Manuel d'utilisation / d'entretien du produit GSX130301B du fabricant Goodman Mfg
Aller à la page of 44
SS-GSX13 www .goodmanmfg.com 2/14 Supersedes 11/13 GSX1 3 S plit S yStem A ir C onditioner 13 Seer / 1½ t o 5 t onS C oolinG C Ap ACity : 1 8,000 - 60,000 BtU/ h Standard Featur es • R-410Ach.
P roduct S Pecifica tionS 2 www .goodmanmfg.com SS-GSX13 n omenClA tUre Brand Engineering * G Goodman ® Brand or Minor Revision Amana ® Distinctions ® Brand Engineering * Major Revision Product Cat.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 3 S peCifiCA tionS GSX13 0181E* GSX13 0241D* GSX13 0301B* GSX13 0361C* GSX13 0361E* GSX13 0421B* GSX13 0481B* GSX13 0601B* GSX13 0611A* Cap aciti.
P roduct S Pecifica tionS 4 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 301 81e* / CApf1 824B6dB Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 525 MBh 15.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 5 e Xp Anded C oolinG d A tA — GSX1 301 81e* / CApf1 824B6dB ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 525 MBh 16.
P roduct S Pecifica tionS 6 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 302 4 1d* / CA*f1 82 4*6d* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 700 MBh 20.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 7 e Xp Anded C oolinG d A tA — GSX1 302 4 1d* / CA*f1 82 4*6d* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 700 MBh 20.
P roduct S Pecifica tionS 8 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30 301B* / CA *f30 30*6d* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 945 MBh 26.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 9 e Xp Anded C oolinG d A tA — GSX1 30 301B* / CA *f30 30*6d* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 945 MBh 27.
P roduct S Pecifica tionS 10 www .goodmanmfg.com SS-GSX13 Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 32.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 11 Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1350 MBh 33.
P roduct S Pecifica tionS 12 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30 36 1e* / CA *f3 6 3 6*6d* Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1350 MBh 32.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 13 e Xp Anded C oolinG d A tA — GSX1 30 36 1e* / CA *f3 6 3 6*6d* ( Cont .) .
P roduct S Pecifica tionS 14 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30421B* / CA *f3 642*6B* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1225 MBh 36.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 15 e Xp Anded C oolinG d A tA — GSX1 30421B* / CA *f3 642*6B* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1225 MBh 37.
P roduct S Pecifica tionS 16 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30481B* / CA *f4860*6B* Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1400 MBh 40.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 17 e Xp Anded C oolinG d A tA — GSX1 30481B* / CA *f4860*6B* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1400 MBh 41.
P roduct S Pecifica tionS 18 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 30601B* / CA *f496 1*6A * Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1500 MBh 50.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 19 e Xp Anded C oolinG d A tA — GSX1 30601B* / CA *f496 1*6A* ( Cont .) Outdoor Ambient Temper a ture 65ºF 75ºF 85ºF 95ºF 105ºF 115ºF Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1500 MBh 51.
P roduct S Pecifica tionS 20 www .goodmanmfg.com SS-GSX13 e Xp Anded C oolinG d A tA — GSX1 306 1 1*/CA *f496 1*6d*+eep Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 1500 MBh 53.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 21 e Xp Anded C oolinG d A tA — GSX1 306 1 1*/CA *f496 1*6d*+eep ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper ature IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 1500 MBh 55.
P roduct S Pecifica tionS 22 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0181E* ACNF18XX16D* 16,800 12,800 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 23 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0181E* CAPT3131*4A* A*EH800603B*A* 18,000 13,700 14.
P roduct S Pecifica tionS 24 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0241D* CA*F1824*6D* A*VC950453BXB* 23,000 16,900 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 25 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* ACNF30XX16D* 27,600 20,800 13.
P roduct S Pecifica tionS 26 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* CA*F3131*6D*+MBVC1200**-1A* 28,400 21,400 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 27 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0301B* CAPT3743*4A*+MBVC1600**-1A* 28,200 21,200 14.
P roduct S Pecifica tionS 28 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0361E* CA*F3642*6D* G*VC950905CXB* 34,000 26,400 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 29 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0361E* CAPT3743*4A* A*VM961005DXB* 34,000 26,400 13.
P roduct S Pecifica tionS 30 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0421B* CA*F3642*6D*+EEP 40,000 30,600 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 31 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0421B* CHPF3642D6C* G*VC950905CXB* 40,000 30,600 13.
P roduct S Pecifica tionS 32 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0481B* CA*F4860*6D*+TXV A*VM960604CXB* 46,000 35,200 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 33 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0481B* CHPF4860D6D*+TXV A*EH801005C*A* 46,000 35,200 13.
P roduct S Pecifica tionS 34 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0601B* CAPT4961*4A* A*VC950915D XB* 55,000 39,000 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 35 Ahri r A tinGS ( Cont .) Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* ARPT48D14A* 54,500 37,400 13.00 11.00 1,500 5586528 ARPT60D14A* 55,000 37,600 13.
P roduct S Pecifica tionS 36 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CA*F4961*6D*+TXV G*VC80805C*B* 56,500 38,500 14.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 37 Ahri r A tinGS ( Cont .) See Notes on P age 38. Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CAPT4961*4A* G*VC950905CXB* 56,500 38,500 13.
P roduct S Pecifica tionS 38 www .goodmanmfg.com SS-GSX13 Ahri r A tinGS ( Cont .) Outdoor Unit Indoor Units Cooling Ra tings CFM AHRI # Coils/ Air Handlers Furnace s T ot al¹ Sens.¹ SEER² EER³ GSX13 0611A* CSCF4860N6D*+TXV GME951005DXA* 55,000 37,600 13.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 39 d imenSionS H W D Model Dimensions W” D” H” GSX130181E* 23 23 25¾ GSX130241D* 23 23 25¾ GSX130301B* 26 26 27½ GSX130361C* 29 29 28¾ .
P roduct S Pecifica tionS 40 www .goodmanmfg.com SS-GSX13 W irinG d iAGrAm — GSX1 3 01 81e USE N.E.C. CLASS 2 WIRE COMP ALTERNA TE DOUBLE POLE CONTACTO R ONL Y IO T1 M A I N R A U X 5 S SR SA 2 1 RC.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 41 W irinG d iAGrAm — GSX1 3 0(3 0-60)1B/C/e* ref er to the wiring diagram or the unit for the most up-t o-date wiring.
P roduct S Pecifica tionS 42 www .goodmanmfg.com SS-GSX13 ref er to the wiring diagram or the unit for the most up-t o-date wiring.
P roduct S Pecifica tionS SS-GSX13 www .goodmanmfg.com 43 W irinG d iAGrAm — GSX1 3 06 1 1* ref er to the wiring diagram or the unit for the most up-t o-date wiring.
P roduct S Pecifica tionS 44 www .goodmanmfg.com SS-GSX13 Goodman Manufacturing Company , L.P ., reserves the right to discontinue, or change at any time, specica tions or designs without notice or without incurring obligations. © 2014 • Goodman Manufacturing Company , L.
Un point important après l'achat de l'appareil (ou même avant l'achat) est de lire le manuel d'utilisation. Nous devons le faire pour quelques raisons simples:
Si vous n'avez pas encore acheté Goodman Mfg GSX130301B c'est un bon moment pour vous familiariser avec les données de base sur le produit. Consulter d'abord les pages initiales du manuel d'utilisation, que vous trouverez ci-dessus. Vous devriez y trouver les données techniques les plus importants du Goodman Mfg GSX130301B - de cette manière, vous pouvez vérifier si l'équipement répond à vos besoins. Explorant les pages suivantes du manuel d'utilisation Goodman Mfg GSX130301B, vous apprendrez toutes les caractéristiques du produit et des informations sur son fonctionnement. Les informations sur le Goodman Mfg GSX130301B va certainement vous aider à prendre une décision concernant l'achat.
Dans une situation où vous avez déjà le Goodman Mfg GSX130301B, mais vous avez pas encore lu le manuel d'utilisation, vous devez le faire pour les raisons décrites ci-dessus,. Vous saurez alors si vous avez correctement utilisé les fonctions disponibles, et si vous avez commis des erreurs qui peuvent réduire la durée de vie du Goodman Mfg GSX130301B.
Cependant, l'un des rôles les plus importants pour l'utilisateur joués par les manuels d'utilisateur est d'aider à résoudre les problèmes concernant le Goodman Mfg GSX130301B. Presque toujours, vous y trouverez Troubleshooting, soit les pannes et les défaillances les plus fréquentes de l'apparei Goodman Mfg GSX130301B ainsi que les instructions sur la façon de les résoudre. Même si vous ne parvenez pas à résoudre le problème, le manuel d‘utilisation va vous montrer le chemin d'une nouvelle procédure – le contact avec le centre de service à la clientèle ou le service le plus proche.