PRODUCT D A T A Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3 R4140G Flame Safeguard Programming Controls APPLICA TION The R4140G Flame Safeguard Programmers provide flame.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor , refer to the TRADELINE ® Catalog or price sheets for complete ordering number or specify order number .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 3 NOTE: Allowable inrush can be up to ten times the pilot duty rating. EXAMPLE: Pilot duty rating = 50 V A. At 120V , running current is: 50 120 = 0.42A . Maximum allowable inrush is ten times 0.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 4 Fig. 1. Mounting dimensions of the Q520A wiring subbase in in. (mm). 13/64 (5) DIAMETER (4) (FOR MOUNTING ON 4 X 4 [102 X 102] JUNCTION BOX.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 5 Accessories: W136A T est Meter (includes 1 17053 Meter Connector Plug); has SPL position with damping for testing self- checking flame detection systems. 1 17053 Meter Connector Plug (for older W136A models).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 6 OPERA TION Models with Preignition Interlocks Fig. 3 shows all contacts in the standby position (zero seconds). The opening and closing times are shown adjacent Fig. 3. Simplified schematic dia gram of R4140G1015 Programmer .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 7 Fig. 4. Timer sequence for R4140G1015 Programmer . Step-By-Step Operation (R4140G1015) Start And Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 8 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 9 Fig. 5. Simplified schematic dia gram of R4140G1106 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 10 Fig. 6. Timer sequence for R4140G1106 Programmer . Step-By-Step Operation (R4140G1106) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 11 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 If using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 12 Fig. 7. Simplified schematic dia gram of R4140G1049 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 13 Fig. 8. Timer sequence for R4140G1049 Programmer . M10055 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERRUPTED PILOT/IGN.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 14 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 15 Fig. 9. Simplified schematic dia gram of the R4140G1056 and R4140G1064 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 16 Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmer s. M10056 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTE.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 17 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or first stage fuel valve when using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 18 Fig. 11. Simplified schematic dia gram of R4140G1171, R4140G122 and R4140G1114 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 19 Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmer s. M10057 1 2 3 4 5 6 TERMINAL NUMBERS (CIRCLED). SLOPE DEPENDS ON MOTOR TIMING. TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 20 Ignition T rials 70 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (and terminal 7, main oil valve solenoid, if using direct spark ignition of oil).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 21 Fig. 13. Simplified schematic dia gram of R4140G1148 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT .
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 22 Fig. 14. Timer sequence for R4140G1148 Programmer . Step-By-Step Operation (R4140G1148) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 23 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 24 Fig. 15. Sample bloc k diagram of field wiring f or R4140G1007, R4140G1015 and R4140G1106 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 25 Fig. 16. Sample bloc k diagram of field wiring f or R4140G1049, R4140G1056, R4140G1064, R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmer s.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 26 Optional Hookups f or T wo-Sta ge Switching or Intermittent Pilot/Ignition (Nonmodulating Oil Burners) If modulation of the firing rate is.
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 27 M10061 TIMER SECONDS INTERRUPTED PILOT/IGNITION OR 1ST STAGE OIL VALVE 20 SECOND INTERRUPTED PILOT/IGNITION MAIN FUEL VALVE OR 2ND STAGE OIL VALVE 0 10 20 30 40 50 60 70 80 90 100 110 120 3 1 1 2 3 2 12 5 6 TERMINAL NUMBERS (CIRCLED).
R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 28 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Honeywell R4140G c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Honeywell R4140G - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Honeywell R4140G, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Honeywell R4140G va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Honeywell R4140G, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Honeywell R4140G.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Honeywell R4140G. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Honeywell R4140G ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.