® U.S. Registered Trademark Copyright © 1998 Honeywell Inc. • All Rights Reserved CHECKOUT AND TEST 65-0229-1 7800 SERIES Relay Modules This publication provides gener al checkout and troub leshooting procedures for the 7800 SERIES Rela y Modules.
2 7800 SERIES RELA Y MODULES 65-0229—1 T able 1. Chec kout Steps and Applicable 7800 Series Systems. Checkout Step Piloted Systems DSI Systems Infrared Flame Detectors Flame Rod Systems Ultraviolet .
7800 SERIES RELA Y MODULES 3 65-0229—1 b . On the subbase, jumper L1 to the ignition ter minal; ref er to the appropriate wir ing diagr am to deter mine the proper terminal. Disconnect the leadwire to the pilot valv e if it is connected to the same ter minal.
4 7800 SERIES RELA Y MODULES 65-0229—1 12. W ait about three minutes. Close the master s witch, open the manual fuel shutoff v alve(s), and tr y to light off the burner again. The first attempt may be required to purge the lines and bring sufficient fuel to the burner .
7800 SERIES RELA Y MODULES 5 65-0229—1 12. Close the master switch to recycle the b ur ner and stop the sequence in the PILOT period b y using the Run/ T est Switch. 13. Increase the pilot flame size by increasing its fuel flo w until a smooth main flame is accomplished.
6 7800 SERIES RELA Y MODULES 65-0229—1 IGNITION SP ARK RESPONSE TEST (ALL UL TRA VIOLET DETECT ORS) T est to mak e cer tain that the ignition spar k is not actuating the FLAME LED: 1. Close the pilot and main burner manual fuel shut-off valv e(s). 2.
7800 SERIES RELA Y MODULES 7 65-0229—1 6. Loss of flame during RUN. a. Open the main fuel manual shutoff valv e(s) and open manual pilot shutoff valv e(s). b . Depress the RESET button. c. Star t the system. Star t-up should be normal and the main b ur ner should light nor mally .
8 7800 SERIES RELA Y MODULES 65-0229—1 Table 2. Keyboard Display Module Sequence and Status Hold Messages. Sequence Status INITIATE mm:ss The Keyboard Display Module (KDM) indicates the burner statu.
7800 SERIES RELA Y MODULES 9 65-0229—1 T able 2. Keyboar d Display Module Sequence and Status Hold Messages (continued). Sequence Status If the relay module is in a PURGE HOLD status, the following .
10 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and F ault Message Summary . Fault Code System Failure Recommended Troubleshooting Fault 1 *No Purge Card* No card is plugged into the purge card slot. 1 . Make sure the purge card is seated properly.
7800 SERIES RELA Y MODULES 11 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). (continued) Fault Code System Failure Recommended Troubleshooting Fault 11 *Running ILK On* Running Interlock powered at improper sequence point. 1 . Check wiring to make sure that interlocks are connected properly between terminals 6 and 7.
12 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 18 *Flame Detected* Flame sensed when shutter is open and no flame is expected during PREPURGE.
7800 SERIES RELA Y MODULES 13 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 27 *Start Switch On* Start Switch was on during PREPURGE (RM7838A, RM7838B only). 1 . Start Switch held on too long.
14 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 32 *Airflow Switch* Combustion Airflow Interlock fault. 1 . Check wiring; correct any errors. 2 .
7800 SERIES RELA Y MODULES 15 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 45 *Low Fire Sw. Off* Low Fire Interlock switch failure to close or stay closed. 1 . Check wiring; correct any errors.
16 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 51 *Flame Too Strong* Flame signal value is too high to be valid. 1 . Make sure that flame detector and flame amplifier are compatible.
7800 SERIES RELA Y MODULES 17 65-0229—1 T ab le 3. Hold and F ault Message Summary (continued). (continued) Fault Code System Failure Recommended Troubleshooting Fault 68 *Preignition ILK* Preignition Interlock fault. 1 . Check wiring; correct any errors.
18 7800 SERIES RELA Y MODULES 65-0229—1 T able 3. Hold and Fault Message Summary (continued). Fault Code System Failure Recommended Troubleshooting Fault 109 *Call Service* Negative cycle test failed, earth ground absent or line voltage phasing improper.
7800 SERIES RELA Y MODULES 19 65-0229—1.
20 7800 SERIES RELA Y MODULES 65-0229—1 65-0229—1 G.R. Re v . 4-98 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524 Printed in U.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté 2nd Ave. 7800 Series c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du 2nd Ave. 7800 Series - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation 2nd Ave. 7800 Series, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le 2nd Ave. 7800 Series va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le 2nd Ave. 7800 Series, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du 2nd Ave. 7800 Series.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le 2nd Ave. 7800 Series. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei 2nd Ave. 7800 Series ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.