01/08 *2P0108* Page 1 505,201M *P505201M* RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE 2006 Lennox Industries Inc. Dallas, Texas, USA Table of Contents Shipping & Packing List 1 . . . . . . . . . . . . . . . . . . . . . . . . . Unit Dimensions 2 .
HORIZONTAL SUPPLY AIR OPENING BACK VIEW END VIEW TOP VIEW A B FRONT VIEW HORIZONTAL RETURN AIR OPENINGS (2) C L FG H J K D E E D DOWN−FLOW SUPPLY AIR OPENING DOWNFLOW RETURN AIR OPENING E D E D END .
Page 3 Parts Arrangement General These installation instructions are intended as a general guide only, for use by an experienced, licensed contractor (or equivalent). The 15CHAX units are single−package electric units designed for outdoor installation o n a rooftop or a slab.
Page 4 For installation on combustible material. WARNING Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance, or repair will expose you to fiberglass wool dust. Breathing this may cause lung cancer.
Page 5 Existing Common Vent Systems The 15CHAX packaged cooling units with auxiliary electric heat may replace an existing furnace which is being re- moved from a venting system commonly run with separate gas appliances. In this case, the existing vent system is likely to be too large to properly vent the remaining at- tached appliances.
Page 6 Filters Filters are not factory−supplied with the unit; however, optional internally installed filter kits are available. Filter kit 92 M 5 4 is used with 2, 2−1/2 and 3−ton units. Filter kit 92M55 is used with 3−1/2, 4 and 5−ton units.
Page 7 Unit must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electric Code, ANSI/NFPA No. 70 (latest edition) or CSA C22.2 Part 1 (latest edition). Power supply to the unit must comply with all applicable codes and NEC or CEC.
Page 8 Figure 7 15CHAX Series Packaged Electric Units Typical Wiring Diagram.
Page 9 Blower Control Board (A54) Electric shock hazard. Can cause injury or death. Before attempting to perform any service or m aintenance, turn the electrical power to unit OFF at disconnect switch(es).
Page 10 COOL The COOL jumper is used to determine the CFM during cooling operation. This jumper selection is activated for cooling when Y1 is energized. Th e blower motor runs at 80 percent of the selected air flow fo r the first 7−1/2 minutes of each cooling demand.
Page 11 System Operation Monitor (LSOM) The system operation monitor (A132) detects the most common fault conditions in the air conditioning system. Whe n an abnormal condition is detected, the module com- municates the specific condition through its ALERT and TRIP lights.
Page 12 Table 5 System Operation Monitor LED Troubleshooting Codes Status LED Condition Status LED Description Status LED Troubleshooting Information Green Power" LED ON Module has power 24VAC control power is present at the module terminal.
Page 13 Unit Start−Up and Operation Each 15CHAX packaged cooling unit is factory−charged with R−410A refrigerant. The compressor is hermetically sealed, internally sprung and base−mounted with rubber−insulated hold−down bolts. Pre−Start Check List: 1 − M a ke sure refrigerant lines do not rub against the cabi- net or each other.
Page 14 Condenser Fan Clearances The top of the condenser fan should be 1−1/2 inches from the bottom of the top grille. This dimension should be checked and the fan should be adjusted accordingly any time servicing of the outdoor fan system is required.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Lennox International Inc. 15CHAX Series c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Lennox International Inc. 15CHAX Series - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Lennox International Inc. 15CHAX Series, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Lennox International Inc. 15CHAX Series va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Lennox International Inc. 15CHAX Series, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Lennox International Inc. 15CHAX Series.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Lennox International Inc. 15CHAX Series. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Lennox International Inc. 15CHAX Series ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.