OPERATING AND MAINTENANCE MANUAL FOR COMMERCIAL HORIZONTAL CEILING-HUNG ELECTRIC WATER HEATER ELECTRIC HEATER COMPANY BASE MODELS “ HE and HSE ”.
2 HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203) 378-2659 FAX: (203) 378-3593 INTERNET: http://www.hubbellheaters.com/ -- IMPORTANT -- Always reference the f ull model num ber and serial number when calling the factory. WARNING / CAUTION 1.
3 TABLE OF CONTENTS SECTION TITLE PAG E # I GENERAL DESCRI P TI ON AND CONSTRUCTION 5 II INSTAL LATI ON 8 III S C H E D U LE D M A IN TE NANC E AND OPERATION 11 I V TROUBL ES HOOTI NG 13 V SERVICI NG .
4.
5 SECTION I - GENERAL DESCRIPTION AND CONST RUCTION GENERAL DESCRIPTION This book describes a packaged electric water heater that is a stationary, self-contained unit.
6 TEMPERATURE HIGH LIMIT SWIT CH As a safety device, a surface mounted hig h temperature cut-off switch with manual reset, factory set at 190° F is provided.
7 MAGNETIC CONTACTOR (HSE Models Only ) The magnetic contactor(s) is a heavy-duty resistiv e load ty pe rate d for 100,000 cy cle s. The contactor s upplies power to th e hea ti ng e lem en t( s) b as.
8 SECTION II – INSTALLATION WARNING / CAUTION DO NOT TURN ON THE ELECTRI C POWER SUPPL Y to this equipment until heate r is completely filled with water and all air has been re leased. If the heater is NOT fille d with water when the power is turned on, the heating elements will burn out.
9 PIP ING INSTALLATION NOTE: The most effect ive means for preventing deteriorat ion from accelerated corrosi on due to galva nic and stray curr ent is the installation of dielectric fittings/unions. The installation of the se fittings is the responsibility of the installing contractor.
10 FILLING THE HEATER 1. Completely close the drain va lve. 2. Open the highest hot water faucet to allow all air to escape from piping. 3. Open the valve to the cold water inlet and allow the hea t er and piping system to comple tely fill, as indicated by a steady flow of water from the open f aucet.
11 SECTION III - SCHEDULED MAINTE NANCE AND OPERATION WARNING / CAUTION Before performing any maintenance procedure, make certain power supply is OFF and cannot accidentally be turned on. MAINTENANCE AND OPERATION The water heater is automatic in its operation.
12 4. I nspect ceiling supports for tightness and/or damag e. 5. Check for loose electri cal connections. Tighten as necessary. ANNUAL INSPECTION 1. Flush tank as follows a. Shut off power supply . b. Close valve on hot water outlet piping. c. Open valve on drain piping.
13 SECTION IV – TROUBLESHOOTING Symptom Probable Cause Corrective Action / Remedy Circuit breaker tripped at source. Reset circuit breaker. High limit switch tr ipped. Reset hig h limit switch. Loose wires. Tighten wires. Torque screws per torque chart included in Section VI .
14 SECTION V - SERVICING & REPLACEMENT OF PARTS WARNING / CAUTION Before servicing or replacing any part make sure to turn the power supply switch to the OF F position. SURFACE TEMPERATURE HIGH LIMIT CUT -OFF 1. Disconnect power from unit. 2. Remove access cover.
15 HEATING ELEM ENT 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Attach hose to drain connection. 4. Lift manual release lever on relief valve to let air into sy stem or break union on outgoing water line. 5. Drain water from tank.
16.
17 IMMERSION THE RMOSTAT 1. Disconnect power from unit. 2. Remove access cover and locate t hermostat. 3. Remove high limit c over screw and cover. Cover Cover Screw 4. Disconnect the two (2) 14 gauge wires. Wires Capillary Tube 5. Remove capilla ry tube a nd bulb from thermowell.
18 MAGNETIC CONTACTOR 1. Disconnect power from unit. 2. Disconnect line and load wires to contactor. 3. Disconnect two (2) 14 gaug e control circuit wires. Control Wires Line Wires Load Wires 4. Loosen two (2) holding screws and remove contactor. Mounting Screws (Bottom screw not shown) 5.
19 RELIEF VALVE 1. Disconnect power from unit. 2. Shut off incoming water supply . 3. Lift test lever on relief valve to relieve pressure in tank. 4. Disconnect overflow piping. 5. Unscrew relief valve, remove assemb ly and repl ace with new one. 6. Connect overflow piping.
20 SECTION VI – MISCELL ANEOUS CHARTS AND FORMULAS FORMULAS 3-PHA S E ELEMENT CHA RT Power (kW) Resistance (Ohms) Element Part # 208V 240V 480V I mmersion L ength Hairpin 1 Φ 3 Φ DELTA 3 Φ WYE 2-38683N 2.5 3 4 13" 57.6 19.2 57.6 38.6 3-38683N 3 4 5 13" 43.
21 SINGLE P HASE ELEMENT CHART Power (Wat ts) Element Part # 120V 208V 240V 277V 480V I mmersion L ength Element Resistance (Ohms) CH-FO-358 ---- 3500 ---- ---- ---- 11 3/8" 12.36 CH-FO-408 ---- 4000 ---- ---- ---- 11 3/8" 10.82 CH-FO-508 ---- 5000 ---- ---- ---- 13 1/4" 8.
22 TORQUE VALUE S BOLT SIZE 18-8 S/S IN. - LB S . BRASS IN. - LB S . SI LI CON BRONZE IN. - LB S . ALUMI NUM 2024-T4 IN. - LB S . 316 S/S IN. - LB S . MONEL IN. - LB S . 4-40 5.2 4.3 4.8 2.9 5.5 5.3 4-48 6.6 5.4 6.1 3.6 6.9 6.7 5-40 7.7 6.3 7.1 4.2 8.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Hubbell Electric Heater Company HE c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Hubbell Electric Heater Company HE - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Hubbell Electric Heater Company HE, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Hubbell Electric Heater Company HE va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Hubbell Electric Heater Company HE, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Hubbell Electric Heater Company HE.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Hubbell Electric Heater Company HE. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Hubbell Electric Heater Company HE ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.