisateurs et notre équipe répondent généralement sous 24 h — et votre question servira aussi aux suivants.
Soyez le premier à poser une question — d'autres utilisateurs ou notre équipe y répondront.