Getting Results

Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
SHOCK HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
BURN HAZARD Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.


Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Pico controllers.
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
i Publication 1760-GR001C-EN-P - April 2005

Purpose of This Manual This manual provides a basic overview of Pico and an introduction to Pico programming. For a more detailed description of how to install and use your Pico Controller, refer to publication 1760-UM001, Pico Controller User Manual.
The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.
The following conventions are used throughout this manual:
Preface ii

Rockwell Automation offers support services worldwide, with over 75 Sales/Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.
Contact your local Rockwell Automation representative for:
If you need to contact Rockwell Automation for technical assistance, please review the Troubleshooting chapter in the Pico Controller User Manual first. Then call your local Rockwell Automation representative.
You can also contact Rockwell Automation Technical Support. To reach our Technical Support, go to the following website to find the support site for your region.
If you find a problem with this manual, or you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Rockwell Automation Control and Information Group Technical Communication, Dept. A602V P.O. Box 2086 Milwaukee, WI 53201-2086
or visit our internet page at: http://www.ab.com/pico or http://www.rockwellautomation.com
Preface iii

Preface iv

The electrical installation and commissioning work must only be carried out by suitably qualified personnel.
Do not work on the device when the power is turned on.
Observe the relevant safety regulations:
Pico is a compact, user-friendly and low-cost controller for simple control applications. Applications range from building and domestic automation to machine and plant control. Pico has built-in user-friendly operating elements and an LCD display.
Connect Pico and draw a circuit diagram on the display by pressing the buttons on the device. Pico works with make contacts, break contacts, and relays.
Enter a circuit diagram in Pico just like it is sketched on paper. Pico has basic and advanced functions for relays, time switches and contactors, among other functions. Make changes to the circuit by pressing the buttons on the device. Time consuming rewiring is not necessary.




Pico can be screwed to a mounting plate with the three or four feet which are included.
Click

28.8 V l = 3.3 mA/24 V I7, I8 = 2.2 mA/24 V 1 ≥ 8 V
l = 3.3 mA/12 V I7, I8 = 1.1 mA/12 V
0 ≤ 5 V
0 ≤ 4 V
BWB DWD
BWB: +24 V DWD: +12 V
0 V l7, l8
3.5 mm
COM
l1 I2 I3 I4 I5 I6 I7 I8
DWD: +12 V
Pico Inputs 1760-L12AWA-xx and 1760-L12NWA-xx
l1–I6 = 0.5 mA 240 V l1–I6 = 0.25 mA 120 V I7, I8 l = 6 mA 240 V l = 4 mA 120V
0 ≤ 40V
>1A
Ue = 120/240 V 50/60 Hz (90 to 264V) le = 40 mA 120V
5-7 lb-in.
3.5 mm
l1 I2 I3 I4 I5 I6 I7 I8
~ · 20 mA 240V


24 V 8 A 120 V 8 A 240 V 8 A
L1, L2, L3 (120/240 V ) + 24 V

Ue = 24 V (20.4–28.8 V ) Ie = 140 mA


l1–I6, I9 –I12 = 0.5 mA 240 V l1–I6, I9 –I12 = 0.25 mA 120 V I7, I8 l = 6 mA 240 V l = 4 mA 120 V
l1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12

1 2 1
24 V 8A 120 V 8 A 240 V 8A
L1, L2, L3 (120/240 V ) + 24 V



+24 V 0 V Q1 Q2 Q3 Q4 Q5 Q6 Q7

28.8 V R1–R12 = 3.3 mA; 24 V
Ue = 24 V (20.4–28.8 V ) Ie = 140 mA
R10 R9 R8 R7 R6 R5 R4 R3 R2 R1 NC NC R11 R12 +24V



1 2 1
24 V 8 A 120 V 8 A 240 V 8 A

1 2 1
S6 S5 S4 S3 S2 S1
24 V 8 A 120 V 8 A 240 V 8 A
1000 W
0 V , N
10 x 58 W
L1, L2, L3 (120/240 V)
+ 24 V
Pico Outputs 1760-OW8

10 000 000

Del Delete object in the circuit diagram
Alt Special functions in the circuit diagram
Choose contact numbers, values, times, etc.
Ok Next menu level, store your entry
Esc Previous menu level, cancel your entry

Show system menu (press both keys at the same time).
Cancel your entry since the last Ok.
MO
12:50

1...5..8
MO 02:00 ST
.2..5..8 RUN
Inputs 1, 5, 8 ON Outputs 2, 5, 8 ON
PASSWORD.. Current choice blinks in the Pico menu
PROGRAM...
RUN...
RUN...
PARAMETER
SET CLOCK..
SET CLOCK..
Main menu with and without password enabled

There are two different cursor types:
Full block navigation is shown as a flashing block:
TIME : 01 25
DAY : MO
Parameter change cursor flashes the selected parameter:
Flashing values/menus are highlighted in grey in this manual.
Each rung can hold four instructions, three input instructions (contacts) and one output instruction (coil or relay). Rungs are connected together through branches at the three positions between instructions. All programming of Pico can be done using the display and keypad.

Cursor button as input
Contact for internal marker bits
Contact for timer relay
Contact for counter relay
Contact for real time clock switch
Analog comparator contact Contact for text display (1)
: R S
Contact for jump (1)
Contact for internal marker relay or Expansion Output (1)
1st circuit connection 2nd circuit connection 3rd circuit connection
(1) For 1760-L18xxx only





PASSWORD...
INFO... SET CLOCK
PASSWORD...


PROGRAM å PARAMETER CLOCK OPRTNG MODE INTERFACE DELETE FUNCT
PROGRAM å PARAMETER å CLOCK å OPRTNG MODE å INTERFACE å DELETE FUNCT å
ENGLISH DEUTSCH FRANCAIS ESPANOL ITALIANO PORTUGUES NEDERLANDS SVENSKA POLSKI TURKCE CESKY MAGYAR
(1) Only for Pico 1760-L18xxx (2) Only for Pico 1760-L12BWB-xx, -L12DWD and -L18xxx.
Password Entry

Delete branch, contact, relay, or empty rung in the circuit diagram
Up/down arrows:
Left/right arrows:

When you power-up Pico for the first time, you are asked to select the menu language.
Use the up and down cursor buttons to select a language. Definitions of the language abbreviations are shown below.
Language LCD display Abbreviaton
Press Ok to confirm your choice or press Esc to exit the menu. The unit then switches to the status display. You can also change the language setting at a later date.
ENGLISH DEUTSCH FRANCAIS ESPANOL ITALIANO PORTUGUES NEDERLANDS SVENSKA POLSKI TURKCE CESKY MAGYAR
If you do not set the language, Pico displays this menu and waits for you to select a language every time the unit is powered up.

Set the Time Controllers with the “-NC” designation do not have real time clocks.
PROGRAM ...
I 1 2 3 4 5 6 7 8
1 ...5 ..8
MO
RE I P
PARAMETER
MO 02:00 ST
14:15
PROGRAM ...
.2 ..5 ..8 RUN
RUN
12-I/O Pico 18-I/O Pico
SET CLOCK
SET CLOCK
SUMMER TIME
Set Week Day and Time
SET CLOCK
WINTER TIME
SUMMER TIME
DAY : MO
TIME : 14:15

SUMMER TIME
Choose Pico Operating Mode
The two Pico operating modes are RUN and STOP.
The alternating RUN/STOP menu shows either RUN or STOP as follows:
SET CLOCK ..
It is possible to select the operating mode to be activated when Pico is powered up. You can choose start-up in “RUN” mode or in “STOP” mode through the System Menu.

Contacts
Contacts are used to modify the flow of current in the circuit diagram. Contacts in the circuit diagram are either make or break contacts. Make contacts are open when off (de-energized) and closed when on. Break contacts are closed when off and open when on.
Make contact; Open when off I, Q, M, A, C, T, P, D, S, :, R
Break contact; Closed when off I, Q, M, A, C, T, P, D, S, R
Pico works with different contacts, which can be used in any order in the contact fields of the circuit diagram.
Contact Type Make Contact
Controller Inputs I I I1 to I8 I1 to I12
0 signal I13 I13
Expansion Status – I14(3)
Short-circuit/overload I16 I15 to I16
Soft Inputs - Keypad P P P1 to P4 P1 to P4
Controller Outputs Q Q Q1 to Q4 Q1 to Q8
Internal Marker Bits M M M1 to M16 M1 to M16
Internal Marker Bits N N N1 to N16 N1 to N16
Counters C C C1 to C16 C1 to C16
Timers T T T1 to T16 T1 to T16
Real Time Clock(1)
1 to 8 1 to 8
Analog Setpoint Compare(2)
A A A1 to A16 A1 to A16
Text Display D D D1 to D16 D1 to D16
Expansion Outputs or Internal Marker Bits
S S S1 to S8 S1 to S8
Expansion Inputs R R – R1 to R12
R R – R15 and R16(3)

Contact Type Make Contact
Operating Hours Counter O O O1 to O4 O1 to O4
Year Time Switch Y Y Y1 to Y8 Y1 to Y8
Master Reset Z Z Z1 to Z3 Z1 to Z3
(1) Not available on “-NC” models.
(2) This applies only to the 1760-LxxBWB-xx and 1760-L12DWD.
(3) This applies only to 1760-L18xxx-EX models. R15 and R16 are used for expansion overload detection for the transistor expansion module, 1760-IB12XOB8, as described on page 9-4.
Pico has thirteen different types of relay for use in a circuit diagram.
Relay type Pico Symbol 1760-L12xxx 1760-L18xxx 1760-L20xxx Coil Function
Controller Outputs Q Q1 to Q8 Q1 to Q8 X –
Internal Marker Bits M M1 to M16 M1 to M16 X –
Internal Marker Bits N N1 to N16 N1 to N16 X –
Counters C C1 to C16 C1 to C16 X X
Timers T T1 to T16 T1 to T16 X X
Real Time Clock(1) – X
1 to 8 1 to 8
Operating Hours Counters O O1 to O4 O1 to O4 X X
Analog Setpoint Compare(2) A A1 to A16 A1 to A16 – X
Text Display D D1 to D16 D1 to D16 X X
Expansion Outputs or Internal Marker Bits
S S1 to S8 (as marker) S1 to S8 X –
Year Time Switch Y Y1 to Y8 Y1 to Y8 – X
Master Reset Z Z1 to Z3 Z1 to Z3 X –
(1) Not available on “-NC” models.
(2) This applies only to the 1760-LxxBWB-xx and 1760-L12DWD.
The switching behavior of these relays is set using coil functions and parameters. The coil functions and parameters are listed with the description of each function relay type.
Break Contact · 1760-L12xxx 1760-L18xxx 1760-L20xxx · Parameter

The options for setting output and marker relays are listed with the description of each coil function.
With Pico 1760-L12BWB-xx, 1760-L12DWD, and 1760-L18xxx, it is possible to save the actual values of markers, timers and counters in the event of a power failure. The quantities and values that may be retained are found in the following table.
For further information see the Pico Controller User Manual, publication number 1760-UM001B-EN-P.
Relay Type Pico Symbol
Internal Marker Bits M 4 (M13 to M16) 4 (M13 to M16)
Counters C 1 (C8) 4 (C5, C6, C7, C8)
Timers T 1 (T8) 2 (T7, T8)
Text Display D – 8 (D1 to D8)
1760-L12BWB-xx 1760-L12DWD 1760-L18xxx


Interconnect Contacts and Relays
S1 S2
M1 CR1
I 1 2 3 4 5 6 7 8
1 ...5 ..8
RE I P
MO 02:00 ST
14:15
PROGRAM...
.2 ..5 ..8 RUN
DELETE PROG
12-I/O Pico 18-I/O Pico

Draw Connection Between Contact and Relay Coil
I1-I2---
I1-I2---
Choose Relay Coil “Q1”
I1-I2---
I1-I2------{Q1
I1-I2------{Q1
I1-I2------{Q1

DELETE PROG
PROGRAM...
PROGRAM...
PARAMETER
SET CLOCK..
Pico now in RUN mode
PROGRAM...
PROGRAM...
STOP
PARAMETER
PARAMETER
SET CLOCK...
SET CLOCK...


Relay “Q1” picks up

I1-I2 {Q1 I 1 2 3 4 5 6 7 8
In the next example, a timing relay will be added to the circuit.
“S2” on

Timing relay with on-delay, with and without random switching
Timing relay with off-delay, with and without random switching
Timing relay, single pulse
Counter relay, up/down counter
Time switch, weekday/time (only in Pico models with clock)
Analog comparator relay (only in Pico models with 24V dc)
Timing Relay with on delay, with and without random switching

Timing Relay with Off-Delay, with and without Random Switching
With random switching, the relay contact switches randomly at any time up to the specified time value (shown shaded in figure).
Timing Relay, Single Pulse

Flash Frequency = 1/2 x setpoint
00.00 Switch Function
{ TRG
T1
RES
Parameter Display (Access Control)

8 6 4 2 0
Accumulated Value (setpoint = 6)
7 5 3 1
Counter Number Parameter Display (Access Control)

Example: Real Time Switch 1 switches on Monday through Friday between 6:30 and 9:00 and again between 17:00 and 22:30 (5:00 pm and 10:30 pm).
1 B +
D MO-FR
D MO-FR
06:30 09:00 ON OFF
17:00 22:30 ON OFF
Parameter Display for Real Time Switches
Parameter Display (Access Control)
Real Time Switch Number
Week Day(s) from - to
ON -- : --
OFF -- : --

Available functions:
The analog comparator can compare voltages from 0V to 10V (setpoints “0.0” to “10.0”).
Compare inputs I7 and I8.
A1
I8 4.2 V +
Parameter Display (Access Control)
Compare input “I7” to a setpoint.
A1
+ 3.2
Parameter Display (Access Control)

The Text Display is used to display eight freely definable messages on the Pico screen. Each text block displays up to 48 characters from the Pico display character set (ASCII + Pico special characters). If the Text Display is enabled, the text entered via PicoSoft is displayed. If several Text Displays are enabled, the next screen is displayed every 4 seconds. When Text Display D1 is enabled it stays displayed (fault indication).
Press Ok to switch to the menus at any time.
Current values or parameters of function relays can be displayed in lines 2 and 3.
Examples:
Fault Signals Time with Text Display
THE TIME
PUMP 1
IS
MOTOR
14:42
Display Current Value and Parameter of Timing Relay Display Counter Value
TIME RELAY 1
SETP99.00 S
ACTV 0042
ACTV 42.00 S
PCS
SETP0100

Conventional Circuit
Pico switches M1 with 10 seconds delay.
S1 S2
I1-I2----{M1
T1 CR1 10.0 sec
T1
M1
Select an Internal Marker Relay
Start Circuit from first example
Position cursor on “Q”
I1-I2----{M1
I1-I2----{M1
Select Marker Contact and Connect to New Output Relay
I1-I2----{M1 I1-I2----{M1 I1
I1-I2----{M1
M1------ {Q1
2 X 2 X 3 X

M1-------{Q1 M1-------TT1
I1-I2----{M1
M1-------TT1
Insert Timing Relay Contact
I1-I2----{M1 I1-I2----{M1
M1-------TT1
M1-------TT1
I1-I2----{M1
M1-------TT1
T1
Select Parameter Access
I1-I2----{M1
X S 00.00
M1-------TT1
{ TRG T1
T1
RES +
Ok · Ok · Ok

T1 X S 00.00 TRG
RES
RES
+ 2 X
T1 X S 10.00 TRG
RES
2 X back to circuit diagram
M1-------TT1 M1-------TT1
T1 T1
I1-I2----{M1
3 X 3 X
M1-------TT1
T1-------{Q1
Change Pico to RUN to test the program. Test the circuit as shown for the first example. To display and access the parameters for the timing relay and change the time value in RUN mode, position the cursor in the circuit diagram on the “T” of “T1” and press Ok.

“0” Make contact open, break contact closed, relay coil not energized
“1” Make contact closed, break contact open, relay coil energized
I1---------{Q1
Permanent Contact (Unconditional Rung)
--- Q1
I1 State Q1 Q1
0 to 1 0 1
0 to 1 1 0
Value Function · Negation (NOR) · Flip-Flop Output

I1-I2-I3-{Q1
0 1
1 0
0 1 0 0 0
1 1 0 0 0
0 0 1 0 0
1 0 1 0 0
0 1 1 0 0
1 0
I1--------{Q1
0 1
1 0 0 1 1
0 1 0 1 1
1 1 0 1 1
0 0 1 1 1
1 0 1 1 1
0 1
1 0
Exclusive OR Circuit (XOR)
I1-I2------{Q1
Series Connection (AND) · Parallel Connection (OR)

I1 I2 Contact Q1
Q1
0
1 0 1 1
0 0 1 1
Alternatively:
0 1 0 0
1 1 0 0
Motor Start/Stop Circuit · Coil Q1



Pico Interface Socket
The Pico interface socket, which is beneath a protective cap, accepts the optional Pico memory module, or connects Pico to a PC using the optional PC interface cable and the PicoSoft software. This allows you to copy the circuit diagrams to and from the PC and/or memory module.
Memory modules are available as an optional accessory. Each memory module can store a single Pico circuit diagram. Information stored on the memory module is non-volatile (the information is not lost when the power is turned off). The memory module can be used to make a backup copy of a program and/or to transfer it to another Pico controller.
Each memory module can hold one Pico program, up to 32K.
Each memory module stores:
1760-MM1 for all 1760-L12xxx controllers
1760-MM2 for the 1760-L18xxx controllers

3-2 Pico Interface Socket
The memory module and PC-cable socket are at the potential of L2. There is a danger of electric shock if L2 is not grounded. Do not make contact with electrical components under the socket cover.
You can only transfer the program from Pico to the memory module or vice versa in the STOP mode.
DEVICE - CARD: Transfer circuit diagram and parameter settings from Pico to the memory module.
CARD -> DEVICE
DELETE CARD
CARD - DEVICE: Transfer circuit diagram and parameter settings from the memory module to Pico.
DELETE CARD: Delete the contents of the memory module.
The following memory modules are available as Pico accessories.
Pico Controller Memory Module
1760-L12xxx 1760-MM1 (Series A only)
1760-L18xxx 1760-MM2 (Series A only)
Series B Pico Controllers 1760-MM2B
Programs including all relevant data can be transferred from the 1760-MM2B memory module to the Series B Pico Controllers. The existing 1760-MM1 and 1760-MM2 memory modules are Read-Only when used with Series B Pico Controllers. The 1760-MM2B memory module will not work with Series A Pico Controllers.

Pico Interface Socket 3-3
PicoSoft is an optional PC program that creates, stores, and manages Pico circuit diagrams. It transfers the circuit diagrams from the PC to Pico or vice versa using a special PC interface cable.
The PicoSoft software also includes extensive on-line Help.
To use the on-line Help, start PicoSoft and choose Contents in the Help menu. Context sensitive help is also available. Choose a menu item with the mouse and press F1 while keeping the mouse button pressed.
If you are using programming software to program the Pico controller, be sure that you are using the correct software version.
Find the Series Letter
The Series letter is printed on the side of the housing as shown.
You can download a free copy of PicoSoft version 6.1 from our web site. Go to http://www.ab.com/picosoft6
For PicoSoft Pro, please contact your Allen-Bradley Distributor or Rockwell Automation representative.
Download the Software

3-4 Pico Interface Socket

Specifications
Specification 1760-L12xxx 1760-L18xxx, 1760-L20xx 1760-IA12XOW6I, 1760-IA12XOW4I 1760-IB12XOB8 1760-IB12XOB8
Weight 200g (7 oz) 300g (10.6 oz) 70g (0.154 lb)
Ambient temperature, (operation) -25°C to + 55°C (-18°F to 131°F)
Storage Temperature -40°C to +70°C (-40°F to +158°F)
Operating Humidity 5 to 95%, non-condensing
Emitted interference, interference immunity
EN 55011, EN 55022, Class B
Standards and regulations Approvals
EN 50178 UL, CSA, CE, C-Tick
Catalog Number Inputs Outputs Line Power Real Time Clock
1760-L12AWA 8 (120/240V ac) 4 (relay) 100 - 240V ac Yes Yes No
1760-L12AWA-NC(1) No Yes
1760-L12AWA-ND(2) Yes No
1760-L18AWA 12 (120/240V ac) 6 (relay) Yes Yes
1760-L18AWA-EX(3) Yes Yes
1760-L18AWA-EXND(2)(3) Yes No
Display and Keypad · Analog

Catalog Number Inputs Outputs Line Power Real Time Clock
1760-L12BWB 8 (24V dc) 4 (relay) 24V dc Yes Yes 2 (0 to 10V dc)
1760-L12BWB-NC(1) No Yes
1760-L12BWB-ND(2) Yes No
1760-L12BBB 4 (MOSFET) Yes Yes 2 (0 to 10V dc)
1760-L12NWA 8 (24V ac) 4 (relay) 24V ac Yes Yes
1760-L12DWD 8 (12V dc) 12V dc Yes Yes
1760-L18BWB-EX(3) 12 (24V dc) 6 (relay) 24V dc Yes Yes
1760-L18BWB-EXND(2)(3) 6 (relay) Yes No 2 (0 to 10V dc)
1760-L20BBB-EX(3) 8 (MOSFET) Yes Yes 4 (0 to 10V dc)
1760-L20BBB-EXND(2)(3) 8 (MOSFET) Yes No
1760-L18DWD-EX(3) 12 (12V dc) 6 (relay) 12V dc Yes Yes
1760-L18DWD-EXND(2)(3) 6 (relay) 12V dc Yes No
1760-L18NWA-EX(3) 12 (24V ac) 6 (relay) 24V ac Yes Yes 4 (0 to 10V dc)
1760-L18NWA-EXND(2)(3) 12 (24V ac) 6 (relay) Yes No
(1) NC = no real time clock
(2) ND = no display
(3) EX = suitable for use with expansion modules

Catalog Number Inputs Outputs Line Power
1760-IA12XOW6I 12 (100 - 240V ac) 6 (relay) 100 - 240V ac
1760-IA12XOW4IF 12 (100 - 240V ac) 4 (relay) 100 - 240V ac
1760-IB12XOW6I 12 (24V dc) 6 (relay) 24V dc
1760-IB12XOB8 12 (24V dc) 8 (transistor) 24V dc
1760-OW2 - 2 (relay) 24V dc
1760-MM1 Memory Module for 12 I/O Pico Controller
1760-MM2 Memory Module for 18 I/O Pico Controller
1760-MM2B Memory Module for Pico Series B Controllers
1760-CBL-PM02 Programming Cable for Pico Controller
1760-RPLCONN Expansion Module Connector - included with expansion module. Catalog number listed is replacement part.
1760-SIM Input Simulator for 12 I/O 24V dc Pico Controller
1760-PICOSOFT Configuration Software for Pico Controllers.
D1760GR001BENP Pico Controllers Getting Results Manual, publication number 1760-GR001B-EN-P
D1760UM001BENP Pico Controllers User Manual, publication number 1760-UM001B-EN-P
Specifications A-3 · Catalog Number Description



A-4 Specifications

7.5 0.295"
90 3.54"
102 4.01"
110 4.33"
0.295"
35.5 1.4"
176-RM… 1760-DU… and 176-RM…
58 2.28"
36.2 1.43" 22.5 0.89" 22.5 0.89" 30 1.18"
20.5 0.81"
75 2.95"
43.2 1.7"
27.5 1.08"
Specifications A-5

A-6 Specifications

Rockwell Automation provides technical information on the web to assist you in using our products. At http://support.rockwellautomation.com you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:

Please contact your local Rockwell Automation representative for any technical support issues.
Rockwell tests all of our products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:

United States Contact your distributor. You must provide a Customer Support case number (see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for return procedure.

Publication 1760-GR001C-EN-P - April 2005 2 PN 40072-085-01(3) Supersedes Publication 1760-GR001B-EN-P - July 2001 Copyright © 2005 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.