User Guide InRoom SC 50 Hz ACPSC3000 MOD E InRoom SC T EMP.
.
American Power Conversion Legal Disclaimer The information presented in this manual is not warranted by the Am erican Power Conversion Corpora- tion to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed operational and site specific development plan.
.
Content s InRoom SC 50 Hz User Guid e i General Information .................. ...................................... 1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Save these instruct ions .
InRoom SC 50 Hz User Guid e ii Display Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Display Screen Informati on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Function But ton and Indicato r Light Operati on .
1 InRoom SC 50 Hz User Guide General Information Overview Save these instructions This manual contains important instructions that must be followed during the installation of this equipment.
InRoom SC 50 Hz User Gu ide 2 Safety symbols that may be used in this manual Electrical Hazard: Indicates an electrical hazard which, if not avoided, could result in injury or death. Danger: Indicates a hazard which, if not avoided, could result in severe personal injury or substantial damage to product or other property .
3 InRoom SC 50 Hz User Guide Safety Electrical Hazard: Connect th e equipment to a 2 20-240V , 50Hz, three prong groun ded outlet (two poles plus a ground ). The use of a time-delay fu se or time-delay circuit bre aker is recommended. Conn ection to an y other power sou rce may result in a sh ock hazard o r damage to the cooling unit.
InRoom SC 50 Hz User Gu ide 4 S toring the Cooling Unit If the cooling unit will not be installed immediately , replace the packaging to protect from damage and dust.
5 InRoom SC 50 Hz User Guide Inspecting the Cooling Unit Y our cooling unit has been tested and inspected be fore shipment. T o ensure that the cooling unit has not been damaged during transit, carefully insp ect the cooling unit imme di ately upon receipt.
InRoom SC 50 Hz User Gu ide 6 T ools Required Inventory Phillips head scr ewdriver Item Description Item Description 1 Cooling unit 7 W rench (for casters) 2 Remote control 8 Drain hose 3 Ceiling adapter 9 Phillips head screw , ST4.2 x 9.5 (for hose clip) 4 Exhaust cap Exhaust hose : Hose Clip 5 Phillips h ead screw ST4.
7 InRoom SC 50 Hz User Guide Component Identification ACPSC3000 Item Description 1 Control panel 2 Air louver 3 Remote contr ol sensor 4 Remote contr ol / stora ge 5 Air filter / upper air intake (eva.
InRoom SC 50 Hz User Gu ide 8 Inst allation Location Requirement s Dimensions are shown in mm (in). > 500 (20) > 500 (20) na3362b MO DE InR oo m SC TE MP When deciding where to locate the cooling unit, consider cooling needs, air flow , and the location of the el ectrical outlet.
9 InRoom SC 50 Hz User Guide Exhaust Duct Assembly Dry Mode. Exhaust air must be allowed to return to the room in orde r for dehumidification to take place.
InRoom SC 50 Hz User Gu ide 10 Inst allation. Exhaust air can be vented to the outside th rough the ceiling. The cooling unit should be positioned a minimum of 500 mm (20 in) from any wall; either at the back or on the sides. In a dropped ceiling, the ceiling adapter ca n be installed in place of one of the ceiling tiles.
11 InRoom SC 50 Hz User Guide Window Inst allation. Exhau st air can be vented to the outside through a window . The ceiling adapter can be placed into a window op ening and the w indow can be pulled down to ho ld the panel in place. Install the exhaust hose to the adapter panel as done on the previous pa ge.
InRoom SC 50 Hz User Gu ide 12 Drain Kit Inst allation The InRoom SC utilizes evaporativ e technology , which eliminates the ne ed for a condensate tank. T o manage any excess condensation, a dr ain pan is located in the bottom of the unit. When the drain pan is full, a light will flash on the display and an al arm will sound to alert yo u.
13 InRoom SC 50 Hz User Guide Operation Control Panel Function Button Locations Item Function Description 1 Te m p Up and down arrow buttons adjust the thermostat. 2 Display interface LCD user interface di splays instructions and functions. 3 Mode selection Three mode control settings: Cool, Dehumi dify , and Fan.
InRoom SC 50 Hz User Gu ide 14 Display Interface Display Screen Information Item Function Description 1 Sleep mode indicator Sleep mode is an underco oling mode that is used during times of non- peak heat. Sleep mode is activat ed by setting the timer .
15 InRoom SC 50 Hz User Guide Function Button and Indicator Light Operation Cooling Mode. In Cool mode the unit attempts to bring the room air temperature down to the set temperature. The fan speed and temperature are adjusted in Cool mode. Note: The room temperature mu st be higher than the set temperature in order for the cooling mode to start.
InRoom SC 50 Hz User Gu ide 16 Remote Control Caution: 1. Do not drop the remote control. 2 . Do not leave the remote contro l exposed to direct sunlight. Note: 1.T o avoid interference, do not use the re mote control within one meter (3 ft) of a television or other electrical appliance 2.
17 InRoom SC 50 Hz User Guide Timer Operation. Set Timer without changing settings: Press the Time r button to show the remaining time on the display . Press the Hour button to change the adjust the de lay time from 0.5 to 18 hours then press Send . If the cooling unit is ON, when the timer coun ts down to 0, the cooling unit wi ll turn OFF .
InRoom SC 50 Hz User Gu ide 18 Battery Care The remote control require s two AAA (IEC R03) 1.5V batteries (not included). Remove the cover on the back of the remote control and inse rt the batteries with the (+) and (-) poles pointing in the proper direction.
19 InRoom SC 50 Hz User Guide Maintenance Electrical Hazard: Before performing maintenance on th e cooling unit: 1. T u rn the cooling unit of f. 2. Unplug the cooling unit. W arning: Damage to equipment may occur if: 1. Caustic substances are used to clean the cooling unit.
InRoom SC 50 Hz User Gu ide 20 Empty the condensate drain p an If the cooling unit is not routed to a permanent drain, allowing the drain pan to drain, the unit will shut down when the drain pan is full. See “Continu ous draining” on pa ge 12 for more information.
21 InRoom SC 50 Hz User Guide Caster replacement W arning: Tipping the cooling unit can cause damage. Raise the unit levelly at least 250 to 300 mm (10 to 12 in) to access the caster . Use the wrench that was shippe d with the unit. See “Inventory” on pa ge 6.
InRoom SC 50 Hz User Gu ide 22 T roubleshooting Problem Solution Unit does not run If you are attempting to run the cooling unit from the remote control, check that the batteries in the remote control are good. Check that the u nit is properly plugg ed into the power outlet.
23 InRoom SC 50 Hz User Guide S p are Part s List Part Number Description 0J-0H-0307 Ceiling exhaust ki t 0J-0H-0308 Exhaust duct kit 0J-870-16520 Swivel caster 0J-876-0317 Air filter.
InRoom SC 50 Hz User Gu ide 24 S pecifications Model APCSC3000 Net weight (Equipment only) - Kg (lb) 36 (79) Shipping weight - Kg (lb) 47 (102) Dimensions - H x D x W - mm (in) 876 x 370 x 455 (34 x 15 x 18 ) V oltage/Frequency/Phase 220/240 V AC - 50 Hz - 1 Ph Power input 1640 W Operating current 7.
.
9/2010 990-4223B-00 1 APC W o rldwide Customer Support Customer support for this or any other APC product is available at no char ge in any of the following ways: • V isit the APC W eb site to acce ss documents in the APC Knowledg e Base and to submit customer support requests.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté APC ACPSC3000 c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du APC ACPSC3000 - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation APC ACPSC3000, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le APC ACPSC3000 va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le APC ACPSC3000, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du APC ACPSC3000.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le APC ACPSC3000. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei APC ACPSC3000 ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.